<8. PR201 Original Communication Protocol>
8-21
IM 77C01E01-10E
■
Command: DP
●
Parameter: 0 (Reads setting value)
• Function
Reads the VT ratio, CT ratio and integrated low-cut power. The read low-cut power is
always 0.
• Command/response
Number
of bytes
1
2
1
2
2
1
1
Command
element
STX
DP
0
Station
number
(ADR)
Checksum ETX
CR
1
2
1
2
6
Response
element
STX
DP
0
Station
number
(ADR)
ⵧⵧⵧⵧⵧⵧ
(VT ratio)
6
ⵧⵧⵧⵧⵧⵧ
(CT ratio)
Number
of bytes
Response data is returned in a 16-byte ASCII character string.
Continued
4
2
1
1
ⵧⵧ
.
ⵧ
(Integrated low-cut power)
Checksum ETX
CR
Response data to be returned for integrated low-cut power is always 0.
• Example
Reads the setting value of PR300 with station number 01.
䊐䊐
indicates the checksum
value.
[Command]
[STX]DP001
䊐䊐
[ETX][CR]
Returns a VT ratio of 10, a CT ratio of 100 and an integrated low-cut power of 0 for the
above command.
[Response]
[STX]DP00100001000010000.0
䊐䊐
[ETX][CR]