Read Before Installation
Maximum Operation Pressure
Applicable Refrigerants
3.4MPa
R22, R407C
4.15MPa
R410A
Use pipes that meet the local standards.
Use pipes made of phosphorus deoxidized copper.
Since the operation pressure of the units that use R410A is higher than that of the units for use with R22, use pipes with
at least the radial thickness specified in the chart below. (Pipes with a radial thickness of 0.7mm or less may not be used.)
Although it was possible to use type-O for pipes with a size of up to 19.05(3/4") with conventional refrigerants, use type-
1/2H pipes for units that use R410A.(Type-O pipes may be used if the pipe size is 19.05 and the radial thickness is 1.2t.)
The table shows the standards in Japan. Using this table as a reference, choose pipes that meet the local standards.
The flare machining dimensions for units that use R410A is larger than those for units that use R22 in order to increase
air tightness.
If a clutch type flare tool is used to machine flares on units that use R410A, make the protruding part of the pipe between
1.0 and 1.5mm. Copper pipe gauge for adjusting the length of pipe protrusion is useful.
Size(mm)
Radial Thickness(mm)
Size(inch)
Type
Type-O pipes
Type-1/2H or Hpipes
Piping Materials
Types of Copper Pipes (Reference)
The table shows the standards in Japan. Using this table as a reference, choose pipes that meet the local standards.
Piping Materials/Radial Thickness
Flare Machining (type-O and OL only)
Flare Machining Dimension(mm)
External dimension of pipes
Size
Dimension A
R410A
R22
6.35
9.52
12.7
15.88
19.05
1/4"
3/8"
1/2"
5/8"
3/4"
9.1
13.2
16.6
19.7
24.0
9.0
13.0
16.2
19.4
23.3
Flare Nut
Type-2 flare nuts instead of type-1 nuts are used to increase the strength. The size of some of the flare nuts have also
been changed.
Flare nut dimension(mm)
R410A(Type2)
R22(Type1)
6.35
9.52
12.7
15.88
19.05
1/4"
3/8"
1/2"
5/8"
3/4"
17.0
22.0
26.0
29.0
36.0
17.0
22.0
24.0
27.0
36.0
6.35
9.52
12.7
15.88
1/4''
3/8''
1/2''
5/8''
0.8t
0.8t
0.8t
1.0t
19.05
3/4''
1.0t
Dimension
A
External dimension of pipes
Size
Dimension B
Dimension B
45
Содержание YHKJXH012BAM--FX
Страница 34: ...Model W D H L1 L2 L3 YHUJYH024BAR A X 860 308 730 633 113 5 340 YHUJYH024BAR A X 34...
Страница 36: ...YHFJZH012BAM AFX YHFJZH018BAM AFX YHFJZH024BAR AFX 3 33 100 22 1 1 0 1 0 0 33 36...
Страница 39: ...800 1320 830 1200 170 270 250 365 185 250 60 45 1105 4 758 2 15 88 YHGJXH048 60BAR GX YHEJXH028 36 48BAR GX 39...
Страница 93: ...YHUJYH024BAR A X power module YHUJYH028 36BAR A X power module 93...
Страница 94: ...YHUJYH028 36BAR A X filter board YHUJYH028 36 48BAR A X YHUJYH048BAS A X YHUJYH060BAS A X PCB 0151800054A 94...
Страница 95: ...YHUJYH048BAS A X YHUJYH060BAS A X power module YHUJYH048BAS A X YHUJYH060BAS A X filter board 95...
Страница 96: ...YHUJYH048BAR A X filter board YHUJYH048BAR A X power module 96...
Страница 111: ...5 2 Indoor unit 5 2 1 PCB 0151800106 for 28 36 48 60 indoor unit 111 YHDJXH018BAM GX...
Страница 151: ...151...