< 6. Modbus/TCP Communication Protocol>
IM 77C01E01-10E
6.3
Network Frame Structure
The Modbus/TCP frame structure is as follows:
MBAP Header
Function code
Data
PDU
MODBUS TCP/IP ADU
MBAP Header (Modbus Application Protocol Header) : Header used to identify the Modbus/TCP protocol
PDU: simple Protocol Data Unit
6.3.1
MBAP Header Structure
The MBAP Header (Modbus Application Protocol Header) consists of the following seven
bytes.
Byte No
0
1
2
3
4
5
6
Transaction ID
Description
Protocol ID
Unit ID
Number of bytes
Transaction ID: Set any value for identifying the transaction. The PR300 returns a value received from a higher-level device
as a response.
Protocol ID: Specify “0” for the Modbus/TCP protocol.
Number of bytes: Number of bytes after the unit ID (byte number 6)
Unit ID: For the communication with the PR300 itself, specify “01” for the higher-level device. The PR300 returns “01” as a
response. For the communication with the device connected to the RS-485 communication terminals of the PR300
using the Ethernet-serial gateway function, specify its station number (02 to 99). The device returns the same value as
a response.
6.3.2
PDU Structure
The PDU (simple Protocol Data Unit) consists of the following
n
bytes.
Byte No
0
1 to (n-1)
Function code
Description
Data
Function code: Specify a command (function code) from a higher-level device.
Data: Specify D register numbers, number of D registers, parameter values, or others in accordance with the function code.
(expressed in hexadecimal in the request)