<Toc> <Ind>
< 6. Modbus/TCP Communication Protocol>
6-11
IM 77C01E01-10E
6.4.4
Response Error Codes
●
When a response is returned
If an inconsistency is found in a request’s PDU, the PR300 ignores the request and returns
the following response.
Element
Number of bytes
Command
element
Hex value
MBAP Header
2
2
2
1
1
1
Arbitrary
0000
03
01 to 99
PDU
Unit ID
Function
code
Transaction ID
Protocol ID
Error
code
Number of
bytes
*The function code entered here is the request’s function code (in hex) plus 80 (in hex).
●
Response Error Codes
Meaning
Funcation code error
Abnormal number of D registers
Error Code
01
03
02
Abnormal D register number
Cause
Function code does not exist.
Number of D registers out of the range is specified.
D register number out of the range is specified.
●
When a response is not returned
In the following cases, the PR300 ignores the request and does not return a response.
•
When no connection is established at the TCP/IP socket interface.
•
When an inconsistency is found in a request’s MBAP header.
•
When the communication with the serial communication device specified in Unit ID is
unusual.
Note: As a measure against the abovementioned problems, add a time-out process to the communication function or
program of the higher-level device.