<2. Initial Settings>
2-5
IM 05D01C12-41E
4th Edition: May 31, 2006-00
■
Instrument Input Range Codes
Input
Type
Instrument Input
Range Code
Instrument
Input Range
Measurement Accuracy
OFF
1
-270.0 to 1370.0
°
C
-450.0 to 2500.0
F
Set the data item PV Input Type "IN" to the OFF option to leave the PV input
type undefined.
2
-270.0 to 1000.0
°
C
-450.0 to 2300.0
F
K
-200.0 to 500.0
°
C
-200.0 to 1000.0
F
J
4
-200.0 to 1200.0
°
C
-300.0 to 2300.0
F
5
-270.0 to 400.0
°
C
-450.0 to 750.0
F
T
6
0.0 to 400.0
°
C
-200.0 to 750.0
F
0.1% of instrument range
1 digit at 0
°
C or more
0.2%
1 digit for temperatures below 0
°
C,
where the accuracy is:
2% of instrument range
1
digit for temperatures below -200.0
°
C for a type-K thermo-
couple, or
1% of instrument range
1 digit for
temperatures below -200.0
°
C for a type-T thermocouple.
B
7
0.0 to 1800.0
°
C
32 to 3300
F
0.15% of instrument range
1 digit at 400
°
C or more
5% of instrument range
1 digit at less than 400
°
C
S
8
0.0 to 1700.0
°
C
32 to 3100
F
R
9
0.0 to 1700.0
°
C
32 to 3100
F
0.15% of instrument range
1 digit
N
10
-200.0 to 1300.0
°
C
-300.0 to 2400.0
F
0.1% of instrument range
1 digit
0.25% of instrument range
1 digit for temperatures
below 0
°
C
E
11
-270.0 to 1000.0
°
C
-450.0 to 1800.0
F
L(DIN)
12
-200.0 to 900.0
°
C
-300.0 to 1600.0
F
-200.0 to 400.0
°
C
-300.0 to 750.0
F
13
U(DIN)
14
0.0 to 400.0
°
C
-200.0 to 1000.0
F
0.1% of instrument range
1 digit at 0
°
C or more
0.2%
1 digit for temperatures below 0
°
C, where the
accuracy is:
1.5% of instrument range
1 digit for
temperatures below -200.0
°
C for a type-E thermocouple.
W 15
0.0 to 2300.0
°
C
32 to 4200
F
0.2% of instrument range
1 digit
Platinel 2
16
0.0 to 1390.0
°
C
32.0 to 2500.0
F
0.1% of instrument range
1 digit
PR20-40
17
0.0 to 1900.0
°
C
32 to 3400
F
0.5% of instrument range
1 digit at 800
°
C or more
No accuracy is guaranteed at less than 800
°
C
Thermocouple
Unspecified
W97Re3-
W75Re25
18
0.0 to 2000.0
°
C
32 to 3600
F
0.2% of instrument range
1 digit
30
-200.0 to 500.0
°
C
-300.0 to 1000.0
F
0.1% of instrument range
1 digit (Note 1) (Note 2)
JPt100
31
-150.00 to 150.00
°
C
-200.0 to 300.0
F
0.2% of instrument range
1 digit (Note 1)
35
-200.0 to 850.0
°
C
-300.0 to 1560.0
F
36
-200.0 to 500.0
°
C
-300.0 to 1000.0
F
0.1% of instrument range
1 digit (Note 1) (Note 2)
RTD
Pt100
37
-150.00 to 150.00
°
C
-200.0 to 300.0
F
0.2% of instrument range
1 digit (Note 1)
0.4 to 2 V
40
Standard
signal
1 to 5 V
41
0 to 2 V
50
0 to 10 V
51
0.400 to 2.000 V
1.000 to 5.000 V
0.000 to 2.000 V
0.00 to 10.00 V
-10 to 20 mV
55
-10.00 to 20.00 mV
DC voltage
0 to 100 mV
56
0.0 to 100.0 mV
0.1% of instrument range
1 digit
Display range is scalable in a range of -19999 to 30000.
Display span is 30000 or less.
3
Select the unit from the UNIT parameter.
*
Performance in the standard operating condition (at 23
2
C, 55
10%RH, and 50/60 Hz power frequency)
Note 1: The accuracy is
0.3
C of instrument range
1 digit for a temperature range from 0
C to 100
C.
Note 2: The accuracy is
0.5
C of instrument range
1 digit for a temperature range from -100
C to 200
C.
*
To receive a 4-20 mA DC signal, select a standard signal of 1 to 5 V DC and connect it to a 250
resistor. This resistor
is optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)