Installation Procedure
Electrical Wiring
Selection of size of power supply and interconnecting wires
Precautions for Electrical wiring
Electrical wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated
grip on the ends of the wires.
Use copper conductor only.
Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage
drop.)
DANGER OF BODILY INJURY OR DEATH
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC
CONNECTIONS.
GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
WARNING!
If the supply cord is damaged, it must be replaced by the manufacturer or itsservice agent or a similar qualified person.
If the fuse of control box is broken, please change it with the type of T25A/450VAC;
If the fuse of control PC board is broken, please change it with the type of T3.15A/250VAC. But for 28K,36K,48K(1
phase),48K(3 phase),60K, the type is T6.3A/250VAC.
The wiring method should be in line with the local wiring standard.
The power cable and connecting cable should be self-provided.
All the cables shall have got the European authentication certificate. During installation, when the connecting cables
break off, it must be assured that the grouding wire is the last one to be broken off.
The breaker of the air conditioner should be all-pole switch; and the distance between its two contacts should not be no
less than 3mm. Such means for disconnection must be incorporation in the fixed wiring.
The distance between its two terminal blocks of indoor unit and outdoor unit should not be over 5m. If exceeded, the
diameter of the wire should be enlarged according to the local wiring standard.
A leakage breaker must be installed.
The specification of power cable
Item
Model
Phase
Switch breaker
(A)
Circuit breaker
Overcurrent protector
rated capacity (A)
Power source
wire size
(minimum)
(mm
2
)
Switch
breaker(A)
Earth leakage breaker
Leak
current(mA)
30
1
40
30
6.0
40
3
30
4.0
30
20
30
28K
36K
48K(1 phase)
30
1
40
266
.0
40
24K
For models 28K,36K,48K(1 phase), the power cable should be H05RN-F 3G 6.0mm
2
.
For models 48K(3 phase), 60K,the power cable should be H07RN-F 5G 4.0mm
2
.
48K(3 phase)
60K
53
Содержание YHKJXH012BAM--FX
Страница 34: ...Model W D H L1 L2 L3 YHUJYH024BAR A X 860 308 730 633 113 5 340 YHUJYH024BAR A X 34...
Страница 36: ...YHFJZH012BAM AFX YHFJZH018BAM AFX YHFJZH024BAR AFX 3 33 100 22 1 1 0 1 0 0 33 36...
Страница 39: ...800 1320 830 1200 170 270 250 365 185 250 60 45 1105 4 758 2 15 88 YHGJXH048 60BAR GX YHEJXH028 36 48BAR GX 39...
Страница 93: ...YHUJYH024BAR A X power module YHUJYH028 36BAR A X power module 93...
Страница 94: ...YHUJYH028 36BAR A X filter board YHUJYH028 36 48BAR A X YHUJYH048BAS A X YHUJYH060BAS A X PCB 0151800054A 94...
Страница 95: ...YHUJYH048BAS A X YHUJYH060BAS A X power module YHUJYH048BAS A X YHUJYH060BAS A X filter board 95...
Страница 96: ...YHUJYH048BAR A X filter board YHUJYH048BAR A X power module 96...
Страница 111: ...5 2 Indoor unit 5 2 1 PCB 0151800106 for 28 36 48 60 indoor unit 111 YHDJXH018BAM GX...
Страница 151: ...151...