background image

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 23

modification procedure is closed.

When you desire to remove the time out (e.g. 
for the first configuration of an instrument) you 
can use a password equal to 1000 plus the 
programmed password  

(e.g. 1000 + 20 [default] = 1020).

It is always possible to manually End the 
parameter configuration procedure (see below). 

3. 

During parameter modification the instrument 
continues to perform the control.

In certain conditions (

e.g. when a parameter 

change can produces a heavy bump to the 
process)

 it is advisable to temporarily stop the 

controller from controlling during the programming 
procedure (its control output will be Off). 

password equal to 2000 + the programmed value 
(e.g. 2000 + 20 = 2020) will switch the control out 

off during configuration.  The control will restart 
automatically when the parameter modification 
procedure will be manually ended.

4. 

Push 

 button.

5. 

The instrument will show on the upper display the 
acronym of the first parameter promoted to this 
level and on the lower display its value.

6. 

By 

 and 

 buttons assign to this parameter 

the desired value.

7. 

Press the 

 button in order to memorize the 

new value and go to the next parameter.

8. 

When you want to come back to the “standard 
display” push the 

 button for more than 3 s.

7.3  HOW TO SEE BUT NOT MODIFY THE “LIMITED 

ACCESS PARAMETERS”

Sometime it is necessary to give to the operator the possibility 
to see the value assigned to the parameter promoted in the 
Limited Access level but it is important that all changes are 
made by authorized personnel only.
In this cases, proceed as follows:

1. 

Press the 

 button for more than 3 seconds;

2. 

The upper display will show 

PASS

 while the lower display 

will show 

0

;

3. 

By 

 and 

 button set the value 

-181

;

4. 

Push 

 button;

5. 

The upper display will show the acronym of the first 
parameter promoted to the level 2 and lower display will 
show its value;

6. 

Using 

 button it is possible to see the value assigned 

to all parameter present in level 2 but it will not be 
possible to modify it;

7. 

It is possible to come back to the “standard display” by 
pushing the 

 button for more than 3 seconds or by 

pushing no pushbutton for more than 10 seconds. 

7.4  AUTOMATIC MODE

7.4.1  Keyboard function when the instrument 
is in Auto mode

  Performs the action programmed by [121] uSrb 

 

(

 button function during RUN TIME) parameter.

  Allows to entrer the parameter modification procedures.

  Allows to start the “Direct set point modification” fun-

ction (see below).

   Allows to display the “additional informations”  

(see below).

7.4.2  Direct set point modification

This function allows to modify rapidly the set point value 

selected by [83] A.SP (selection of the active Set point).

The instrument is showing the “standard display”.

1. 

Push 

 button. 

The upper display shows the acronym of the selected set 
point (e.g. SP2) and the lower display will show its value.

2. 

By 

 and 

 buttons, assign to this parameter the 

desired value.

3. 

Do not push any button for more than 10 second or push 
the 

 button.

In both cases the instrument memorize the new value and 
come back to the “standard display”.

Note: 

If the selected set point has not been promoted to the 
Operator level, the instrument allows you to see the 
value but not to modify it.

7.4.3  Additional information

This instrument is able to show you some additional 
informations that can help you to manage your system.
The additional informations are related to how the instrument 
is programmed, hence in many cases, only part of this 
information is available.

1. 

When the instrument is showing the “standard display” 
push 

 button.

The lower display will show 

H

 or 

c

 followed by a number. 

This value is the current power output applied to the 
process. The 

H

 show you that the action is a Heating action 

while the 

c

 show you that the action is a Cooling action.

2. 

Push 

 button again.  When the wattmeter function 

is running the lower display will show 

U

 followed by the 

measured energy.

Note: 

 The energy calculation will be in accordance with 

the [134] Co.tY parameter setting.

3. 

Push 

 button again.  When the “Worked time count” 

is running the lower display will show 

d

 for days or 

h

 for 

hours followed by the measured time.

4. 

Push 

 button again. The instrument returns to the 

“standard display”.

Note: 

The additional information visualization is subject to 
a time out. If no button is pressed for more than 5 
second the instrument comes automatically back to 
the Standard display.

7.4.4  Display management

This instrument allows you to program (see parameter 

[125] diS.t the time out of the display.

This function allows to turn OFF the display when no alarm 
is present and no action is made on the instrument.

When [125] diS.t is different to OFF (display ever ON) and 

no button is pressed for more than the programmed time 
out, the display goes OFF and only 4 segments of the less 
significant digit are turned ON in sequence in order to show 
that the instrument is working correctly.
If an alarm occurs or a button is pressed, the display will 
come back to the normal operation. 

Содержание TC10

Страница 1: ...ce with the operative temperature 0 to 50 C 6 The relative humidity is in accordance with the instrument specifications 20 to 90 The instrument can be mounted on panel with a maximum thickness of 8 mm...

Страница 2: ...mpedance 1 M for mV Input 500 k for Volt Input 2 2 5 mA Input 0 4 to 20 mA input wiring for passive transmitter using the auxiliary pws _ 4 to 20 mA Passive transmitter 4 1 Input impedance 53 Internal...

Страница 3: ...1 OP1 Relay Output C NO 7 8 Contact rating 4 A 250 V cosj 1 2 A 250 V cosj 0 4 Operation 1 x 105 SSR Output SSR 7 8 Logic level 0 Vout 0 5 VDC Logic level 1 12 V 20 15 mA max Current Analog Output mA...

Страница 4: ...l gasket is mounted for indoor locations according to EN 60070 1 Terminals protection IP 20 according to EN 60070 1 Installation Panel mounting Terminal block 16 screw terminals for cables of 0 25 to...

Страница 5: ...or ON OFF or Heat Cool control with 1 alarm V N N DC Output for SSR V R R DC Output for SSR with 2 alarm relays or DCV and relay output for Heat Cool control with 1 alarm V V R 2 DCV outputs for SSR w...

Страница 6: ...figuration parameters The complete configuration method allows to take advantage of all instrument features giving more capabilities it requires more actions and time Note that you can take advantage...

Страница 7: ...on The upper display shows cod2 flashing while the lower display shows 0000 or the cod2 value stored in memory 6 Using and buttons set the code 2 value according to the following tables P Q R S Prepar...

Страница 8: ...o return to the previous group Proceed as follows Push the button and maintaining the pressure then push the button release both the buttons Note The group selection is cyclic as well as the selection...

Страница 9: ...n an underrange is detected the po wer output will be forced to the value of 8 oPE parameter 8 oPE Safety output value Available Always Range 100 to 100 of the output Notes 1 When the instrument is pr...

Страница 10: ...When a Sequential set point selection is used diF1 or diF2 18 every closure of of the logic input increase the value of SPAT active set point of one step The selection is cyclic SP SP2 SP3 SP4 12 di...

Страница 11: ...Heating output see warning c rEG Cooling output AL Alarm output t out Reserved t HoF Reserved P End Reserved P HLd Reserved P uit Reserved P run Reserved P Et1 Reserved P Et2 Reserved or bo Out of ran...

Страница 12: ...ute band alarm with alarm indication inside the band SE br Sensor break LodE Deviation low alarm relative HidE Deviation high alarm relative LHdo Relative band alarm with alarm indication out of the b...

Страница 13: ...e difference between the Alarm threshold value and the point the Alarm automatically resets 2 When the alarm threshold plus or minus the hysteresis is out of input range the instrument will not be abl...

Страница 14: ...le When 36 AL2t different from nonE Range 0 Never 1 During stand by 2 During overrange and underrange 3 During overrange underrange and stand by AL3 Group Alarm 3 parameters 44 AL3t Alarm 3 type Avail...

Страница 15: ...ID 52 LbAt LBA time Available When 56 Cont PID Range oFF LBA not used 1 to 9999 seconds 53 LbSt Delta measure used by LBA during Soft start Available When 52 LbAt is different from oFF Range oFF loop...

Страница 16: ...ed for all process subjected to big load variation able to change heavily the process response Available When 56 cont PID Range YES self tune active no self tune not active 60 HSEt Hysteresis of the O...

Страница 17: ...and soft start function are programmed the instrument performs the soft start and than the program function 4 The auto tune function will be performed after soft start function 5 The Soft start functi...

Страница 18: ...ill be used as remote set point Note A 84 SPrt change produces the following actions When 84 SP rt rSP the remote set point will be forced to be equal to the active set point When 84 SP rt trin the re...

Страница 19: ...t Display time out Available Always Range oFF The display is ever ON 0 1 to 99 59 minutes and seconds Note This function allows to turn OFF the display when no alarm is present and no action is made o...

Страница 20: ...e threshold set with parameter 137 h Job the display shows r iSP Inspection Requested The count reset with r iSP cancellation can be done only by changing the threshold value parameter 137 h Job Using...

Страница 21: ...is NOT password protected Notes 1 The limited access parameter are collected in a list 2 The sequence of the limited access parameters is programmable and can be made according to your needs 3 The par...

Страница 22: ...1 when the instrument is powered it starts immediately to work according to the memorized parameter value In other words the instrument has one status only the run time status During run time we can f...

Страница 23: ...ocedures Allows to start the Direct set point modification fun ction see below Allows to display the additional informations see below 7 4 2 Direct set point modification This function allows to modif...

Страница 24: ...lute alarms are operative or not according to the ALxo Alarm x enabling during Stand by mode parameter setting 2 If you set stand by mode during program execution the program will be aborted 3 If you...

Страница 25: ...sponsibility for any damage to people things or animals deriving from violation wrong or improper use or in any case not in compliance with the instrument s features 9 2 WARRANTY This product is under...

Страница 26: ...s 1 0 7 inE Sensor error used to enable the safety output value or Over range ou Under range our Over and under range our 8 oPE Safety output value of the output 100 to 100 0 9 IO4 F I O 4 function on...

Страница 27: ...d the programmed threshold 15 Ao1L Initial scale value of the analog retransmission when Out 1 is an analog output dP 1999 Ao1H 1999 16 Ao1H Full scale value of the analog retransmission when Out 1 is...

Страница 28: ...days counter has reached the programmed threshold AL 23 o3AL Alarms linked up with the out 3 0 0 to 63 1 Alarm 1 2 Alarm 2 4 Alarm 3 8 Loop break alarm 16 Sensor Break 32 Overload on output 4 AL2 24 o...

Страница 29: ...abled in stand by mode 2 Alarm 1 enabled in out of range condition 3 Alarm 1 enabled in stand by mode and in overrange condition 0 AL2 group no Param Description Dec Point Values Default 36 AL2t Alarm...

Страница 30: ...3 enabled in stand by mode and in overrange condition 0 LBA group Loop Break Alarm Parameters no Param Description Dec Point Values Default 52 LbAt LBA time 0 From 0 oFF to 9999 s oFF 53 LbSt Delta m...

Страница 31: ...0 100 to 100 0 74 SSt Soft start time 2 0 00 oFF 0 01 to 7 59 hh mm inF always ON oFF 75 SS tH Threshold for soft start disabling dP 1999 to 9999 E U 9999 SP group Set point parameters no Param Descri...

Страница 32: ...d Reserved P t tu Reserved P t td Reserved ti uP Reserved ti du Reserved PErc Percent of the power output used during soft start when the soft start time is equal to infinite the limit is ever active...

Страница 33: ...e controller is forced in stand by when Co ty value reaches the threshold set in 137 h Job 8 Totalizer of control relay worked days number of hours the con trol relay has been in ON condition divided...

Страница 34: ...Yokogawa Electric Corporation TC10 ENGINEERING MANUAL PAG 34...

Страница 35: ...Yokogawa Electric Corporation TC10 ENGINEERING MANUAL PAG 35...

Страница 36: ...Yokogawa Electric Corporation TC10 ENGINEERING MANUAL PAG 36...

Отзывы: