<8. PR201 Original Communication Protocol>
8-13
IM 77C01E01-10E
• Example
Reads in batch the measured values and maximum/minimum value of PR300 with station
number 01.
[Command]
[STX]DGA01
䊐䊐
[ETX][CR]
Returns the following response for the above command.
[Response]
[STX]DGA01100001001.000E+31.000E+31.000E+3G0.8001.000E+31.000E+21.000E+3
䊐䊐
[ETX][CR]
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(1) Active energy: 10000 kWh, (2) Optional electric energy (previous value):
10000 Wh, (3) Optional electric energy (current value): 10000 Wh, (4) Active
power: +1.000E+3 W (1000 W), (5) Voltage-1: 1.000E+3 V (1000 V),
(6) Current-1: 1.000E+3 A (1000 A), (7) Power factor: G0.800,
(8) Maximum voltage-1: 1.000E+3 V (1000 V), (9) Minimum voltage-1:
1.000E+2 V (100 V), (10) Maximum current-1: 1.000E+3 A (1000 A)
●
Parameter: B (Reads maximum voltage-1), Parameter: C (Reads minimum
voltage-1), Parameter: N (Reads maximum voltage-2), Parameter: P (Reads
maximum voltage-3), Parameter: Q (Reads minimum voltage-2), Parameter: R
(Reads minimum voltage-3)
• Function
Reads the maximum voltage-1 by parameter: B, the minimum voltage-1 by parameter C,
the maximum voltage-2 by parameter: N, the maximum voltage-3 by parameter: P, the
minimum voltage-2 by parameter: Q, and the minimum voltage-3 by parameter: R.
• Command/response
Number
of bytes
1
2
1
2
2
1
1
Command
element
STX
DG
B
(C)
(N)
(P)
(Q)
(R)
Station
number
(ADR)
Checksum ETX
CR
There is no command data for data reading.
1
2
1
2
8
Response
element
STX
DG
B
(C)
(N)
(P)
(Q)
(R)
Station
number
(ADR)
ⵧ
.
ⵧⵧⵧ
E
䊊
2
1
1
Checksum ETX
CR
Number
of bytes
Response data is returned as an 8-byte ASCII character string (0.000E+0 to 9.999E+6).
Содержание PR300