The target setpoint ramp rate setting function prevents the target setpoint form changing
suddenly. It is possible to set the upward and downward changing rate (i.e., ramp rate)
independently in the parameters UPR and DNR. The unit of the ramp rate (hour, or minute)
is specified in TMU.
Setup Parameters
Function
Parameter
Ramp-rate time unit setting
TMU
SP
Menu
Operating Parameters
Function
Parameter
Target setpoint ramp-rate setting UPR, DNR
OP.PA
Menu
■
Control Output
Control output (OUTPUT1) selects the output type among the current output, voltage pulse
output, and relay contact output signal. For heating/cooling control, the cooling-side signals
are output to OUTPUT2.
Preset output value is output when the operation is stopped by key operation or contact
input, which takes priority over the manual operation.
Each function can be set by the following parameters.
Setup Parameters
Function
Parameter
Control output type selection
OT
Control output cycle time
CT
I/O
I/O
Cooling-side control output cycle time CTc
I/O
Menu
Operating Parameters
Function
Parameter
Preset output
n.PO
Output limiter
n.OL, n.OH
OP.PA
OP.PA
Menu
Cooling-side preset output
n.Oc
OP.PA
Note: Parameters n.PO, n.OL, n.OH, n.Oc, (n=1 to 8) correspond to the target setpoint number selected in the target setpoint
number selection (SPN).