background image

Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 17

On the contrary, when you want to decrease the temperature 
from 250 to 230°C (

D

T = 20°C) using 100% of the cooling 

power (fan), you will need 20 seconds only.

In our example the ratio is equal to 60/20 = 3 ([67] rcG = 3) 

and it say that the efficiency of the cooling system is 3 time 
more efficient of the heating one.

Available: 

When two control action are programmed  

(H.rEG and c.rEG) and [56] cont = PID and 

 

[59] SELF = no.

Range: 

 0.01 to 99.99.

Note: 

auto-tune functions calculate this value.

[68] tcc - Cycle time of the cooling output

Available: 

When at least one output is programmed in order 

to be the cooling output (c.rEG), [56] cont  = PID 
and [59] SELF = no.

Range: 

1.0 to 130.0 seconds.

[69] rS - Manual reset (integral pre-load)

It allows to drastically reduce the undershoot due to a 
hot restart.  When your process is steady, the instrument 
operates with a steady power output (e.g.: 30%).
If a short power down occurs, the process restarts with a 
process variable close to the set point while the instrument 
starts with an integral action equal to zero. 
Setting a manual reset equal to the average power output (in our 
example 30%) the instrument will start with a power output equal 
to the value it will use at steady state (instead of zero) and the 
undershoot will become very little (in theory equal to zero).

Available: 

When [56] cont = PID.

Range: 

-100.0 to +100.0%.

[72] od - Delay at power up

Available: 

When at least one output is programmed as 
control output.

Range: 

oFF: 

Function not used;

0.01 to 99.59 hh.mm.

Notes: 1. 

This parameter defines the time during which 
(after a power up) the instrument remains in stand 
by mode before to start all other function (control, 
alarms, program, etc.).

2. 

When a program with 

automatic start at power up

 

and 

od function

 are programmed, the instrument 

performs od function before to start the program.

3. 

When an auto-tune with 

automatic start at power 

up

 and 

od function

 are programmed, the autotune 

will start at the end of 

od delay

.

[73] St.P  - Maximum power output used during  

soft start

Available: 

When at least one output is programmed as 
control output.

Range: 

-100 to +100%.

Notes: 1. 

When St.P parameter have a positive value, the 
limit will be applied to the heating output(s) only.

2. 

When St.P parameter have a negative value, the 
limit will be applied to the cooling output(s) only.

3. 

When a program with automatic start at power 
up and soft start function are programmed, the 
instrument performs the soft start and than the 
program function.

4. 

The auto-tune function will be performed after 
soft start function.

5. 

The Soft start function is available also when ON/
OFF contro l is used.

[74] SSt - Soft start time 

Available: 

When at least one output is programmed as 
control output.

Range: 

oFF =  Function not used;
0.01 to 7.59 hh.mm;
inF = 

Soft start always active.

[75] SS.tH - Threshold for soft start disabling

Available: 

When at least one output is programmed as 
control output.

Range: 

-1999 to 9999 engineering units.

Notes: 1. 

When the power limiter have a positive value (the 
limit is applied to the heating action) the soft start 
function will be aborted when the measured value 
is greater or equal to SS.tH parameter.

2. 

When the power limiter have a negative value 
(the limit is applied to the cooling action) the soft 
start function will be aborted when the measured 
value is lower or equal to SS.tH parameter.

]

SP Group - Set point parameters

The SP group will be available only when at least one output 
is programmed as control output (H.rEG or C.rEG).

[76] nSP - Number of used set points

Available: 

When at least one output is programmed as 
control output.

Range: 

1 to 4.

Note: 

When you change the value of this parameter, the 
instrument operates as follows:

•  [83] A.SP parameter will be forced to SP.
• 

The instrument verifies that all used set point are 

within the limits programmed by [77] SPLL and  [78] 

SPHL.  If an SP is out of this range, the instrument 
forces it to the maximum acceptable value

[77] SPLL - Minimum set point value

Available: 

When at least one output is programmed as 
control output.

Range: 

 From -1999 to [78] SPHL engineering units.

Notes: 1. 

When you change the [77] SPLL value, the 

instrument checks all local set points (SP, SP2, 
SP3 and SP4 parameters) and all set points of the 

program ([97] Pr.S1, [102] Pr.S2,  [107] Pr.S3, [112] 

Pr.S4 parameters).  If an SP is out of this range, the 
instrument forces it to the maximum acceptable value

2. 

A [77] SPLL change produces the following actions:

•  When [84] SP.rt = SP the remote set point will 

be forced to be equal to the active set point

•  When [84] SP.rt = trim the remote set point will 

be forced to zero

•  When [84] SP.rt = PErc the remote set point 

will be forced to zero

[78] SPHL - Maximum set point value

Available: 

When at least one output is programmed as 
control output.

Range: 

From [78] SPLL to 9999 engineering units.

Note: 

For other details see [78] SPLL parameter.

[79] SP - Set Point 1

Available: 

When at least one output is programmed as 
control output.

Range: 

From [77] SPLL to [78] SPHL engineering units.

Содержание TC10

Страница 1: ...ce with the operative temperature 0 to 50 C 6 The relative humidity is in accordance with the instrument specifications 20 to 90 The instrument can be mounted on panel with a maximum thickness of 8 mm...

Страница 2: ...mpedance 1 M for mV Input 500 k for Volt Input 2 2 5 mA Input 0 4 to 20 mA input wiring for passive transmitter using the auxiliary pws _ 4 to 20 mA Passive transmitter 4 1 Input impedance 53 Internal...

Страница 3: ...1 OP1 Relay Output C NO 7 8 Contact rating 4 A 250 V cosj 1 2 A 250 V cosj 0 4 Operation 1 x 105 SSR Output SSR 7 8 Logic level 0 Vout 0 5 VDC Logic level 1 12 V 20 15 mA max Current Analog Output mA...

Страница 4: ...l gasket is mounted for indoor locations according to EN 60070 1 Terminals protection IP 20 according to EN 60070 1 Installation Panel mounting Terminal block 16 screw terminals for cables of 0 25 to...

Страница 5: ...or ON OFF or Heat Cool control with 1 alarm V N N DC Output for SSR V R R DC Output for SSR with 2 alarm relays or DCV and relay output for Heat Cool control with 1 alarm V V R 2 DCV outputs for SSR w...

Страница 6: ...figuration parameters The complete configuration method allows to take advantage of all instrument features giving more capabilities it requires more actions and time Note that you can take advantage...

Страница 7: ...on The upper display shows cod2 flashing while the lower display shows 0000 or the cod2 value stored in memory 6 Using and buttons set the code 2 value according to the following tables P Q R S Prepar...

Страница 8: ...o return to the previous group Proceed as follows Push the button and maintaining the pressure then push the button release both the buttons Note The group selection is cyclic as well as the selection...

Страница 9: ...n an underrange is detected the po wer output will be forced to the value of 8 oPE parameter 8 oPE Safety output value Available Always Range 100 to 100 of the output Notes 1 When the instrument is pr...

Страница 10: ...When a Sequential set point selection is used diF1 or diF2 18 every closure of of the logic input increase the value of SPAT active set point of one step The selection is cyclic SP SP2 SP3 SP4 12 di...

Страница 11: ...Heating output see warning c rEG Cooling output AL Alarm output t out Reserved t HoF Reserved P End Reserved P HLd Reserved P uit Reserved P run Reserved P Et1 Reserved P Et2 Reserved or bo Out of ran...

Страница 12: ...ute band alarm with alarm indication inside the band SE br Sensor break LodE Deviation low alarm relative HidE Deviation high alarm relative LHdo Relative band alarm with alarm indication out of the b...

Страница 13: ...e difference between the Alarm threshold value and the point the Alarm automatically resets 2 When the alarm threshold plus or minus the hysteresis is out of input range the instrument will not be abl...

Страница 14: ...le When 36 AL2t different from nonE Range 0 Never 1 During stand by 2 During overrange and underrange 3 During overrange underrange and stand by AL3 Group Alarm 3 parameters 44 AL3t Alarm 3 type Avail...

Страница 15: ...ID 52 LbAt LBA time Available When 56 Cont PID Range oFF LBA not used 1 to 9999 seconds 53 LbSt Delta measure used by LBA during Soft start Available When 52 LbAt is different from oFF Range oFF loop...

Страница 16: ...ed for all process subjected to big load variation able to change heavily the process response Available When 56 cont PID Range YES self tune active no self tune not active 60 HSEt Hysteresis of the O...

Страница 17: ...and soft start function are programmed the instrument performs the soft start and than the program function 4 The auto tune function will be performed after soft start function 5 The Soft start functi...

Страница 18: ...ill be used as remote set point Note A 84 SPrt change produces the following actions When 84 SP rt rSP the remote set point will be forced to be equal to the active set point When 84 SP rt trin the re...

Страница 19: ...t Display time out Available Always Range oFF The display is ever ON 0 1 to 99 59 minutes and seconds Note This function allows to turn OFF the display when no alarm is present and no action is made o...

Страница 20: ...e threshold set with parameter 137 h Job the display shows r iSP Inspection Requested The count reset with r iSP cancellation can be done only by changing the threshold value parameter 137 h Job Using...

Страница 21: ...is NOT password protected Notes 1 The limited access parameter are collected in a list 2 The sequence of the limited access parameters is programmable and can be made according to your needs 3 The par...

Страница 22: ...1 when the instrument is powered it starts immediately to work according to the memorized parameter value In other words the instrument has one status only the run time status During run time we can f...

Страница 23: ...ocedures Allows to start the Direct set point modification fun ction see below Allows to display the additional informations see below 7 4 2 Direct set point modification This function allows to modif...

Страница 24: ...lute alarms are operative or not according to the ALxo Alarm x enabling during Stand by mode parameter setting 2 If you set stand by mode during program execution the program will be aborted 3 If you...

Страница 25: ...sponsibility for any damage to people things or animals deriving from violation wrong or improper use or in any case not in compliance with the instrument s features 9 2 WARRANTY This product is under...

Страница 26: ...s 1 0 7 inE Sensor error used to enable the safety output value or Over range ou Under range our Over and under range our 8 oPE Safety output value of the output 100 to 100 0 9 IO4 F I O 4 function on...

Страница 27: ...d the programmed threshold 15 Ao1L Initial scale value of the analog retransmission when Out 1 is an analog output dP 1999 Ao1H 1999 16 Ao1H Full scale value of the analog retransmission when Out 1 is...

Страница 28: ...days counter has reached the programmed threshold AL 23 o3AL Alarms linked up with the out 3 0 0 to 63 1 Alarm 1 2 Alarm 2 4 Alarm 3 8 Loop break alarm 16 Sensor Break 32 Overload on output 4 AL2 24 o...

Страница 29: ...abled in stand by mode 2 Alarm 1 enabled in out of range condition 3 Alarm 1 enabled in stand by mode and in overrange condition 0 AL2 group no Param Description Dec Point Values Default 36 AL2t Alarm...

Страница 30: ...3 enabled in stand by mode and in overrange condition 0 LBA group Loop Break Alarm Parameters no Param Description Dec Point Values Default 52 LbAt LBA time 0 From 0 oFF to 9999 s oFF 53 LbSt Delta m...

Страница 31: ...0 100 to 100 0 74 SSt Soft start time 2 0 00 oFF 0 01 to 7 59 hh mm inF always ON oFF 75 SS tH Threshold for soft start disabling dP 1999 to 9999 E U 9999 SP group Set point parameters no Param Descri...

Страница 32: ...d Reserved P t tu Reserved P t td Reserved ti uP Reserved ti du Reserved PErc Percent of the power output used during soft start when the soft start time is equal to infinite the limit is ever active...

Страница 33: ...e controller is forced in stand by when Co ty value reaches the threshold set in 137 h Job 8 Totalizer of control relay worked days number of hours the con trol relay has been in ON condition divided...

Страница 34: ...Yokogawa Electric Corporation TC10 ENGINEERING MANUAL PAG 34...

Страница 35: ...Yokogawa Electric Corporation TC10 ENGINEERING MANUAL PAG 35...

Страница 36: ...Yokogawa Electric Corporation TC10 ENGINEERING MANUAL PAG 36...

Отзывы: