035-19699-001-B-0804

Unitary Products Group

3

When the room thermostat is satisfied, the electrical
circuit to the gas valve is opened, closing off both main
burner and pilot gas simultaneously. If the pilot burner
should fail to light, contact your heating contractor or
gas utility for service to insure that proper operating
conditions are restored.

INPUT

The correct heat capacity of the furnace is regulated by
the burner orifices and the gas pressure. The proper
orifices are furnished but the gas pressure regulator
must be adjusted by the installer or gas utility service
technician.

OPERATING INSTRUCTIONS

TO SHUT DOWN THE FURNACE:

1.

Close the main gas shutoff valve(s).

2.

Turn off the electric power supply.

TO LIGHT THE FURNACE:

1.

Do not attempt to light manually.

2.

Open the main gas shutoff valve(s).

3.

Adjust the set point of the room thermostat above 
the temperature in the space.

4.

Turn on the electric power supply.

5.

The draft fan will operate. After an adequate purge 
time, the electric spark igniter will light the burners.

6.

The burners will extinguish and relight automati-
cally upon the demand of the room thermostat.

VENT SAFETY SYSTEM:

This gas furnace is equipped with an automatic reset
high temperature sensor or rollout switch which in the
unlikely event of a sustained main burner flame rollout
will shut off the flow of gas by closing the main gas
valve. The ignition modules will also be disabled, pre-
venting the flow of gas to the valves. The switch is
located inside the gas heat access panel above the
burner inlet. Flame rollout can be caused by blockage
of the power vent system, improper gas pressure or
adjustment. If this event occurs the furnace will not
operate properly, gas supply to the furnace should be
shut off and no attempt should be made to place the
furnace in operation. The system should be inspected
by a qualified service technician. Refer to Figure 2 for a
typical installation.

100% SHUT OFF:

The ignition modules are designed for 100% shut-off. If
the furnace fails to ignite within 85 seconds after a call
for heat, the flow of gas (including pilot) will be shut off
and the ignition module will lock out. The module can
be reset by:

A. Turning the system switch on the room thermostat 

to the “OFF” position and back to the “HEAT” posi-
tion.

B. Decreasing the set point of the room thermostat 

below the temperature in the conditioned space 
and returning it to its original setting.

C. Opening and closing the unit's main disconnect 

switch.

FIGURE 2 - TYPICAL INSTALLATION

Содержание Thermostat

Страница 1: ...FORE CALLING A SERVICE PERSON 7 REPLACEMENT PARTS 8 The manufacturer recommends that the User read all sections of this manual and keep the manual for future reference FIRE OR EXPLOSION HAZARD Failure...

Страница 2: ...pply air duct Confirm the equipment is well supported and there are no signs of deterioration The manufacturer recommends that main burner ignition device and controls are inspected by a qualified ser...

Страница 3: ...his gas furnace is equipped with an automatic reset high temperature sensor or rollout switch which in the unlikely event of a sustained main burner flame rollout will shut off the flow of gas by clos...

Страница 4: ...s or other debris If any soot is found it is rec ommended a qualified service technician be called immediately If any blockage is found it must be cleared immediately Check for obvious signs of deteri...

Страница 5: ...s 7 Brush out the inside of the flue collector box and the flue baffles 8 Run the wire brush down the vent hoods from the flue collector end 9 If soot build up is particularly bad remove the vent moto...

Страница 6: ...RS Outdoor fan motors are permanently lubricated and require no maintenance Ventor motor is factory lubricated for an estimated 10 year life Indoor Blower Motor and Drive The indoor blower motor featu...

Страница 7: ...ly dirty a hose can be used to wash the coil from the inside out while brushing a soapy solution on the outside REGISTERS Supply and return air registers must be open when the unit is in operation Obs...

Страница 8: ...19036 000 DM180 035 19697 000 DH180 035 19413 000 DR180 SINGLE PACKAGE AIR CONDITIONER GAS ELECTRIC 20 TON REPLACEMENT PARTS FORM No RESPECTIVE MODEL No 035 18898 000 DJ240 1 035 19799 000 DJ240 2 03...

Отзывы: