![YOKOGAWA SMARTDAC+ GM Скачать руководство пользователя страница 42](http://html2.mh-extra.com/html/yokogawa/smartdac-gm/smartdac-gm_technical-information_3465448042.webp)
3-21
TI04L55B01-01EN
3.2.3
Control Event Action Function
The control event action function is used to execute a specified action when certain events
occur.
For details, see the Loop Control Function, Program Control Function (/PG Option) User’s
Manual (IM 04L51B01-31EN).
Control Operation
l
Loop Control and Common Control
Function
Description
Run all control loops
Starts running all loops when the input changes from off to on.
Stop all control loops
Stops all loops when the input changes from off to on.
Control operation stop/start (specified loop)
Stops the control operation of specified loops when the input
changes from off to on.
Starts the control operation of specified loops when the input
changes from on to off.
Auto/manual switch (specified loop)
Switches the control operation of specified loops to auto
when the input changes from off to on.
Switches the control operation of specified loops to manual
when the input changes from on to off.
Remote/local switch (specified loop)
Switches the control operation of specified loops to remote
when the input changes from off to on.
Switches the control operation of specified loops to local
when the input changes from on to off.
Auto switch (specified loop)
Switches the control operation of specified loops to auto
when the input changes from off to on.
Manual switch (specified loop)
Switches the control operation of specified loops to manual
when the input changes from off to on.
Cascade switch (specified loop)
Switches the control operation of specified loops to cascade
when the input changes from off to on (during cascade
control).
Remote switch (specified loop)
Switches the control operation of specified loops to remote
when the input changes from off to on.
Local switch (specified loop)
Switches the control operation of specified loops to local
when the input changes from off to on.
SP number switch (binary/BCD)
Switches the SP number according to the combination of
input ON/OFF states (binary or BCD).
3
Functions
Содержание SMARTDAC+ GM
Страница 2: ...Blank Page...