Record the code and repeat the disconnect and reconnect of the red
wire, recording each code until code 11 is displayed indicating no
additional codes. After the last code is displayed or after 2 minutes
in the code recall mode the control will return to normal standby
mode.

Step 2—Component Test

NOTE:

The furnace control component test allows all compo-

nents to run for a short time; except the gas valve and humidifier
terminal HUM are not energized for safety reasons. The EAC-1
terminal is energized when blower is energized. This feature helps
diagnose a system problem in case of a component failure. The
component test feature will not operate if any thermostat signal is
present at control and not until all time delays are completed.

To Begin Component Self-Test:

Blower access panel door switch opens 115-v power to
control board. No component operation can occur. Caution
must be taken when manually closing this switch for service
purposes. Failure to follow this warning could result in
electrical shock, personal injury, or death.

1. Remove blower access door.

2. Disconnect thermostat R lead from furnace control.

3. Manually close blower door switch.

4. For approximately 2 sec, short (jumper) the C

OM

-24v terminal

on control to the TEST/TWIN 3/16-in. quick-connect terminal
on control until LED turns off. Remove jumper from termi-
nals. (See Fig. 12.)

NOTE:

If TEST/TWIN and C

OM

-24v terminals are jumpered

loner than 2 sec, LED will flash rapidly and ignore status code
retrieval request.

Component test sequence for 2-stage furnace is as follows:

a. LED will display previous status code 4 times.

b. Inducer motor starts on high-speed and continues to run

until Step g of component test sequence.

c. Hot surface igniter is energized for 15 sec, then off.

d. Blower motor operates on LO-HEAT speed for 10 sec.

e. Blower motor operates on HI-HEAT speed for 10 sec.

f. Blower motor operates on COOL speed for 10 sec.

g. Inducer motor goes to low-speed for 10 sec, then stops.

5. Reconnect R lead to furnace control, remove tape from blower

door switch, and re-install blower door.

6. Operate furnace per instruction on outer door.

7. Verify furnace shut down by lowering thermostat setting

below room temperature.

8. Verify that furnace restarts by raising thermostat setting above

room temperature.

Fig. 14—Inducer Housing Drain Tube Cap

A99118

Fig. 15—Funnel in Drain and Antifreeze

Running Through Trap

A99119

11

Содержание 58MTA Series

Страница 1: ...g Collector Box and Drainage System 6 Servicing Hot Surface Igniter 7 Electrical Controls and Wiring 8 Checking Heat Tape Operation If Applicable 8 Winterizing 9 WIRING DIAGRAM 10 TROUBLESHOOTING 10 Status Codes 10 Component Test 11 SAFETY CONSIDERATIONS Recognize safety information This is the safety alert symbol When you see this symbol on the furnace and in instructions or manuals be alert to t...

Страница 2: ...e to the control Tools held in a person s hand during grounding will be satisfactorily discharged 3 After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity for example DO NOT move or shuffle your feet DO NOT touch ungrounded objects etc 4 If you touch ungrounded objects recharge your body with ...

Страница 3: ...ectrical supply to furnace 2 Remove filter cabinet door 3 Slide filter out of cabinet 4 If equipped with permanent washable filter clean filter by spraying cold tap water through filter in opposite direction of airflow Rinse filter and let dry Oiling or coating of the filter is not recommended 5 If equipped with factory specified disposable media filter replace only with a factory authorized filte...

Страница 4: ... assembly on blower shelf 12 Reinstall condensate trap and tubing if previously removed a Reinstall condensate trap in hole in blower shelf b Connect condensate trap drain tubes See Fig 8 or tubing diagram on main furnace door for proper tube location 1 Connect 1 tube blue or blue and white striped from collector box 2 Connect 1 tube violet or unmarked from inducer housing 3 Connect 1 tube relief ...

Страница 5: ...rs get an accumulation of light dirt or dust on the inside they may be cleaned by the following procedure NOTE If the heat exchangers get a heavy accumulation of soot and carbon both the primary and secondary heat exchangers should be replaced rather than trying to clean them thoroughly due to their intricate design A build up of soot and carbon indicates that a problem exists which needs to be co...

Страница 6: ...s can be inspected by removing the inducer assembly See Flushing Collector Box and Drainage System section for details on removing inducer assembly Step 5 Flushing Collector Box and Drainage System 1 Turn off gas and electrical supplies to furnace 2 Remove main furnace door 3 Disconnect inducer motor and pressure switch wires or connectors 4 Disconnect pressure switch tubes 5 Disconnect vent pipe ...

