Yokogawa Electric Corporation - TC10 - ENGINEERING MANUAL - PAG. 22

1. 

Push the 

 button for more than 3 seconds.

2. 

The upper display will show 

PASS

 while the lower display 

will show 

0

.

3. 

By 

 and 

 buttons set a password equal to 

-81

.

4. 

Push 

 button. 

The instrument will show the acronym of the first 
configuration parameter group “

]inp

”.

5. 

By 

 button select the group of the first parameter of 

your list.

6. 

By 

 button select the first parameter of your list 

7. 

The upper display will show the acronym of the parameter  
while the lower display will show his current promotion level. 
The promotion level is defined by a letter followed by a 
number.

The letter can be:

c

:  It shows that this parameter is 

NOT

 promoted 

and it is present only in configuration. 
In this case the number is forced to zero.

A

:  It shows that this parameter has been promoted 

to the limited access level. 
The number will show the position in the limited 
access list.

o

:  It shows that the parameter has been promoted 

to the Operator level. 
The number will show the position in the limited 
access list.

8. 

By 

 and 

 buttons assign to this parameter the 

desired position.

Note: 

 Setting a value different from 0 the letter 

c

 will change 

automatically to 

A

 and the parameter is automatically 

promoted to the limited access level.

9. 

In order to modify the level from limited access 
to operator and vice versa, push 

 button and, 

maintaining the pressure, push 

 button. 

The letter will change from 

A

 to 

o

 and vice versa.

10. 

Select the second parameter that you want to add to the 
assistance level and repeat step 6, 7 and 8.

11. 

Repeat step 5, 6, 7, 8 until the list has been completed.

12. 

When you need to exit from promotion procedure, push 

 button and maintain the pressure for more than 10 s.  

The instrument will show the “standard display”.

Note: 

When you set the some number to two parameter, 
the instrument will use only the last programmed 
parameter.

Example:

 In the previous example, I have set for SP2 a 

promotion value equal to A3.
If now I set for SP3 a promotion value equal to 

o3

, the 

Limited Access list and the operator list becomes. 

Parameter

Promotion 

Limited Access

Operator

- OPEr - 

o 1

OPEr

OPEr

- SP - 

o 2

SP

SP

- SP3 - 

o 3

SP3

SP3

- A.SP - 

A 4

A.SP

- AL1 - 

o 5

AL1

AL1

7.  OPERATIVE MODES

As we said at paragraph 4.1, when the instrument is 
powered, it starts immediately to work according to the 
memorized parameter value.
In other words, the instrument has one status only, the “run 
time” status.
During “run time”  we can force the instrument to operate 
in three different modes: Automatic mode, Manual mode or 
Stand by mode:

 

In 

Automatic mode

 the instrument drives automatically 

the control output according to the parameter value set 
and the set point/measured value.

 

In 

Manual mode

 the the upper display shows the measured 

value while the lower display shows the power output The 
lower display shows the power output [preceded by 

H

 (for 

heating) or 

C

 (for cooling)], MAN is lit 

and the instrument 

allows you to set manually the control output power.

No Automatic action will be made.

 

In 

Stand by

 mode the instrument operates as an indicator. 

It will show on the upper display the measured value and 
on the lower display the set point alternately to the “St.bY” 
messages and forces the control outputs to zero.

As we have seen, it is always possible to modify the value 
assigned to a parameter independently from the operative 
modes selected.

7.1  MODIFY A PARAMETER DURING 

“OPERATOR LEVEL”

The instrument is showing the “standard display”.

1. 

Press the 

 button.

2. 

The upper display will show the acronym of the first 
parameter promoted to this level while the lower display 
will show its value.

3. 

By 

 and 

 button assign to this parameter the 

desired value.

4. 

Press the 

 button in order to memorize the new value 

and go to the next parameter.

5. 

When you want to come back to the “standard display” 
push the 

 button for more than 3 seconds.

Note: 

The parameter modification of the Operator level 
is subject to a time out.  If no button is pressed for 
more than 10 seconds, the instrument goes back to 
the “standard display” and the new value of the last 
selected parameter will be lost.

