Output (Relay output)
The GM can generate alarms assigned to measurement channels, turn the output on and off
according to manual operation, and output relay signals through the event action function (digital
output module, digital input/output module, PID control module).
For details on output, see section 3.1.3, “Output.”
For the combinations of events and actions that can be used to output relay signals through the
event action function, see section 3.2.2, “Event Action Function.”
1.1.2
Actual Values Underlying Accurate Measurements
The measuring accuracies noted in the general specifications have a margin of error that takes
into account the product’s components and the equipment used for adjustment and testing.
However, the actual values calculated from the accuracy testing data upon shipment of the
instrument from the factory are as follows.
Input Type
Measuring Accuracy* (typical value)
DCV
20mV
± (0.01% of rdg + 5 μV)
60mV
± (0.01% of rdg + 5 μV)
6V(1-5V)
± (0.01% of r 2 mV)
TC
R, S
± 1.1°C
B
± 1.5°C
K (−200.0 to 1370.0°C)
± (0.01% of rdg +0.2°C) for 0.0 to 1370.0°C;
± (0.15% of rdg +0.2°C) for -200.0 to 0.0°C
K (−200.0 to 500.0°C)
± 0.2°C for 0.0 to 500.0°C;
± (0.15% of rdg +0.2°C) for -200.0 to 0.0°C
J
± 0.2°C for 0.0 to 1100.0 °C;
± (0.10% of rdg + 0.2 °C) for -200.0 to 0.0 °C
T
± 0.2°C for 0.0 to 400.0°C;
± (0.10% of rdg + 0.2 °C) for -200.0 to 0.0 °C
N
± (0.01% of rdg + 0.2°C) for 0.0 to 1300.0 °C;
± (0.22% of rdg + 0.2°C) for -200.0 to 0.0 °C
RTD
Pt100
(−200.0 to 850.0°C)
± (0.02% of r 0.2°C)
Pt100
(−150.00 to 150.00°C)
± (0.02% of r 0.16°C)
*1 Applies to GX90XA-10-U2, A/D integration time 16.67 ms or more, General operating conditions: 23±2
ºC, 55±10% RH, supply voltage 90–132, 180–264 V AC, power frequency within 50/60 Hz ±1%, warm-up
of 30 minutes or more, no vibrations or other hindrances to performance.
*2 For the measuring accuracy (guaranteed), see the module’s general specifications (GS
04L53B01-01EN).
*3 These values do not include the reference junction compensation accuracy.
rdg: Reading value
•
For details on modules with higher guaranteed accuracy specifications, contact your
nearest YOKOGAWA dealer.