Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 15

[49] HAL3 - Alarm 3 hysteresis

Available: 

When [44] AL3t is different to “nonE” or [44] AL3t 

is different from “SE.br”.

Range: 

1 to 9999 engineering units.

Note: 

For other details see [33] HAL1 parameter.

[50] AL3d - Alarm 3 delay

Available: 

When [44] AL3t different form “nonE”.

Range: 

 From oFF (0) to 9999 seconds.

Note: 

The alarm goes ON only when the alarm condition 

persist for a time longer than [50] AL3d time but the 

reset is immediate.

[51] AL3o - Alarm 3 enabling during Stand-by mode 

and out of range indications

Available: 

When [44] AL3t is different from “nonE” or 
[44] AL3t is different from “SE.br”.

Range: 

0 = 

Never;

1 = 

During stand by;

2 = 

During overrange and underrange;

3 = 

During overrange, underrange and stand-by.

]

 LbA group - Loop break alarm

General note about LBA alarm

The LBA operate as follows:  applying the 100% of the power 
output to a process, the process variable, after a time due to the 
process inertia, begins to change in a known direction (increases 
for an heating action or decreases for a cooling action).

Example:

 If I apply 100% of the power output to a furnace, 

the temperature must go up unless one of the component in 
the loop is faulty (heater, sensor, power supply, fuse, etc.)
The same philosophy can be applied to the minimum power.  
In our example, when I turn OFF the power to a furnace, the 
temperature must go down, if not the SSR is in short circuit, 
the valve is jammed, etc..
LBA function is automatically enabled when the PID requires 
the maximum or the minimum power.
When the process response is slower than the programmed 
limit the instrument generates an alarm.

Notes: 1. 

 When the instrument is in manual mode, the LBA 
function is disabled.

2. 

 When LBA alarm is ON the instrument continues 
to perform the standard control.  If the process 
response comes back into the programmed limit, 
the instrument automatically resets the LBA alarm.

3. 

This function is available only when the programmed 
control algorithm is equal to PID (Cont = PID).

[52] LbAt - LBA time

Available: 

When [56] Cont = PID.

Range: 

oFF = LBA not used;
1 to 9999 seconds.

[53] LbSt - Delta measure used by LBA during  

Soft start

Available: 

When [52] LbAt is different from oFF.

Range: 

oFF = loop break alarm is inhibit during soft start;
1 to 9999 engineering units.

[54] LbAS - Delta measure used by loop break  

alarm (loop break alarm step)

Available: 

When [52] LbAt is different from oFF.

Range: 

 1 to 9999 engineering units.

[55] LbcA - Condition for LBA enabling

Available: 

when [52] LbAt is different from oFF.

Range: 

uP =  

Enabled when the PID requires the maxi-
mum power only;

dn =  

Enabled when the PID requires the mini-
mum power only;

both =   Enabled in both condition (when the PID re-

quires the maximum or the minimum power).

LBA application example: 
 

LbAt (LBA time) = 120 seconds (2 minutes);

 

LbAS (delta LBA) = 5°C.

The machine has been designed in order to reach 200°C in 
20 minutes (20°C/min);
When the PID demands 100% power, the instrument starts 
the time count.
During time count if the measured value increases more 
than 5°C, the instrument restarts the time count.  Otherwise 
if the measured value does not reach the programmed delta 
(5°C in 2 minutes) the instrument will generate the alarm.

]

rEG group - Control parameters

The rEG group will be available only when at least one 
output is programmed as control output (H.rEG or C.rEG).

[56] cont - Control type:

Available: 

When at least one output is programmed as con-
trol output (H.rEG or C.rEG).

Range:  • 

When two control action (heat & cool) are pro-
grammed:

Pid = 

PID (heat and cool);

nr =  

Heat/Cool ON/OFF control with neutral zone.