7.2  ENTER THE “LIMITED ACCESS LEVEL”

The instrument is showing the “standard display”.

1. 

Press the 

 button for more than 3 seconds;

2. 

The upper display will show 

PASS

 while the lower display 

will show 

0

;

3. 

By 

 and 

 buttons set the value assigned to 

[118] PAS2 (Level 2 password).

Notes: 1. 

The factory default password for configuration 
parameters is equal to 20.

2. 

All parameter modification are protected by a 
time out.  If no button is pressed for more than 
10 second the instrument comes automatically 
back to the Standard display, the new value of the 
last selected parameter is lost and the parameter 

Содержание TC10

Страница 1: ...ce with the operative temperature 0 to 50 C 6 The relative humidity is in accordance with the instrument specifications 20 to 90 The instrument can be mounted on panel with a maximum thickness of 8 mm...

Страница 2: ...mpedance 1 M for mV Input 500 k for Volt Input 2 2 5 mA Input 0 4 to 20 mA input wiring for passive transmitter using the auxiliary pws _ 4 to 20 mA Passive transmitter 4 1 Input impedance 53 Internal...

Страница 3: ...1 OP1 Relay Output C NO 7 8 Contact rating 4 A 250 V cosj 1 2 A 250 V cosj 0 4 Operation 1 x 105 SSR Output SSR 7 8 Logic level 0 Vout 0 5 VDC Logic level 1 12 V 20 15 mA max Current Analog Output mA...

Страница 4: ...l gasket is mounted for indoor locations according to EN 60070 1 Terminals protection IP 20 according to EN 60070 1 Installation Panel mounting Terminal block 16 screw terminals for cables of 0 25 to...

Страница 5: ...or ON OFF or Heat Cool control with 1 alarm V N N DC Output for SSR V R R DC Output for SSR with 2 alarm relays or DCV and relay output for Heat Cool control with 1 alarm V V R 2 DCV outputs for SSR w...

Страница 6: ...figuration parameters The complete configuration method allows to take advantage of all instrument features giving more capabilities it requires more actions and time Note that you can take advantage...

Страница 7: ...on The upper display shows cod2 flashing while the lower display shows 0000 or the cod2 value stored in memory 6 Using and buttons set the code 2 value according to the following tables P Q R S Prepar...

Страница 8: ...o return to the previous group Proceed as follows Push the button and maintaining the pressure then push the button release both the buttons Note The group selection is cyclic as well as the selection...

Страница 9: ...n an underrange is detected the po wer output will be forced to the value of 8 oPE parameter 8 oPE Safety output value Available Always Range 100 to 100 of the output Notes 1 When the instrument is pr...

Страница 10: ...When a Sequential set point selection is used diF1 or diF2 18 every closure of of the logic input increase the value of SPAT active set point of one step The selection is cyclic SP SP2 SP3 SP4 12 di...

Страница 11: ...Heating output see warning c rEG Cooling output AL Alarm output t out Reserved t HoF Reserved P End Reserved P HLd Reserved P uit Reserved P run Reserved P Et1 Reserved P Et2 Reserved or bo Out of ran...

Страница 12: ...ute band alarm with alarm indication inside the band SE br Sensor break LodE Deviation low alarm relative HidE Deviation high alarm relative LHdo Relative band alarm with alarm indication out of the b...

Страница 13: ...e difference between the Alarm threshold value and the point the Alarm automatically resets 2 When the alarm threshold plus or minus the hysteresis is out of input range the instrument will not be abl...

Страница 14: ...le When 36 AL2t different from nonE Range 0 Never 1 During stand by 2 During overrange and underrange 3 During overrange underrange and stand by AL3 Group Alarm 3 parameters 44 AL3t Alarm 3 type Avail...

Страница 15: ...ID 52 LbAt LBA time Available When 56 Cont PID Range oFF LBA not used 1 to 9999 seconds 53 LbSt Delta measure used by LBA during Soft start Available When 52 LbAt is different from oFF Range oFF loop...

Страница 16: ...ed for all process subjected to big load variation able to change heavily the process response Available When 56 cont PID Range YES self tune active no self tune not active 60 HSEt Hysteresis of the O...

Страница 17: ...and soft start function are programmed the instrument performs the soft start and than the program function 4 The auto tune function will be performed after soft start function 5 The Soft start functi...

Страница 18: ...ill be used as remote set point Note A 84 SPrt change produces the following actions When 84 SP rt rSP the remote set point will be forced to be equal to the active set point When 84 SP rt trin the re...

Страница 19: ...t Display time out Available Always Range oFF The display is ever ON 0 1 to 99 59 minutes and seconds Note This function allows to turn OFF the display when no alarm is present and no action is made o...

Страница 20: ...e threshold set with parameter 137 h Job the display shows r iSP Inspection Requested The count reset with r iSP cancellation can be done only by changing the threshold value parameter 137 h Job Using...

Страница 21: ...is NOT password protected Notes 1 The limited access parameter are collected in a list 2 The sequence of the limited access parameters is programmable and can be made according to your needs 3 The par...

Страница 22: ...1 when the instrument is powered it starts immediately to work according to the memorized parameter value In other words the instrument has one status only the run time status During run time we can f...

Страница 23: ...ocedures Allows to start the Direct set point modification fun ction see below Allows to display the additional informations see below 7 4 2 Direct set point modification This function allows to modif...

Страница 24: ...lute alarms are operative or not according to the ALxo Alarm x enabling during Stand by mode parameter setting 2 If you set stand by mode during program execution the program will be aborted 3 If you...

Страница 25: ...sponsibility for any damage to people things or animals deriving from violation wrong or improper use or in any case not in compliance with the instrument s features 9 2 WARRANTY This product is under...

Страница 26: ...s 1 0 7 inE Sensor error used to enable the safety output value or Over range ou Under range our Over and under range our 8 oPE Safety output value of the output 100 to 100 0 9 IO4 F I O 4 function on...

Страница 27: ...d the programmed threshold 15 Ao1L Initial scale value of the analog retransmission when Out 1 is an analog output dP 1999 Ao1H 1999 16 Ao1H Full scale value of the analog retransmission when Out 1 is...

Страница 28: ...days counter has reached the programmed threshold AL 23 o3AL Alarms linked up with the out 3 0 0 to 63 1 Alarm 1 2 Alarm 2 4 Alarm 3 8 Loop break alarm 16 Sensor Break 32 Overload on output 4 AL2 24 o...

Страница 29: ...abled in stand by mode 2 Alarm 1 enabled in out of range condition 3 Alarm 1 enabled in stand by mode and in overrange condition 0 AL2 group no Param Description Dec Point Values Default 36 AL2t Alarm...

Страница 30: ...3 enabled in stand by mode and in overrange condition 0 LBA group Loop Break Alarm Parameters no Param Description Dec Point Values Default 52 LbAt LBA time 0 From 0 oFF to 9999 s oFF 53 LbSt Delta m...

Страница 31: ...0 100 to 100 0 74 SSt Soft start time 2 0 00 oFF 0 01 to 7 59 hh mm inF always ON oFF 75 SS tH Threshold for soft start disabling dP 1999 to 9999 E U 9999 SP group Set point parameters no Param Descri...

Страница 32: ...d Reserved P t tu Reserved P t td Reserved ti uP Reserved ti du Reserved PErc Percent of the power output used during soft start when the soft start time is equal to infinite the limit is ever active...

Страница 33: ...e controller is forced in stand by when Co ty value reaches the threshold set in 137 h Job 8 Totalizer of control relay worked days number of hours the con trol relay has been in ON condition divided...

Страница 34: ...Yokogawa Electric Corporation TC10 ENGINEERING MANUAL PAG 34...

Страница 35: ...Yokogawa Electric Corporation TC10 ENGINEERING MANUAL PAG 35...

Страница 36: ...Yokogawa Electric Corporation TC10 ENGINEERING MANUAL PAG 36...

Отзывы: