<5. Parameters>
5-15
IM 05D01C12-41E
4th Edition: May 31, 2006-00
Control output
type
0
Heating/cooling
type: 4
Control output cycle time
Heating-side control
output cycle time in
heating/cooling control
Cooling-side control
output cycle time
1 to 1000 second.
30 second.
1 to 1000 second.
30 second.
DI function selection
(Note)
UT420 can not switch
the five or more of target
setpoints by external
contact input, because
it does not have DI4 to
DI6.
1
(OT)
(CT)
(CTc)
(DIS)
The following 4 to 12 are displayed only for
heating/ cooling type controllers.
0
1
2
3
4
5
6
7
8
9
10
11
12
R/L = Remote (ON) / local (OFF)
DI1 = Auto (ON) / Man (OFF)
DI2 = Stop (ON) / Run (OFF)
DI3 to DI6 = Switching between 1.SP to 8.SP
R/L = Remote (ON) / local (OFF)
DI1 = Auto (ON) / Man (OFF)
DI2 = 2.SP (ON) / 1.SP (OFF)
DI3 = Stop (ON) / Run (OFF)
R/L = Remote (ON) / local (OFF)
DI1 = Stop (ON) / Run (OFF)
DI2 = 2.SP (ON) / 1.SP (OFF)
DI3 = Auto (ON) / Man (OFF)
R/L = Remote (ON) / local (OFF)
DI1, DI2 = Switching between 1.SP to 4.SP
DI3 = Stop (ON) / Run (OFF)
DI4 = Auto (ON) / Man (OFF)
R/L = Remote (ON) / local (OFF)
0
1
2
3
4
Time proportional PID relay contact output
(terminals - - )
1
2
3
Time proportional PID voltage pulse output
(terminals - )
16 17
Current output (terminals - )
16 17
ON/OFF control relay contact output
(terminals - - )
1
2
3
Heating-side relay output (terminals - - ),
cooling-side relay output (terminals - - )
1
2
3
48 49 50
Heating-side pulse output (terminals - ),
cooling-side relay output (terminals - - )
16 17
48 49 50
Heating-side current output (terminals - ),
cooling-side relay output (terminals - - )
16 17
48 49 50
Heating-side relay output (terminals - - ),
cooling-side pulse output (terminals - )
1
2
3
46 47
Heating-side pulse output (terminals - ),
cooling-side pulse output (terminals - )
16 17
46 47
Heating-side current output (terminals - ),
cooling-side pulse output (terminals - )
16 17
46 47
Heating-side relay output (terminals - - ),
cooling-side current output (terminals - )
46 47
1
2
3
Heating-side pulse output (terminals - ),
cooling-side current output (terminals - )
46 47
16 17
Heating-side current output (terminals - ),
cooling-side current output (terminals - )
46 47
16 17
Parameter
Symbol
Name of Parameter
Setting Range and Description
Initial Value
User Setting
Target Item
in CD-ROM
Ref.3.3(4)
same as
above
Ref.3.1(2)
Note: External Contact Input
If the power is turned on when the external contact input is OFF, the mode (SPN, R/L, or A/M) existing before the power
is turned off will be continued. (except for RUN/STOP)