HSEt
HSEt

SP

PV

time

OUTH.rEG

(heating)
OUTc.rEG

(cooling)

off

ON

ON

off

off

ON

• 

When one control action (heat or cool) is programmed:

Pid = 

PID (heat or cool);

On.FA = ON/OFF asymmetric hysteresis;
On.FS = ON/OFF symmetric hysteresis;

HEAt - On.FA

OUT
H.rEG

SP

PV

HSEt

time

off

off

C ooL - O n.FA

OUT
C.rEG

SP

PV

HSEt

time

ON

ON

ON

off

off

ON

ON

ON

HEAt - On.FS

OUT
H.rEG

SP

PV

HSEt

HSEt

time

C ooL - O n.FS

OUT
H.rEG

SP

PV

HSEt

HSEt

time

ON

ON

ON

off

off

off

off

ON

ON

ON

Notes: 1. 

ON/OFF control with asymmetric hysteresis:

• 

OFF when PV > SP;

• 

ON when PV < (SP - hysteresis).

2. 

ON/OFF control with symmetric hysteresis: 

• 

OFF when PV >

 (SP +  hysteresis);

• 

ON when PV < (SP -  hysteresis).

Содержание TC10

Страница 1: ...ce with the operative temperature 0 to 50 C 6 The relative humidity is in accordance with the instrument specifications 20 to 90 The instrument can be mounted on panel with a maximum thickness of 8 mm...

Страница 2: ...mpedance 1 M for mV Input 500 k for Volt Input 2 2 5 mA Input 0 4 to 20 mA input wiring for passive transmitter using the auxiliary pws _ 4 to 20 mA Passive transmitter 4 1 Input impedance 53 Internal...

Страница 3: ...1 OP1 Relay Output C NO 7 8 Contact rating 4 A 250 V cosj 1 2 A 250 V cosj 0 4 Operation 1 x 105 SSR Output SSR 7 8 Logic level 0 Vout 0 5 VDC Logic level 1 12 V 20 15 mA max Current Analog Output mA...

Страница 4: ...l gasket is mounted for indoor locations according to EN 60070 1 Terminals protection IP 20 according to EN 60070 1 Installation Panel mounting Terminal block 16 screw terminals for cables of 0 25 to...

Страница 5: ...or ON OFF or Heat Cool control with 1 alarm V N N DC Output for SSR V R R DC Output for SSR with 2 alarm relays or DCV and relay output for Heat Cool control with 1 alarm V V R 2 DCV outputs for SSR w...

Страница 6: ...figuration parameters The complete configuration method allows to take advantage of all instrument features giving more capabilities it requires more actions and time Note that you can take advantage...

Страница 7: ...on The upper display shows cod2 flashing while the lower display shows 0000 or the cod2 value stored in memory 6 Using and buttons set the code 2 value according to the following tables P Q R S Prepar...

Страница 8: ...o return to the previous group Proceed as follows Push the button and maintaining the pressure then push the button release both the buttons Note The group selection is cyclic as well as the selection...

Страница 9: ...n an underrange is detected the po wer output will be forced to the value of 8 oPE parameter 8 oPE Safety output value Available Always Range 100 to 100 of the output Notes 1 When the instrument is pr...

Страница 10: ...When a Sequential set point selection is used diF1 or diF2 18 every closure of of the logic input increase the value of SPAT active set point of one step The selection is cyclic SP SP2 SP3 SP4 12 di...

Страница 11: ...Heating output see warning c rEG Cooling output AL Alarm output t out Reserved t HoF Reserved P End Reserved P HLd Reserved P uit Reserved P run Reserved P Et1 Reserved P Et2 Reserved or bo Out of ran...

Страница 12: ...ute band alarm with alarm indication inside the band SE br Sensor break LodE Deviation low alarm relative HidE Deviation high alarm relative LHdo Relative band alarm with alarm indication out of the b...

Страница 13: ...e difference between the Alarm threshold value and the point the Alarm automatically resets 2 When the alarm threshold plus or minus the hysteresis is out of input range the instrument will not be abl...

Страница 14: ...le When 36 AL2t different from nonE Range 0 Never 1 During stand by 2 During overrange and underrange 3 During overrange underrange and stand by AL3 Group Alarm 3 parameters 44 AL3t Alarm 3 type Avail...

Страница 15: ...ID 52 LbAt LBA time Available When 56 Cont PID Range oFF LBA not used 1 to 9999 seconds 53 LbSt Delta measure used by LBA during Soft start Available When 52 LbAt is different from oFF Range oFF loop...