Страница 7: ...e Trap on LEFT Side Optional CAP COLLECTOR BOX DRAIN TUBE BLUE PLUGGEDEND COLLECTORBOX DRAIN TUBE BLUE WHITE STRIPED COLLECTOR BOX TUBE GREEN COLLECTOR BOX TUBE PINK COLLECTOR BOX EXTENSIONTUBE CONDENSA TE TRAP INDUCERHOUSINGDRAINTUBE VIOLET COLLECTOR BOX EXTENSIONTUBE Condensate Trap on RIGHT Side PLUG CAP COLLECTOR BOX DRAIN TUBE BLUE WHITE STRIPED CONDENSA TE TRAP COLLECTOR BOX EXTENSIONTUBE CO...

Страница 8: ...tion NOTE If the polarity is not correct the STATUS LED on the furnace control board will flash rapidly and prevent the furnace from operating The control system also requires an earth ground for proper operation of the furnace control board and flame sensor The 24 v circuit contains an automotive type 3 amp fuse located on the control See Fig 12 Any direct shorts of the 24 v wiring during install...

Страница 9: ...GND GND FIELD 24 V WIRING FIELD 115 208 230 460 V WIRING FACTORY 24 V WIRING FACTORY 115 V WIRING 208 230 OR 460 V THREE PHASE 208 230 V SINGLE PHASE WHT BLK WHT BLK W W1 W2 Y Y2 G NOTES 1 Connect Y terminal as shown for proper operation 2 Some thermostats require a C terminal connection as shown 3 If any of the original wire as supplied must be replaced use same type or equivalent wire 115 V FUSE...

Страница 10: ... and all blower off delays must be completed to view previous codes To retrieve previous codes remove 1 of the red main limit or flame rollout switch wires 1 to 4 sec until the LED light goes out then reconnect it Do not leave red wire disconnected for longer periods of time as the control will assume an overtemperature condition exists and will respond with blower operation This places the contro...

Страница 11: ...R lead from furnace control 3 Manually close blower door switch 4 For approximately 2 sec short jumper the COM 24v terminal on control to the TEST TWIN 3 16 in quick connect terminal on control until LED turns off Remove jumper from termi nals See Fig 12 NOTE If TEST TWIN and COM 24v terminals are jumpered loner than 2 sec LED will flash rapidly and ignore status code retrieval request Component t...

Страница 12: ... EMITTING DIODE FOR STATUS CODES AMBER LGPS LOW GAS PRESSURE SWITCH SPST N O LPS LOW HEAT PRESSURE SWITCH SPST N O LS LIMIT SWITCH AUTO RESET SPST N C OL AUTO RESET INTERNAL MOTOR OVERLOAD TEMPERATURE SWITCH N C PCB PRINTED CIRCUIT BOARD CONTROL PL1 12 CIRCUIT PCB CONNECTOR PL2 3 CIRCUIT PCB HSI IDM CONNECTOR PL3 6 CIRCUIT ICM MOTOR CONNECTOR NOT SHOWN PL4 4 CIRCUIT IDM CONNECTOR PL5 2 CIRCUIT HSI...

Страница 13: ...ITCH DID NOT CLOSE OR REOPENED If open longer than five minutes inducer shuts off for 15 minutes before retry If opens during blower on delay period blower will come on for the selected blower off delay Check for Excessive wind Restricted vent Defective inducer motor Low inlet gas pressure if LGPS used Defective pressure switch Low inducer voltage 115 VAC Inadequate combustion air supply Proper ve...

Страница 14: ...ducer will run for the entire component test The HSI blower motor LO HEAT speed HI HEAT speed and COOL speed will run for 10 15 seconds each Gas valve and humidifier will not be turned on When the blower motor is turned OFF the inducer will be switched to low speed for 10 seconds Was there a previous status code other than 11 Is door switch closed Is there 115V going to switch Replace door switch ...

Страница 15: ...ION PROVING FAILURE If flame is not sensed during the trial for ignition period the control will repeat the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected blower off delay Check the following items first before proceeding to the next step Gas valve turned off Manual shut off valve Green Yellow w...

Страница 16: ...31 58mta4sm Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 6a 8a PC 101 Catalog No 535 80098 Printed in U S A Form 58MTA 4SM Pg 16 11 02 Replaces 58MTA 3SM ...

Отзывы: