8-18
<Toc> <Ind>
<8. PR201 Original Communication Protocol>
IM 77C01E01-10E
●
Example
Reads the measured value and maximum/minimum values of PR300 with station number
01 in batch.
䊐䊐
indicates the checksum value.
[Command]
[STX]DGM01
䊐䊐
[ETX][CR]
Returns the following response for the above command.
[Response]
[STX]DGM031001.000E+31.000E+31.000E+31.000E+3
1.000E+31.000E+31.000E+3G0.8001.000E+31.000E+21.000E+3
1.000E+31.000E+31.000E+21.000E+21.000E+31.000E+3
䊐䊐
[ETX][CR]
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(12)
(13)
(14)
(11)
(15)
(16)
(17)
(18)
(19)
(20)
(1) Active energy: 3 Wh (10 MWh), (2) Optional electric energy (previ-
ous value): 10000 Wh, (3) Optional electric energy (current value): 10000 Wh,
(4) Active power: +1.000E+3 W (1000 W), (5) Voltage-1: 1.000E+3 V (1000 V),
(6) Voltage-2: 1.000E+3 V (1000 V), (7) Voltage-3: 1.000E+3 V (1000 V),
(8) Current-1: 1.000E+3 A (1000 A), (9) Current-2: 1.000E+3 A (1000 A),
(10) Current-3: 1.000E+3 A (1000 A), (11) Power factor: G0.800, (12) Maximum
voltage-1: 1.000E+3 V (1000 V), (13) Minimum voltage-1: 1.000E+ 2 V (100 V),
(14) Maximum current-1: 1.000E+3 A (1000 A), (15) Maximum voltage-2:
1.000E+3 V (1000 V), (16) Maximum voltage-3: 1.000E+3 V (1000 V),
(17) Minimum voltage-2: 1.000E+2 V (100 V), (18) Minimum voltage-3:
1.000E+2 V (100 V), (19) Maximum current-2: 1.000E+3 A (1000 A),
(20) Maximum current-3: 1.000E+3 A (1000 A).
●
Parameter: X (Reads model and suffix codes)
• Function
Returns the model and suffix codes of PR300.
• Command/response
Number
of bytes
1
2
1
2
2
1
1
Command
element
STX
DG
X
Station
number
(ADR)
Checksum ETX
CR
There is no command data for data reading.
1
2
1
2
14
Response
element
STX
DG
X
Station
number
(ADR)
PR201-
ⵧⵧⵧⵧⵧ
-
䉭䉭
(Note 1)
2
1
1
Checksum ETX
CR
Number
of bytes
Response data is returned in a 14-byte ASCII character string.