3-19
TI04L55B01-01EN
Event Types
Item
Explanation
Remote (DI)
DI channel of remote control input
Relay (DO)
Relay status
Internal switch
Internal switch status
Alarm - IO channel
Alarm of an I/O channel
Alarm - Math channel
Alarm of a math channel
Alarm - Communication channel
Alarm of a communication channel
Any alarm
The change from no active alarms to one or more active alarms is regarded
as an event.
Timer
Timer (timer 1 to 12) expiration
Match Time Timer
Match time timer (match time timer 1 to 12) expiration
User function key
User function key (USER1/USER2)
Status
Recording, math, memory/media error, measurement error, communication
error
Action Types
Item
Explanation
Recording
Starts or stops recording.
Computation
Starts or stops computation (/MT option) or resets the computed values of
all math channels.
Flag
Sets a flag to 1 (On) or 0 (Off). (/MT option)
Manual sample
Executes manual sampling.
Alarm ACK
Clears the alarm output.
Event Trigger
Applies a trigger that starts event data recording. You can specify this when
the GM is configured to event data.
Message writing
Writes a message. Specify the message number and the message write
destination. Set the destination to all groups, or specify a write destination
group number. You can execute this while recording is in progress.
Save event data
Saves the event data being recorded to a file in the internal memory. You
can specify this when the GM is configured to event data.
Save display data
Saves the display data being recorded to a file in the internal memory. You
can specify this when the GM is configured to record display data.
Reset the relative timer
Resets a relative timer. The timer starts immediately.
Load settings
Loads the setting parameter file from the root directory of the SD card and
configures the GM accordingly.
Save settings
Saves the current setting parameter to the SD card.
Adjust the time
Sets the clock to the nearest hour.
Relay
Sets the relay output to On or Off.
Internal switch
Sets the internal switch to 1 (On) or 0 (Off).
Load program pattern
Loads all the pattern files (ProgPatYY, YY: 01 to 99) in the specified folder
at the root directory of the SD memory card. GM Feature Overview