background image

035-17480-000 Rev. A (800)

22

Unitary Products Group

ADJUSTMENT OF MANIFOLD GAS PRESSURE

Manifold gas pressure may be measured by two different pro-
cedures. It may be measured with the burner box cover in
place or it may be measured with the burner box cover
removed. Follow the appropriate section, 1a or 1b in the
instructions below.

1.

Read the inlet gas pressure using either of the two meth-
ods below.

a.

Reading the gas pressure with the burner box
cover in place 
- Disconnect the pressure reference
hose from the right side of the burner box. Using a
tee fitting and a short piece of hose, connect the
negative side of the manometer to the burner box
pressure reference port. Connect the positive side
of the manometer to the adapter previously installed
in the gas valve ( Refer to Figure 27.)

b.

Reading the gas pressure with the burner box
cover removed 
- Remove the screws securing the
burner box front cover plate. Remove the cover. It is
gasketed and may stick in place. Connect the posi-
tive side of the manometer to the adapter previously
installed in the gas valve as shown in Figure 27.
There will be no second connection to the manome-
ter as it will reference atmospheric pressure.

The regulated outlet pressures, both low and high, have been
calibrated at the factory. Additional pressure adjustment
should not be necessary. If adjustment is necessary, set to
the following specifications. After adjustment, check for gas
leakage.

Low Outlet Pressure Adjustment

1.

Turn off all electrical power to the system at main fuse or
circuit breaker.

2.

Attach a manometer to the outlet pressure tap of the
valve.

3.

Turn on power and energize main and redundant (P.M.)
solenoids. Do not energize HI terminal.

4.

Remove low adjustment seal screw Figure 25 on
page 21.

5.

To increase outlet pressure, turn the 3/32” socket set
screw below the low adjustment seal screw clockwise.

To decrease outlet pressure, turn the set screw counter-
clockwise. Adjust regulator until pressure shown on
manometer matches the pressure specified on the appli-
ance rating plate.

6.

Replace low adjustment seal screw and tighten securely.
Cycle the valve several times to verify regulator setting.

7.

Remove manometer and replace the outlet pressure tap
plug.

High Outlet Pressure Adjustment

1.

Turn off all electrical power to the system at main fuse or
circuit breaker.

2.

Attach a manometer to the outlet pressure tap of the
valve.

3.

Turn on power and energize main and redundant (P.M.)
solenoids as well as the HI terminal.

4.

Remove high adjustment seal screw to expose the 3/32”
socket set screw (refer to Figure 26).

Be sure to relight any gas appliance that were
turned off at the start of this input check.

Natural Gas

Propane Gas

Low Fire

1.6 IWG

6.5 IWG

High Fire

3.5 IWG

10.0 IWG

TABLE 6 : GAS RATE (CUBIC FEET PER HOUR)

SECONDS FOR ONE

REVOLUTION

SIZE OF TEST DIAL

1/2

CUBIC FOOT

1

CUBIC FOOT

10

180

360

12

150

300

14

129

257

16

113

225

18

100

200

20

90

180

22

82

164

24

75

150

26

69

138

28

64

129

30

60

120

32

56

113

34

53

106

36

50

100

38

47

95

40

45

90

42

43

86

44

41

82

46

39

78

48

37

75

50

36

72

52

35

69

54

34

67

56

32

64

58

31

62

60

30

60

Содержание P*XU/G9D-UP

Страница 1: ...TART UP AND ADJUSTMENTS 20 ACCESSORY CONNECTIONS 24 FURNACE ACCESSORIES 25 FILTER PERFORMANCE 26 OPERATION AND MAINTENANCE 26 TROUBLESHOOTING 30 FURNACE CONTROL DIAGNOSTICS 30 WIRING DIAGRAM UPFLOW MO...

Страница 2: ...THREE TWO PIPE SYSTEM USING COMBUSTION AIR FROM A VENTILATED ATTIC SPACE 18 HORIZONTAL VENT APPLICATIONS 18 CONDENSATE PIPING 19 SAFETY CONTROLS 19 START UP AND ADJUSTMENTS 20 IGNITION SYSTEM SEQUENCE...

Страница 3: ...ransit There are no shipping or spacer brackets which need to be removed NOTES CAUTIONS WARNINGS The installer should pay particular attention to the words NOTE CAUTION and WARNING NOTES are intended...

Страница 4: ...size as determined using the appropriate tables in Appendix G of the above codes SPECIFIC UNIT INFORMATION LIMITATIONS LOCATION This furnace should be installed in accordance with all national and lo...

Страница 5: ...leaning Eighteen 18 inches at the side where access is required for passage to the front when servicing or for inspection or replacement of flue vent connections 8 Where it will not interfere with the...

Страница 6: ...ust comply with the National Electrical Code NFPA 70 latest edition For altitudes above 2 000 ft reduce capacity 4 for each 1 000 ft above sea level Refer to Form 650 78 N1 1V Wire size based on coppe...

Страница 7: ...ls NOTE In order to achieve the airflow indicated in the table it is recommended those applications over 1800 CFM use return air from two sides one side and the bottom or bottom only For single return...

