manualshive.com logo in svg
background image

035-19699-001-B-0804

4

Unitary Products Group

If the furnace continues to lock out, a qualified service
technician should be called to determine the cause of
the problem.

   

EXPLAIN UNIT FUNCTION

When the system is functioning properly, show the
owner the location of all disconnect switches and the
thermostat. Explain how to start and stop the unit and
how to adjust temperature settings within the limitations
of the system. Advise that the flue exhaust hood sur-
face and the immediate area will experience high tem-
peratures during the heating cycle, and that all
unauthorized personnel and debris must be kept away
from this area.

GENERAL MAINTENANCE

In order to insure long and trouble free service from
your system, we recommend periodic inspection,
cleaning, lubrication and adjustment by your installing
Dealer/Contractor. Be sure to ask about this service.
For those who prefer to do-it-yourself, please follow the
instructions listed below to care for your system.

Snow or debris should not be allowed to accumulate in
or around the unit. Do not permit overhanging struc-
tures or shrubs to obstruct outdoor air discharge, com-
bustion air inlets or vent outlets on your unit. These
provide air for combustion and ventilation. Adequate air

is important to the safe and proper operation of the
unit.

HEATING SYSTEM INSPECTION

It is the owner's responsibility to insure that an annual
inspection of the entire heating portion of the unit is
made by a qualified service technician. This should
include inspection of the burner, heating element and
flue for any corrosion or soot accumulation which may
require cleaning and also checking of burner and con-
trols for proper operation.

In addition, at least once during the heating season,
the owner shall make a visual inspection of the flue out-
let for evidence of black soot or blockage of flue outlet
by leaves or other debris. If any soot is found, it is rec-
ommended a qualified service technician be called
immediately. If any blockage is found, it must be
cleared immediately.

Check for obvious signs of deterioration of the unit.
Check that the return and supply ducts attached to the
unit are sound and air tight. Check that the unit's physi-
cal support, concrete slab or roof curb, is sound and
not in need of repair. Make sure there are no gaps
between the roof curb and the unit where rain could
leak into the building.

Start the furnace. The vent motor should start, the igniter
will start to spark and ignite the pilot flame. After a short
delay the main burner should ignite. If it does not, con-
tact a qualified service technician for assistance. Check
the appearance of the main burner flame. Adjust burner
shutters so no yellow flame is observed in the heat
exchanger tubes. (See Figure 3.) If flame adjustment
cannot be made, obtain the assistance of a qualified ser-
vice technician and refer to the PILOT CHECKOUT and
BURNER AIR SHUTTER ADJUSTMENT sections in the
UNIT INSTALLATION INSTRUCTION.

BURNER AND PILOT CHECK

Periodically (at least annually at the beginning of each
heating season) make a visual check of the pilot and
main burner flame. If necessary, adjust main burner pri-
mary air shutters to give a distinct, sharp blue flame as
explained under BURNER AIR SHUTTER ADJUST-
MENT. If it is not possible to adjust for the proper flame,
the burners may need cleaning.

ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings exactly could result
in dangerous operation, serious injury, death or prop-
erty damage.

Improper servicing could result in dangerous opera-
tion, serious injury, death or property damage.

Before servicing, disconnect all electrical power 
to furnace.

When servicing controls, label all wires prior to 
disconnecting. Reconnect wires correctly.

Verify proper operation after servicing.

Prior to any of the following maintenance procedures,
shut off all power to the unit, to avoid personal injury.

FIGURE 3 - TYPICAL FLAME APPEARANCE

Содержание Thermostat

Страница 1: ...FORE CALLING A SERVICE PERSON 7 REPLACEMENT PARTS 8 The manufacturer recommends that the User read all sections of this manual and keep the manual for future reference FIRE OR EXPLOSION HAZARD Failure...

Страница 2: ...pply air duct Confirm the equipment is well supported and there are no signs of deterioration The manufacturer recommends that main burner ignition device and controls are inspected by a qualified ser...

Страница 3: ...his gas furnace is equipped with an automatic reset high temperature sensor or rollout switch which in the unlikely event of a sustained main burner flame rollout will shut off the flow of gas by clos...

Страница 4: ...s or other debris If any soot is found it is rec ommended a qualified service technician be called immediately If any blockage is found it must be cleared immediately Check for obvious signs of deteri...

Страница 5: ...s 7 Brush out the inside of the flue collector box and the flue baffles 8 Run the wire brush down the vent hoods from the flue collector end 9 If soot build up is particularly bad remove the vent moto...

Страница 6: ...RS Outdoor fan motors are permanently lubricated and require no maintenance Ventor motor is factory lubricated for an estimated 10 year life Indoor Blower Motor and Drive The indoor blower motor featu...

Страница 7: ...ly dirty a hose can be used to wash the coil from the inside out while brushing a soapy solution on the outside REGISTERS Supply and return air registers must be open when the unit is in operation Obs...

Страница 8: ...19036 000 DM180 035 19697 000 DH180 035 19413 000 DR180 SINGLE PACKAGE AIR CONDITIONER GAS ELECTRIC 20 TON REPLACEMENT PARTS FORM No RESPECTIVE MODEL No 035 18898 000 DJ240 1 035 19799 000 DJ240 2 03...

Отзывы: