Unitary Products Group

5

CLEANING BURNERS

Remove them from the furnace as explained in
BURNER INSTRUCTIONS section in the Unit Installa-
tion Instructions. Clean burners with wire brush and
vacuum as needed.

CLEANING FLUE PASSAGES AND 
HEATING ELEMENTS

With proper combustion adjustment, the heating ele-
ment of a gas fired furnace will seldom need cleaning.
If the element should become sooted, it can be cleaned
as follows:

1.

Remove the burner assembly as outlined in 

“BURNER INSTRUCTIONS” of the unit installation 
instructions.

2.

Remove the unit roof from over the gas heat section.

3.

Remove the top plate and the top draft blower 
wheel from the upper draft blower housing.

4.

Remove the screws holding the top of the flue col-
lector box. Carefully remove the top of the flue col-
lector box without ripping the adjacent insulation. 
Then remove the center divider plate separating 
the upper and lower flue boxes.

5.

On the inside of the flue collector box, remove the 
flue baffles from the tube interiors. Note the last 
bend of the baffle fits tightly against the tube forc-
ing the end of the baffle to lock into the tube collar. 
This collar is formed when the tube is expanded 
into the end sheet. To remove, move the end of the 
baffle toward the center of the tube releasing the 
end of the baffle from the tube collar, then pull 
straight out of the tube. Refer to Figure 4.

6.

Using a wire brush on a flexible wand, brush out 
the inside of each heat exchanger from the burner 
inlet and flue outlet ends.

7.

Brush out the inside of the flue collector box and 
the flue baffles.

8.

Run the wire brush down the vent hoods from the 
flue collector end.

9.

If soot build-up is particularly bad, remove the vent 
motor and clean the wheel and housings. Run the 
wire brush down the flue extensions at the outlet of 
the vent housings.

10. After brushing is complete, blow all brushed areas 

with air or nitrogen. Vacuum as needed.

11. Replace parts in the order they were removed in 

Steps 1 thru 5.

12. When replacing the center and top of the flue col-

lector box, be careful not to tear the adjoining insu-
lation.

13. Ensure that all seams on the vent side of the com-

bustion system are air tight. Apply a high tempera-
ture (+500°F) sealing compound where needed.

AIR FILTERS

All units contain 2" filters. Filters can be installed in the
building at a suitable return air location if an econo-
mizer or outside air accessory is not used. Filters must
always be used. They should be inspected once a
month and thoroughly cleaned or replaced if it appears
they are beginning to accumulate excessive dirt. Filter
sizes and quantities are shown in the following table.

To install the filters, remove the filter access panel
located to the left of the condensate drain connection
as shown in Figure 5.

NOTE: 

Filters must be installed with “Air Flow” arrows 
pointing inward -- toward the indoor coil. In the 
event the spacers in the filter section are 
removed, they must be reinstalled in their origi-
nal position.

FIGURE 4 - TYPICAL FLUE BAFFLE INSTALLATION

THROWAWAY

FILTER

 SIZES

(Inches)

QUANTITY PER UNIT (Nom, Tons)

15 TON 

STD

& HIGH

EFF.

15, 20, 25

 TON REHEAT

20 TON

STD & HIGH

 EFF.

25 TON 

STD
EFF.

15 - 25

 TON 

ULTRA

HIGH

EFF.

12 x 24

-

-

12

12

16x 20

-

4

-

-

16 x 25

-

4

-

-

18 x 24

5

-

-

-

Содержание Thermostat

Страница 1: ...FORE CALLING A SERVICE PERSON 7 REPLACEMENT PARTS 8 The manufacturer recommends that the User read all sections of this manual and keep the manual for future reference FIRE OR EXPLOSION HAZARD Failure...

Страница 2: ...pply air duct Confirm the equipment is well supported and there are no signs of deterioration The manufacturer recommends that main burner ignition device and controls are inspected by a qualified ser...

Страница 3: ...his gas furnace is equipped with an automatic reset high temperature sensor or rollout switch which in the unlikely event of a sustained main burner flame rollout will shut off the flow of gas by clos...

Страница 4: ...s or other debris If any soot is found it is rec ommended a qualified service technician be called immediately If any blockage is found it must be cleared immediately Check for obvious signs of deteri...

Страница 5: ...s 7 Brush out the inside of the flue collector box and the flue baffles 8 Run the wire brush down the vent hoods from the flue collector end 9 If soot build up is particularly bad remove the vent moto...

Страница 6: ...RS Outdoor fan motors are permanently lubricated and require no maintenance Ventor motor is factory lubricated for an estimated 10 year life Indoor Blower Motor and Drive The indoor blower motor featu...

Страница 7: ...ly dirty a hose can be used to wash the coil from the inside out while brushing a soapy solution on the outside REGISTERS Supply and return air registers must be open when the unit is in operation Obs...

Страница 8: ...19036 000 DM180 035 19697 000 DH180 035 19413 000 DR180 SINGLE PACKAGE AIR CONDITIONER GAS ELECTRIC 20 TON REPLACEMENT PARTS FORM No RESPECTIVE MODEL No 035 18898 000 DJ240 1 035 19799 000 DJ240 2 03...

Отзывы: