background image

58MTA

Deluxe 4-Way Multipoise 2-Stage

Direct-Vent Condensing Gas Furnace

Service and Maintenance Instructions

For Sizes 060-120, Series 110

ELECTRICAL SHOCK, FIRE, OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death, or property dam-
age.
Improper servicing could result in dangerous operation,
serious injury, death, or property damage.
- Before servicing, disconnect all electrical power to furnace.
- When servicing controls, label all wires prior to

disconnecting. Reconnect wires correctly.

- Verify proper operation after servicing.

The ability to properly perform maintenance on this equip-
ment requires certain knowledge, mechanical skills, tools, and
equipment. If you do not possess these, do not attempt to
perform any maintenance on this equipment other than those
procedures recommended in the User’s Manual. FAILURE
TO FOLLOW THIS WARNING COULD RESULT IN
POSSIBLE DAMAGE TO THIS EQUIPMENT, SERIOUS
PERSONAL INJURY, OR DEATH.

Never store anything on, near, or in contact with the furnace,
such as:
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum

cleaners, or other cleaning tools.

2. Soap powders, bleaches, waxes or other cleaning com-

pounds, plastic or plastic containers, gasoline, kerosene,
cigarette lighter fluid, dry cleaning fluids, or other volatile
fluids.

3. Paint thinners and other painting compounds, paper bags,

or other paper products.

A failure to follow this warning can cause corrosion of the
heat exchanger, fire, personal injury, or death.

NOTE:

Read the entire instruction manual before starting the

installation.

This symbol

indicates a change since the last issue.

TABLE OF CONTENTS

SAFETY CONSIDERATIONS .....................................................1

GENERAL......................................................................................2

ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS........2

CARE AND MAINTENANCE.....................................................2

Cleaning and/or Replacing Air Filter.......................................3
Blower Motor and Wheel Maintenance ...................................3
Cleaning Burners ......................................................................4
Cleaning Heat Exchangers........................................................5

Primary Heat Exchangers....................................................5
Secondary Heat Exchangers................................................6

Flushing Collector Box and Drainage System ........................6
Servicing Hot Surface Igniter...................................................7
Electrical Controls and Wiring.................................................8
Checking Heat Tape Operation (If Applicable) ......................8
Winterizing................................................................................9

WIRING DIAGRAM...................................................................10

TROUBLESHOOTING ...............................................................10

Status Codes............................................................................10
Component Test ......................................................................11

SAFETY CONSIDERATIONS

Recognize safety information. This is the safety-alert symbol

.

When you see this symbol on the furnace and in instructions or
manuals, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.

Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified
service agency personnel should install, repair, or service
heating equipment. Untrained personnel can perform basic
maintenance functions described in User’s Information
Manual such as cleaning and replacing air filters.

All other operations must be performed by trained and qualified
service agency personnel. When working on heating equipment,
observe precautions in the literature, on tags, and on labels
attached to or shipped with the unit and other safety precautions
that may apply.

Follow all safety codes including the National Fuel Gas Code
(NFGC) NFPA 54-2002/ANSI Z223.1-2002 in the USA; the
National Standard of Canada, Natural Gas and Propane Installation
Code CSA B149.1-00 (NSCNGPIC) in Canada; and the Installa-
tion Standards, Warm Air Heating and Air Conditioning Systems

A93040

Visit www.carrier.com

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

4

Tab

6a 8a

PC 101

Catalog No. 535-80098

Printed in U.S.A.

Form 58MTA-4SM

Pg 1

11-02

Replaces: 58MTA-3SM

Содержание 58MTA Series

Страница 1: ...g Collector Box and Drainage System 6 Servicing Hot Surface Igniter 7 Electrical Controls and Wiring 8 Checking Heat Tape Operation If Applicable 8 Winterizing 9 WIRING DIAGRAM 10 TROUBLESHOOTING 10 Status Codes 10 Component Test 11 SAFETY CONSIDERATIONS Recognize safety information This is the safety alert symbol When you see this symbol on the furnace and in instructions or manuals be alert to t...

Страница 2: ...e to the control Tools held in a person s hand during grounding will be satisfactorily discharged 3 After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity for example DO NOT move or shuffle your feet DO NOT touch ungrounded objects etc 4 If you touch ungrounded objects recharge your body with ...

Страница 3: ...ectrical supply to furnace 2 Remove filter cabinet door 3 Slide filter out of cabinet 4 If equipped with permanent washable filter clean filter by spraying cold tap water through filter in opposite direction of airflow Rinse filter and let dry Oiling or coating of the filter is not recommended 5 If equipped with factory specified disposable media filter replace only with a factory authorized filte...

Страница 4: ... assembly on blower shelf 12 Reinstall condensate trap and tubing if previously removed a Reinstall condensate trap in hole in blower shelf b Connect condensate trap drain tubes See Fig 8 or tubing diagram on main furnace door for proper tube location 1 Connect 1 tube blue or blue and white striped from collector box 2 Connect 1 tube violet or unmarked from inducer housing 3 Connect 1 tube relief ...

Страница 5: ...rs get an accumulation of light dirt or dust on the inside they may be cleaned by the following procedure NOTE If the heat exchangers get a heavy accumulation of soot and carbon both the primary and secondary heat exchangers should be replaced rather than trying to clean them thoroughly due to their intricate design A build up of soot and carbon indicates that a problem exists which needs to be co...

Страница 6: ...s can be inspected by removing the inducer assembly See Flushing Collector Box and Drainage System section for details on removing inducer assembly Step 5 Flushing Collector Box and Drainage System 1 Turn off gas and electrical supplies to furnace 2 Remove main furnace door 3 Disconnect inducer motor and pressure switch wires or connectors 4 Disconnect pressure switch tubes 5 Disconnect vent pipe ...

Страница 7: ...e Trap on LEFT Side Optional CAP COLLECTOR BOX DRAIN TUBE BLUE PLUGGEDEND COLLECTORBOX DRAIN TUBE BLUE WHITE STRIPED COLLECTOR BOX TUBE GREEN COLLECTOR BOX TUBE PINK COLLECTOR BOX EXTENSIONTUBE CONDENSA TE TRAP INDUCERHOUSINGDRAINTUBE VIOLET COLLECTOR BOX EXTENSIONTUBE Condensate Trap on RIGHT Side PLUG CAP COLLECTOR BOX DRAIN TUBE BLUE WHITE STRIPED CONDENSA TE TRAP COLLECTOR BOX EXTENSIONTUBE CO...

Страница 8: ...tion NOTE If the polarity is not correct the STATUS LED on the furnace control board will flash rapidly and prevent the furnace from operating The control system also requires an earth ground for proper operation of the furnace control board and flame sensor The 24 v circuit contains an automotive type 3 amp fuse located on the control See Fig 12 Any direct shorts of the 24 v wiring during install...

Страница 9: ...GND GND FIELD 24 V WIRING FIELD 115 208 230 460 V WIRING FACTORY 24 V WIRING FACTORY 115 V WIRING 208 230 OR 460 V THREE PHASE 208 230 V SINGLE PHASE WHT BLK WHT BLK W W1 W2 Y Y2 G NOTES 1 Connect Y terminal as shown for proper operation 2 Some thermostats require a C terminal connection as shown 3 If any of the original wire as supplied must be replaced use same type or equivalent wire 115 V FUSE...

Страница 10: ... and all blower off delays must be completed to view previous codes To retrieve previous codes remove 1 of the red main limit or flame rollout switch wires 1 to 4 sec until the LED light goes out then reconnect it Do not leave red wire disconnected for longer periods of time as the control will assume an overtemperature condition exists and will respond with blower operation This places the contro...

Страница 11: ...R lead from furnace control 3 Manually close blower door switch 4 For approximately 2 sec short jumper the COM 24v terminal on control to the TEST TWIN 3 16 in quick connect terminal on control until LED turns off Remove jumper from termi nals See Fig 12 NOTE If TEST TWIN and COM 24v terminals are jumpered loner than 2 sec LED will flash rapidly and ignore status code retrieval request Component t...

Страница 12: ... EMITTING DIODE FOR STATUS CODES AMBER LGPS LOW GAS PRESSURE SWITCH SPST N O LPS LOW HEAT PRESSURE SWITCH SPST N O LS LIMIT SWITCH AUTO RESET SPST N C OL AUTO RESET INTERNAL MOTOR OVERLOAD TEMPERATURE SWITCH N C PCB PRINTED CIRCUIT BOARD CONTROL PL1 12 CIRCUIT PCB CONNECTOR PL2 3 CIRCUIT PCB HSI IDM CONNECTOR PL3 6 CIRCUIT ICM MOTOR CONNECTOR NOT SHOWN PL4 4 CIRCUIT IDM CONNECTOR PL5 2 CIRCUIT HSI...

Страница 13: ...ITCH DID NOT CLOSE OR REOPENED If open longer than five minutes inducer shuts off for 15 minutes before retry If opens during blower on delay period blower will come on for the selected blower off delay Check for Excessive wind Restricted vent Defective inducer motor Low inlet gas pressure if LGPS used Defective pressure switch Low inducer voltage 115 VAC Inadequate combustion air supply Proper ve...

Страница 14: ...ducer will run for the entire component test The HSI blower motor LO HEAT speed HI HEAT speed and COOL speed will run for 10 15 seconds each Gas valve and humidifier will not be turned on When the blower motor is turned OFF the inducer will be switched to low speed for 10 seconds Was there a previous status code other than 11 Is door switch closed Is there 115V going to switch Replace door switch ...

Страница 15: ...ION PROVING FAILURE If flame is not sensed during the trial for ignition period the control will repeat the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected blower off delay Check the following items first before proceeding to the next step Gas valve turned off Manual shut off valve Green Yellow w...

Страница 16: ...31 58mta4sm Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 6a 8a PC 101 Catalog No 535 80098 Printed in U S A Form 58MTA 4SM Pg 16 11 02 Replaces 58MTA 3SM ...