<2. Handling Cautions>
2-16
IM 01S01C01-01EN
2.8.4 IECEx Certification
a. IECEx Flameproof Type
Caution for IECEx flameproof type.
Note 1. FVX110 Fieldbus Segment Indicator with
optional code /SF25 are applicable for use
in hazardous locations:
• No. IECEx KEM10.0071 X
• Applicable Standard:
IEC60079-0:2011,
IEC60079-1:2014
• Type of Protection and Marking Code:
Ex db IIC T6 Gb
• Temperature Class: T6
• Enclosure: IP66 / IP67
• Ambient Temperature for gas-proof:
–50 to 75ºC
• Supply voltage: 32 V dc max.
• Output current: 15 mA dc
Note 2. Wiring
•
In hazardous locations, the cable entry
devices shall be of a certified flameproof
type, suitable for the conditions of use and
correctly installed.
•
Unused apertures shall be closed with
suitable flameproof certified blanking
elements.
Note 3. Operation
•
WARNING:
AFTER DE-ENERGIZING, DELAY 5
MINUTES BEFORE OPENING.
•
WARNING:
WHEN AMBIENT TEMPERATURE ≥65ºC,
USE THE HEAT-RESISTING CABLES AND
CABLE GLAND ≥ 90ºC.
•
Take care not to generate mechanical
sparking when accessing to the instrument
and peripheral devices in a hazardous
location.
• Electrostatic charge may cause an explosion
hazard. Avoid any actions that cause the
generation of electrostatic charge, such as
rubbing with a dry cloth on coating face of the
product.
Note 4. Maintenance and Repair
• The instrument modification or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation is prohibited and will void IECEx
Certification.
•
Electrical Connection
A mark indicating the electrical connection
type is stamped near the electrical
connection port. These marks are as follows.
F0216.ai
Location of the mark
ISO M20
×
1.5 female
ANSI 1/2 NPT female
Marking
Screw Size
N or W
M
b. IECEx Intrinsically Safe Type
Caution for IECEx Intrinsically safe type.
Note 1. FVX110 Fieldbus Segment Indicator with
optional code /SS25 are applicable for use
in hazardous locations:
•
No. IECEx DEK 11.0004 X
•
Applicable Standard:
IEC60079-0:2007, IEC60079-11:2006,
IEC60079-26:2006, IEC60079-27:2008
Note 2. Ratings
[Ex ia IIB/IIC T4 Ga]
•
Type of Protection: II1G Ex ia IIB/IIC T4 Ga
•
Ambient Temperature: –40* to 60ºC
* –15ºC when O-ring material is Fluoro-rubber.
•
Degree of Protection of the Enclosure:
IP66 and IP67
•
When combined with Trapezoidal output
characteristic FISCO model
IIC or IIB barrier
[Supply/Output circuit (ter and –)]
Ui = 17.5 V, Ii = 500 mA, Pi = 5.5 W,
Ci = 3.52 nF, Li = 0 µH
•
When combined with Linear characteristic
barrier
[Supply/Output circuit (ter and –)]
Ui = 24.0 V, Ii = 250 mA, Pi = 1.2 W,
Ci = 3.52 nF, Li = 0 µH
[Ex ic IIC T4 Gc]
•
Type of Protection: II3G Ex ic IIC T4 Gc
•
Ambient Temperature: –40* to 60ºC
* –15ºC when O-ring material is Fluoro-rubber.
•
Degree of Protection of the Enclosure:
IP66 and IP67
[Supply/Output circuit (ter and –)]
Ui = 32.0 V, Ci = 3.52 nF, Li = 0 µH
Содержание FVX110
Страница 1: ...User s Manual FVX110 Fieldbus Segment Indicator IM 01S01C01 01EN IM 01S01C01 01EN 4th Edition ...
Страница 15: ... 2 Handling Cautions 2 4 IM 01S01C01 01EN ...
Страница 16: ... 2 Handling Cautions 2 5 IM 01S01C01 01EN ...
Страница 17: ... 2 Handling Cautions 2 6 IM 01S01C01 01EN ...
Страница 18: ... 2 Handling Cautions 2 7 IM 01S01C01 01EN ...
Страница 19: ... 2 Handling Cautions 2 8 IM 01S01C01 01EN ...
Страница 20: ... 2 Handling Cautions 2 9 IM 01S01C01 01EN ...