rotor, compressor great vibration, compressor abnormal startup, state detecting curcuit abnormal or
compressor damaged.
The former twice failure can be resumed automatically, if outdoor board occurs this failure always, and
can not be resumed for a long time, that shows:
1. Power module (SPDU) damaged, please replace the power module, then re-wiring as per the wiring
diagram (70% possibility)
2. Short circuit in power board results in the power module damaged (15
%
possibility)
3. Damaged compressor results in this failure (10
%
possibility)
4. Main control board is faulty, replace it (5
%
possibility)
Trouble 10: High pressure failure
Reasons:
1. Over high system pressure results that the unit stop, and the compressor protection will work. The
failure can be resumed.
2. Pressure switch wire is not fixed well or in open circuit.
start
no
check if the connector
between pressure
switch and PCB is
fixed badly or damaged
no
no
no
yes
yes
yes
check if the 2 straight
lugs on the pressure
switch are in good
condition
if outdoor fan
motor cannot
startup normally
in cooling mode
replace main
control board
and check again
replace pressure switch
connector, shut off and
be electrified again,
re-check
replace pressure
switch connector, shut
off and be electrified
again, re-check
check if the
outdoor motor
has power input
replace outdoor
motor and check
again
Trouble 7: AC current over current protection or current transducer damaged, or compressor blocked
127
Содержание YHKJXH012BAM--FX
Страница 34: ...Model W D H L1 L2 L3 YHUJYH024BAR A X 860 308 730 633 113 5 340 YHUJYH024BAR A X 34...
Страница 36: ...YHFJZH012BAM AFX YHFJZH018BAM AFX YHFJZH024BAR AFX 3 33 100 22 1 1 0 1 0 0 33 36...
Страница 39: ...800 1320 830 1200 170 270 250 365 185 250 60 45 1105 4 758 2 15 88 YHGJXH048 60BAR GX YHEJXH028 36 48BAR GX 39...
Страница 93: ...YHUJYH024BAR A X power module YHUJYH028 36BAR A X power module 93...
Страница 94: ...YHUJYH028 36BAR A X filter board YHUJYH028 36 48BAR A X YHUJYH048BAS A X YHUJYH060BAS A X PCB 0151800054A 94...
Страница 95: ...YHUJYH048BAS A X YHUJYH060BAS A X power module YHUJYH048BAS A X YHUJYH060BAS A X filter board 95...
Страница 96: ...YHUJYH048BAR A X filter board YHUJYH048BAR A X power module 96...
Страница 111: ...5 2 Indoor unit 5 2 1 PCB 0151800106 for 28 36 48 60 indoor unit 111 YHDJXH018BAM GX...
Страница 151: ...151...