Other Types of Input Processing
l
Moving average
Performs moving average over the specified number of sampling points.
For example, you can use this to smooth the data when the input signal is fluctuating due to noise
or other unwanted influences.
Average
Scan interval
Sampling count
Average
l
Bias
This is used to add a constant value to input values or scaled values (input computation).
Input value
Measured value
Bias (a constant value)
+
Channel on which bias is added
l
Calibration correction
Input values can be corrected using segment linearization. Up to 12 correction points can be
specified.
Linearizer approximation
Corrects input values using characteristics specified with segments to derive output values.
Output value
Measured value
Input value
Number of setpoints: 2 to 12
( )
Linearizer Bias
Corrects input values using bias values specified with segments to derive output values.
Input value
Number of setpoints: 2 to 12
Linearizer bias
After correction
Output value
Measured value
( )
Correction factor
Corrects input values using the instrument correction factor and sensor correction factor specified
with segments to derive output values.
Input value
Number of setpoints: 2 to 12
Instrument correction Sensor correction factor
After correction
Output value
Measured value
( )
Uncorrected value