Страница 8: ...cation outside the utility room or basement For further details consult Section 5 3 Air for Combustion and Ventilation of the National Fuel Gas Code ANSI Z223 1 or CAN CGA B149 1 or 2 Installation Cod...

Страница 9: ...for 63 F 35 C rise wire when installed in accordance with instructions Refer the rating plate or Physi cal and Rating Data Tables in these instructions for specific furnace electrical data Provide a p...

Страница 10: ...mostat to the terminal board on the ignition module Connect Class 2 control wiring for single stage thermostat or for two stage thermostat Refer to Figure 7 for single stage and Fig ure 8 for two sta...

Страница 11: ...e observed Long radius elbows are required for all units 1 Long radius elbows are required for all units 2 Elbows are assumed to be 90 degrees Two 45 degree elbows count as one 90 degree elbow 3 Elbow...

Страница 12: ...e grade and anticipated snow depth 1 ft Above grade when adjacent to public walkway 7 ft From electric gas meters regulators and relief equipment min horizontal distance 4 ft Does not apply to multipl...

Страница 13: ...ional Clearance FIGURE 12 Horizontal Termination Configuration With Horizontal Extension VENT OVERHANG COMBUSTION AIR ELBOW PARALLEL TO WALL 12 SEPARATION BETWEEN BOTTOM OF COMBUSTION AIR AND BOTTOM O...

Страница 14: ...fined space is an area with less than 50 cubic feet per 1000 Btu hr input rating for all appliances installed in that area The following must be considered to obtain proper air for combustion and vent...

Страница 15: ...all be permitted to be waived where special engineering approved by the authority having jurisdiction provides an adequate supply of air for combus tion ventilation and dilution of flue gases Combusti...

Страница 16: ...nted vertical terminals may be field fabricated Standard PVC SRD fittings may be used Terminal configuration must comply as detailed in this section When selecting the locations for vent termination t...

Страница 17: ...ater tight seal 7 Support the vent piping such that it is angled 1 4 per lin ear foot so that condensate will flow back towards the furnace Piping should be supported with pipe hangers to prevent sagg...

Страница 18: ...Table 5 on page 16 Follow all notes installation procedures and required materials in the METHOD TWO ONE PIPE SYSTEM on page 14 to install the vent pipe from the unit to the outdoors VENT TERMINATION...

Страница 19: ...quiva lent pipe be field installed as drain pipe The condensate piping may be tied together with the air conditioning con densate drain if the air conditioning condensate drain line is trapped upstrea...

Страница 20: ...furnace the gas piping may be full of air In order to purge this air it is recommended that the ground union be loosened until the odor of gas is detected When gas is detected immediately retighten th...

Страница 21: ...more accurate input rate adjustment To calculate a meter correction factor use the following formula Using the information from above calculate the gas input rat ing by multiplying the number of cubi...

Страница 22: ...djustment 1 Turn off all electrical power to the system at main fuse or circuit breaker 2 Attach a manometer to the outlet pressure tap of the valve 3 Turn on power and energize main and redundant P M...

Страница 23: ...crease the rise All direct drive blowers have multi speed motors The blower motor speed taps are located in the control box in the blower compartment Refer to Figure 28 and the unit wiring label to ch...

Страница 24: ...ion of the circulating blower NOTE EAC and HUM power leads are provided in the junction box for easier installation FIGURE 27 Upflow Models P XU G9D UP Reading Gas Pressure GAS VALVE U TUBE MANOMETER...

Страница 25: ...5 1075 1060 1045 1030 1000 960 910 830 755 LOW 805 795 785 770 755 730 700 655 615 565 80 75 1600 C HIGH 1940 1905 1870 1815 1760 1700 1620 1555 1460 1305 MED 1400 1390 1380 1370 1355 1320 1285 1255 1...

Страница 26: ...urnace with 2 return openings and operating on high speed blower it is found that total sys tem static is 0 58 w c To determine the system airflow com plete the following steps 1 Obtain the airflow va...

Страница 27: ...035 17480 000 Rev A 800 Unitary Products Group 27 FIGURE 29 Sequence Timing For 50a51 243 Control...

Страница 28: ...eriod the gas valve is de energized the ignitor is turned off and the 50A51 control goes into the retry sequence The retry sequence provides a 120 second wait with inducer inter purge following an uns...

Страница 29: ...l the filter simply reverse this procedure Lubrication Blower motors in these furnaces are permanently lubricated and do not require periodic oiling BLOWER CARE Even with good filters properly in plac...

Страница 30: ...valves in the gas line to the furnace must be open 3 Make sure all wiring connections are secure 4 Review the sequence of operation Start the system by setting the thermostat above the room temperatur...

Страница 31: ...used by a number of problems blocked vent or chimney faulty inducer cracked pressure switch hose 7 FLASH This fault code indicates that flame could not be established This no light condition occurred...

Страница 32: ...NACE RELAY IGNITER GV GRD DOOR SWITCH N O SW ELEMENTARY DIAGRAM POWER SUPPLY 120 1 60 SEE NOTE 1 GRD DS C NO LS1 C 1LP COM 120V 24V SEC PRI 1T 40VA VENTOR MOTOR HSI NOTES LEGEND DOT DELAY ON TIMER FUS...

Отзывы: