ELECTRICAL WIRING
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation to about 15/16"(25mm) to expose the
solid wire.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal board.
(3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the terminal board and tighthen securely with the terminal screw using a
screwdriver.
B.For strand wiring
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation to about 3/8"(10mm) to expose the
solid wire.
(2) Using a screwdriver, remove the terminal screw(s) on the terminal board.
(3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and tighten the terminal screw using a screwdriver.
A.For solid core wiring (or F-cable)
Screw with
special washer
Round
terminal
Wire
Terminal
board
Screw with
special washer
Round
terminal
Wire
A. Solid wire
Insulation
Loop
Strip 15/16"(25mm)
B. Strand wire
Round
terminal
Strip 3/8"(10mm)
After passing the connection cord and power cable through the insulation tube,
fasten it with the cord clamp.
Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
Fix connection cord and power cable at the cord clamp
Insulation tube
Cord clamp
Installation Procedure
CAUTION
Match the terminal block numbers and connection cord colors with those of the outdoor unit. Erroneous wiring may cause
burning the electric parts.
Connect the connection cords firmly to the terminal block. Imperfect installation may cause a fire.
Always fasten the outside covering of the connection cord with the cord clamp. If the insulator is chafed, electric leakage
may occur.
Always connect the ground wire.
Electrical requirement
Connect wiring to the terminals
(1) Remove the cord clamp.
(2) Process the end of the connection cords to the dimensions shown in wiring diagram.
(3) Connect the end of the connection cord fully into the terminal block.
(4) Fasten the connection cord with a cord clamp.
(5) Fasten the end of the connection cord with the screw.
Connect indoor unit and outdoor unit
28K 36K
48K 60K
Select wire sizes and circuit protection from table below. (This table shows 20m length wires with less than 2% voltage drop).
30
Item
Model
Phase
Switch breaker
(A)
Circuit breaker
Overcurrent protector
rated capacity (A)
Power source
wire size
(minimum)
(mm
2
)
1
40
30
6.0
Switch
breaker(A)
Earth leakage breaker
Leak
current(mA)
40
1
30
4.0
10
20
30
The Unit has default temperature compensation setting, please cancel it when floor standing installation.
72
Содержание YHKJXH012BAM--FX
Страница 34: ...Model W D H L1 L2 L3 YHUJYH024BAR A X 860 308 730 633 113 5 340 YHUJYH024BAR A X 34...
Страница 36: ...YHFJZH012BAM AFX YHFJZH018BAM AFX YHFJZH024BAR AFX 3 33 100 22 1 1 0 1 0 0 33 36...
Страница 39: ...800 1320 830 1200 170 270 250 365 185 250 60 45 1105 4 758 2 15 88 YHGJXH048 60BAR GX YHEJXH028 36 48BAR GX 39...
Страница 93: ...YHUJYH024BAR A X power module YHUJYH028 36BAR A X power module 93...
Страница 94: ...YHUJYH028 36BAR A X filter board YHUJYH028 36 48BAR A X YHUJYH048BAS A X YHUJYH060BAS A X PCB 0151800054A 94...
Страница 95: ...YHUJYH048BAS A X YHUJYH060BAS A X power module YHUJYH048BAS A X YHUJYH060BAS A X filter board 95...
Страница 96: ...YHUJYH048BAR A X filter board YHUJYH048BAR A X power module 96...
Страница 111: ...5 2 Indoor unit 5 2 1 PCB 0151800106 for 28 36 48 60 indoor unit 111 YHDJXH018BAM GX...
Страница 151: ...151...