<Toc>
<5. Parameters>
5-17
IM 05D01C12-41E
4th Edition: May 31, 2006-00
●
Motor-driven Valve Calibration-related Parameters (Displayed for Position
Proportional Controllers)
Valve position setting
reset
The parameters V.RS, V.L and V.H are designed for
manual adjustment of valve positions.
Setting V.RS to 1 resets the valve adjustment
settings and causes the indication “V.RS” to blink.
0
Fully-closed valve
position setting
Pressing the SET/ENT key with valve position
set to the fully-closed position causes the
adjusted value to be stored.
Pressing the SET/ENT key with valve position
set to the fully-opened position causes the
adjusted value to be stored. When V.H
adjustment is complete, V.H stops blinking.
Undefined
Fully-opened valve
position setting
Undefined
Valve action time
5 to 300 sec.
Used to operate a valve according to the estimated
valve position. Set the time required for the valve to
open fully from a state of being fully closed. Confirm
the valve action time by consulting the datasheet of
the valve’s specifications.
The valve action time is only effective when Valve
Adjustment Mode (V.MD) is set to 1 or 2.
60 sec.
Valve adjusting mode
0: Valve position feedback type
1: Valve position feedback type (moves to the
estimating type if a valve input error or burnout
occurs.)
2: Valve position estimating type
0
(V.RS)
(V.L)
(V.H)
(TR.T)
(V.MD)
Automatic valve
adjustment
Automatically adjusts the fully-closed and fully-open
positions of a valve. When this function is used, there is no
need for adjustment using the parameters V.RS, V.L and V.H.
OFF (0): -
ON (1): Start automatic adjustment
OFF (0)
(V.AT)
Parameter
Symbol
Name of Parameter
Setting Range and Description
Initial Value
User Setting
Target Item
in CD-ROM
Содержание NEW GREEN SERIES
Страница 2: ...Blank Page ...
Страница 6: ...Blank Page ...
Страница 56: ...Blank Page ...
Страница 68: ...Blank Page ...
Страница 86: ...Blank Page ...
Страница 96: ...Blank Page ...
Страница 97: ......