6.1.2. Diagnostic code for indoor unit
Flash times of
Timing LED(or
indoor PCB
LED4
)
Flash times of
Running LED(or
indoor PCB
LED3
)
Failure code(from
wired controller)
Failure
code(from panel
controller )
trouble shooting
Possible reasons
1
0
01
E1
Temperature sensor
Ta faulty
Sensor disconected
,
or broken
,
or
at wrong position
,
or short circuit
0
2
02
E2
Temperature sensor
Te faulty
Sensor disconected
,
or broken
,
or
at wrong position
,
or short circuit
0
4
04
F8
EEPROM WRONG
Faulty indoor unit PCB
0
7
07
E9
Abnormal
communication
between indoor and
outdoor units
Wrong connection
,
or the wires be
disconected
,
or wrong address
setting of indoor unit
,
or faulty power
supply or faulty PCB
8
0
NO EEROR
CODE DISPLAY
E8
Abnormal
communication
between indoor wired
controller and indoor
Abnormal communication between
indoor wired controller and indoor unit
PCB
0
12
0C
E0
unit PCB
Drainage system
abnormal
Pump motor disconnected
,
or at
wrong position
,
or the float switch
broken down
,
or the float switch
disconected
,
or at wrong position.
0
13
OD
EF
Zero cross sigal wrong Zero cross sigal detected wrong
0
14
0E
/
Indoor unit DC fan
motor abnormal
DC fan motor disconnected,or DC fan
motor broken,or circuit
broken
0
16
10
F3
Indoor mode abnormal
Different from outdoor unit mode
2
1
15
/
Outdoor unit abnormal
2
2
16
/
Outdoor unit abnormal
2
4
18
/
Outdoor unit abnormal
2
5
19
/
Outdoor unit abnormal
2
7
1B
/
Outdoor unit abnormal
2
8
1C
/
Outdoor unit abnormal
2
9
1D
/
Outdoor unit abnormal
3
0
1E
/
Outdoor unit abnormal
3
1
1F
/
Outdoor unit abnormal
3
2
20
/
Outdoor unit abnormal
3
3
21
/
Outdoor unit abnormal
3
5
23
/
Outdoor unit abnormal
3
6
24
/
Outdoor unit abnormal
3
7
25
/
Outdoor unit abnormal
3
8
26
/
Outdoor unit abnormal
3
9
27
/
Outdoor unit abnormal
4
3
2B
/
Outdoor unit abnormal
4
4
2C
/
Outdoor unit abnormal
4
7
2F
/
Outdoor unit abnormal
4
8
30
/
Outdoor unit abnormal
4
9
31
/
Outdoor unit abnormal
5
8
3A
/
Outdoor unit abnormal
5
9
3B
/
Outdoor unit abnormal
6
3
3F
/
Outdoor unit abnormal
6
4
40
/
Outdoor unit abnormal
1.. For the indoor failu
,
only running LED ON remote receiver will indicate.
2.. For the outdoor failu
,
timer LED and running LED will indicate.timer LED of remote receiver stands for ten's place,and running LED
stands for one's place.timer LED will flash firstly,2 seconds later,running LED will flash too. Afer that,4 seconds later,they will flash in
turns again.Flash times equals to the failure code of outdoor plus
20.For example,failure code of outdoor is 2,the indoor unit should display 22.As a result,timer LED flashes twice firstly,then running LED
flashes twice.
To get much more details of outdoor unit failure,Please refer to the the outdoor unit trouble shooting list
3.
Refer to the outdoor unit trouble
shooting
list
124
Содержание YHKJXH012BAM--FX
Страница 34: ...Model W D H L1 L2 L3 YHUJYH024BAR A X 860 308 730 633 113 5 340 YHUJYH024BAR A X 34...
Страница 36: ...YHFJZH012BAM AFX YHFJZH018BAM AFX YHFJZH024BAR AFX 3 33 100 22 1 1 0 1 0 0 33 36...
Страница 39: ...800 1320 830 1200 170 270 250 365 185 250 60 45 1105 4 758 2 15 88 YHGJXH048 60BAR GX YHEJXH028 36 48BAR GX 39...
Страница 93: ...YHUJYH024BAR A X power module YHUJYH028 36BAR A X power module 93...
Страница 94: ...YHUJYH028 36BAR A X filter board YHUJYH028 36 48BAR A X YHUJYH048BAS A X YHUJYH060BAS A X PCB 0151800054A 94...
Страница 95: ...YHUJYH048BAS A X YHUJYH060BAS A X power module YHUJYH048BAS A X YHUJYH060BAS A X filter board 95...
Страница 96: ...YHUJYH048BAR A X filter board YHUJYH048BAR A X power module 96...
Страница 111: ...5 2 Indoor unit 5 2 1 PCB 0151800106 for 28 36 48 60 indoor unit 111 YHDJXH018BAM GX...
Страница 151: ...151...