Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 3
2.3 OUTPUTS
Safety notes:
–
To avoid electrical shocks, connect power line at last.
–
For supply connections use No. 16 AWG or larger wires
rated for at last 75°C.
–
Use copper conductors only.
–
SSR outputs are not isolated. A reinforced isolation must
be assured by the external solid state relays.
–
For SSR, mA and V outputs if the line length is longer than
30 m use a shielded wire.
–
Do not short-circuit the terminals of the SSR output.
WARNING! Before connecting the output actuators
,
we recommend to configure the parameters to
suit your application (e.g.: input type, Control
strategy, alarms, etc.).
2.3.1 Output 1 (OP1)
Relay Output
C
NO
7
8
Contact rating:
• 4 A /250 V cos
j
=1;
• 2 A /250 V cos
j
=0.4.
Operation:
1 x 10
5
.
SSR Output
SSR
+
-
7
8
Logic level 0:
Vout < 0.5 VDC;
Logic level 1:
12 V ±20%, 15 mA max..
Current Analog Output
mA
+
-
7
8
mA output:
0/4... 20 mA, galvanically isolated, RL max. 600
Ω
.
Voltage Analog Output
V
+
-
7
8
V output:
0/2... 10 V, galvanically isolated, RL min.: 500
Ω
.
2.3.2 Output 2 (OP2)
Relay Output
C
NO
13
14
Contact rating:
• 2 A /250 V cos
j
= 1;
• 1 A /250 V cos
j
= 0.4.
Operation:
1 x 10
5
.
SSR Output
SSR
-
+
13
14
Logic level 0:
Vout < 0.5 VDC;
Logic level 1:
12 V ±20%, 15 mA max..
2.3.3 Output 3 (OP3)
Relay Output
C
NO
11
12
Contact rating:
• 2 A /250 V cos
j
= 1;
• 1 A /250 V cos
j
= 0.4.
Operation:
1 x 10
5
.
SSR Output
SSR
-
+
11
12
Logic level 0:
Vout < 0.5 VDC;
Logic level 1:
12 V ±20%, 15 mA max..
2.3.4 Output 4 (OP4)
SSR Output
SSR
+
-
4
Out4
4
16
Logic level 0:
Vout < 0.5 VDC;
Logic level 1:
12 V ±20%, 20 mA max..
Note:
Overload protected.