Unitary Products Group

Slide filters all the way into the filter racks provided.
When more than one filter in a filter rack is required,
they must butt each other when sliding into position.
Replace the filter access panel.

ECONOMIZER

Even with good filters properly in place, the economizer
assembly will become dust laden after many months of
use. The entire assembly should be inspected annu-
ally. If the assembly is heavily coated with dust, it can
be brushed and cleaned with a vacuum. A common
aerosol contact cleaner will help remove excess accu-
mulation.

After the dust and debris is removed, a silicon based
spray lubricant should be applied to each of the gears
used to connect and ensure proper alignment of the
damper blades.

BLOWER ASSEMBLY

Even with good filters properly in place, blower wheels
and motors will become dust laden after many months
of operation. The entire blower assembly should be
inspected annually. If the motor and wheel are heavily
coated with dust, they can be brushed and cleaned
with a vacuum cleaner.

BLOWER SHAFT BEARING

Blower shaft bearings should be inspected on a
monthly basis. At a minimum, the bearings should be
relubricated every 6 months using a lithium-based
grease (NLGI grade 2) recommended for ball bearing
service.

MOTORS

Outdoor fan motors are permanently lubricated and
require no maintenance.

Ventor motor is factory lubricated for an estimated 10
year life.

Indoor Blower Motor and Drive - The indoor blower
motor features ball bearings that do not require peri-
odic lubrication. Periodic lubrication of the motor and
bearings can extend the life of components but is
optional.

If desired, every three years, using a low pressure
grease gun, pump grease into the bearing grease fit-
ting until grease just begins to show at the seals. Do
not over lubricate. Use any lithium base grease recom-
mended for ball bearing service.

FIGURE 5 - END VIEW LESS FILTER ACCESS 

PANEL

Perform all maintenance operations on the
damper assembly with power discon-
nected. Do not clean or lubricate with the
unit in operation.

15, 17.5, 20, 25 TON ULTRA-HIGH EFFICIENCY UNITS

25 TON STANDARD EFFICIENCY

15 TON

(2) 18" X 24"

FILTERS

20 TON

15,20,25 TON REHEAT

20 TON

15,20,25 TON REHEAT

(4) 16" X 20"

FILTERS

(4) 16" X 25"

FILTERS

(3) 18" X 24"

FILTERS

15 TON

(6) 12" X 24"

FILTERS

(6) 12" X 24"

FILTERS

15, 20, 25 TON REHEAT UNITS

15 & 20 TON STANDARD & HIGH EFFICIENCY UNITS

INDOOR COIL

CONDENSATE

DRAIN

CONNECTION

CONDENSATE

DRAIN

CONNECTION

INDOOR COIL

Excessive lubrication may accelerate the
accumulation of dust.

Perform all maintenance operations on the
blower motor with electric power discon-
nected from the unit. Do not attempt to lubri-
cate bearings with the unit in operation.

Damage can occur if the bearings are overlu-
bricated. Use grease sparingly.

Содержание Thermostat

Страница 1: ...FORE CALLING A SERVICE PERSON 7 REPLACEMENT PARTS 8 The manufacturer recommends that the User read all sections of this manual and keep the manual for future reference FIRE OR EXPLOSION HAZARD Failure...

Страница 2: ...pply air duct Confirm the equipment is well supported and there are no signs of deterioration The manufacturer recommends that main burner ignition device and controls are inspected by a qualified ser...

Страница 3: ...his gas furnace is equipped with an automatic reset high temperature sensor or rollout switch which in the unlikely event of a sustained main burner flame rollout will shut off the flow of gas by clos...

Страница 4: ...s or other debris If any soot is found it is rec ommended a qualified service technician be called immediately If any blockage is found it must be cleared immediately Check for obvious signs of deteri...

Страница 5: ...s 7 Brush out the inside of the flue collector box and the flue baffles 8 Run the wire brush down the vent hoods from the flue collector end 9 If soot build up is particularly bad remove the vent moto...

Страница 6: ...RS Outdoor fan motors are permanently lubricated and require no maintenance Ventor motor is factory lubricated for an estimated 10 year life Indoor Blower Motor and Drive The indoor blower motor featu...

Страница 7: ...ly dirty a hose can be used to wash the coil from the inside out while brushing a soapy solution on the outside REGISTERS Supply and return air registers must be open when the unit is in operation Obs...

Страница 8: ...19036 000 DM180 035 19697 000 DH180 035 19413 000 DR180 SINGLE PACKAGE AIR CONDITIONER GAS ELECTRIC 20 TON REPLACEMENT PARTS FORM No RESPECTIVE MODEL No 035 18898 000 DJ240 1 035 19799 000 DJ240 2 03...

Отзывы: