Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 27
]
Out group
no. Param.
Description
Dec.
Point
Values
Default
13
o1t
Output 1 type
(when Out 1 is an analog output)
0-20 = 0 to 20 mA;
4-20 = 4 to 20 mA;
0-10 = 0 to 10 V;
2-10 = 2 to 10 V.
0-20
14
o1F
Out 1 function
(when Out 1 is an analog output)
0
NonE = Output not used;
H.rEG = Heating output;
c.rEG = Cooling output;
r.inP = Measure retransmission;
r.Err = Error (SP - PV) retransmission;
r.SP = Set point retransmission ;
r.SEr = Serial value retransmission.
H.rEG
Out 1 function
0
NonE = Output not used
H.rEG = Heating output
c.rEG = Cooling output
AL =
Alarm output
t.out = Reserved
t.HoF = Reserved
P.End = Reserved
P.HLd = Reserved
P.uit = Reserved
P.run = Reserved
P.Et1 = Reserved
P.Et2 = Reserved
or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out and Power failure indicator
St.bY = Stand by status indicator
diF.1 = The output repeats the digital input 1 status
diF.2 = The output repeats the digital input 2 status
on =
Out 1 always ON
riSP = Inspection requested (the worked hours/days
counter has reached the programmed threshold)
15
Ao1L
Initial scale value of the analog retransmission
(when Out 1 is an analog output)
dP
-1999 ... Ao1H
-1999
16
Ao1H
Full scale value of the analog retransmission
(when Out 1 is an analog output)
dP
Ao1L ... 9999.
9999
17
o1AL
Alarms linked up with the out 1
0
0 to 63
+1 =
Alarm 1
+2 =
Alarm 2
+4 =
Alarm 3
+8 =
Loop break alarm
+16 =
Sensor Break
+32 =
Overload on output 4
AL1
18
o1Ac
Out 1 action
0
dir =
Direct action
rEU =
Reverse action
dir.r =
Direct with reversed LED
ReU.r = Reverse with reversed LED
dir
19
o2F
Out 2 function
0
NonE = Output not used
H.rEG = Heating output
c.rEG = Cooling output
AL =
Alarm output
t.out = Reserved
t.HoF = Reserved
P.End = Reserved
P.HLd = Reserved
P.uit = Reserved
P.run = Reserved
P.Et1 = Reserved
P.Et2 = Reserved
or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator
bo.PF = Out-of-range, burn out and Power failure indicator
St.bY = Stand by status indicator
diF.1 = The output repeats the digital input 1 status
diF.2 = The output repeats the digital input 2 status
on =
Out 2 always ON
riSP = Inspection requested (the worked hours/days
counter has reached the programmed threshold)
AL
20
o2AL
Alarms linked up with the out 2
0
0 to 63
+1 =
Alarm 1
+2 =
Alarm 2
+4 =
Alarm 3
+8 =
Loop break alarm
+16 =
Sensor Break
+32 =
Overload on output 4
AL1