Relay contact output
(Standard type: terminals
1
-
2
-
3
, heating-side: terminals
1
-
2
-
3
, cooling-side:
terminals
48
-
49
-
50
, position proportional type: terminals
48
-
49
-
50
)
Number of outputs
1 or 2 (two for heating/cooling type)
Output signal
Three terminals (NC, NO, and common)
Contact rating
250 V AC or 30 V DC, 3 A (resistance load)
Resolution
10 ms or 0.1% of output, whichever is larger
Contact Inputs
•
Purpose: Target setpoint selection, remote/local mode switching, and run/stop switch-
ing
•
Number of inputs: Differs with model and suffix codes as shown in the table below.
Model and Suffix Codes
Number of Inputs
UT420-00
UT420-07
UT420-08
2
7
3
6
3
2
4
4
UT450- 0
UT450- 1
UT450- 2
UT450- 3
UT450- 4
•
Input type: Non-voltage contact or transistor open collector input
•
Input contact rating: 12 V DC, 10 mA or more
•
On/off determination: For non-voltage contact input, contact resistance of 1 k
or less
is determined as “on” and contact resistance of 20 k
or more as “off.”
For transistor open collector input, input voltage of 2 V or less is determined as “on”
and leakage current must not exceed 100
A when “off.”
•
Minimum status detection hold time: 0.6 second
Contact Outputs
•
Purpose: Alarm output, FAIL output, and others
•
Number of outputs: Differs with the model and suffix code as shown in the table below.
Model and Suffix Codes
Number of Outputs
UT420-00
UT420-07
UT420-08
UT450- 0
UT450- 1
UT450- 2
UT450- 3
UT450- 4
3
3
3
3
4
3
4
3
•
Relay contact rating: 240 V AC, 1 A, or 30 V DC, 1 A
•
Transistor contact rating: 24 V DC, 50 mA