<3. Operations>
3-3
IM 05D01C12-41E
4th Edition: May 31, 2006-00
3.2
Setting Target Setpoint (SP)
The following operating procedure describes an example of setting 150.0 to a target
setpoint. In automatic operation, the controller starts control using set target setpoints.
1.
Bring the operating display into view
(display appears at power on).
P V
AL1
2
3
4
M A N
R E M
S E T / E N T
A / M
Displays PV.
Displays
target setpoint-1
“1.SP”.
2.
Press the
or
key to display the
required setpoint.
PV
AL1
2
3
4
M A N
R E M
S E T / E N T
A / M
Blinks during
change.
3.
Press the
S E T / E N T
key once to register the
setpoint.
PV
AL1
2
3
4
M A N
R E M
S E T / E N T
A / M
3.3
Performing/Canceling Auto-tuning
Auto-tuning should be carried out after setting a target setpoint (SP). Make sure the control-
ler is in automatic operation mode (AUTO) and in running state (RUN) before carrying out
auto-tuning. See “3.8 Switching between AUTO and MAN,” to change to AUTO and “3.7
Switching between Run and Stop,” to change to Run.
NOTE
When on-off control is being used, auto-tuning cannot be carried out. Moreover, do not
perform auto-tuning when controlling any of the following processes.
•
Control processes with quick response such as flow control or pressure control
•
Processes where even temporary output on/off results in inconvenience
•
Processes where a large output change at control element results in inconvenience
•
Processes where variations in PV may exceed an allowable range, adversely affect-
ing product quality
Содержание NEW GREEN SERIES