Страница 16: ...ed for all process subjected to big load variation able to change heavily the process response Available When 56 cont PID Range YES self tune active no self tune not active 60 HSEt Hysteresis of the O...

Страница 17: ...and soft start function are programmed the instrument performs the soft start and than the program function 4 The auto tune function will be performed after soft start function 5 The Soft start functi...

Страница 18: ...ill be used as remote set point Note A 84 SPrt change produces the following actions When 84 SP rt rSP the remote set point will be forced to be equal to the active set point When 84 SP rt trin the re...

Страница 19: ...t Display time out Available Always Range oFF The display is ever ON 0 1 to 99 59 minutes and seconds Note This function allows to turn OFF the display when no alarm is present and no action is made o...

Страница 20: ...e threshold set with parameter 137 h Job the display shows r iSP Inspection Requested The count reset with r iSP cancellation can be done only by changing the threshold value parameter 137 h Job Using...

Страница 21: ...is NOT password protected Notes 1 The limited access parameter are collected in a list 2 The sequence of the limited access parameters is programmable and can be made according to your needs 3 The par...

Страница 22: ...1 when the instrument is powered it starts immediately to work according to the memorized parameter value In other words the instrument has one status only the run time status During run time we can f...

Страница 23: ...ocedures Allows to start the Direct set point modification fun ction see below Allows to display the additional informations see below 7 4 2 Direct set point modification This function allows to modif...

Страница 24: ...lute alarms are operative or not according to the ALxo Alarm x enabling during Stand by mode parameter setting 2 If you set stand by mode during program execution the program will be aborted 3 If you...

Страница 25: ...sponsibility for any damage to people things or animals deriving from violation wrong or improper use or in any case not in compliance with the instrument s features 9 2 WARRANTY This product is under...

Страница 26: ...s 1 0 7 inE Sensor error used to enable the safety output value or Over range ou Under range our Over and under range our 8 oPE Safety output value of the output 100 to 100 0 9 IO4 F I O 4 function on...

Страница 27: ...d the programmed threshold 15 Ao1L Initial scale value of the analog retransmission when Out 1 is an analog output dP 1999 Ao1H 1999 16 Ao1H Full scale value of the analog retransmission when Out 1 is...

Страница 28: ...days counter has reached the programmed threshold AL 23 o3AL Alarms linked up with the out 3 0 0 to 63 1 Alarm 1 2 Alarm 2 4 Alarm 3 8 Loop break alarm 16 Sensor Break 32 Overload on output 4 AL2 24 o...

Страница 29: ...abled in stand by mode 2 Alarm 1 enabled in out of range condition 3 Alarm 1 enabled in stand by mode and in overrange condition 0 AL2 group no Param Description Dec Point Values Default 36 AL2t Alarm...

Страница 30: ...3 enabled in stand by mode and in overrange condition 0 LBA group Loop Break Alarm Parameters no Param Description Dec Point Values Default 52 LbAt LBA time 0 From 0 oFF to 9999 s oFF 53 LbSt Delta m...

Страница 31: ...0 100 to 100 0 74 SSt Soft start time 2 0 00 oFF 0 01 to 7 59 hh mm inF always ON oFF 75 SS tH Threshold for soft start disabling dP 1999 to 9999 E U 9999 SP group Set point parameters no Param Descri...

Страница 32: ...d Reserved P t tu Reserved P t td Reserved ti uP Reserved ti du Reserved PErc Percent of the power output used during soft start when the soft start time is equal to infinite the limit is ever active...

Страница 33: ...e controller is forced in stand by when Co ty value reaches the threshold set in 137 h Job 8 Totalizer of control relay worked days number of hours the con trol relay has been in ON condition divided...

Страница 34: ...Yokogawa Electric Corporation TC10 ENGINEERING MANUAL PAG 34...

Страница 35: ...Yokogawa Electric Corporation TC10 ENGINEERING MANUAL PAG 35...

Страница 36: ...Yokogawa Electric Corporation TC10 ENGINEERING MANUAL PAG 36...

Отзывы: