<Appendix 3. Input Selector (IS) Block>
A3-10
IM 01S01C01-01EN
If there is an odd number of valid inputs:
IN_1 = 23
SELECT_TYPE = Middle
STATUS_OPTS
MIN_GOOD = 1
SELECTION
SELECTED = 5
OUT = 23.6
IN_2 = 34.5
IN_3 = 45
IN_4 = 2.34
IN_5 = 23.6
IN_6 = 15.5
IN_7 = 32.5
IN_8 = 27.4
DISABLE_1 = OFF
DISABLE_2 = OFF
DISABLE_3 = OFF
DISABLE_4 = OFF
DISABLE_5 = OFF
DISABLE_6 = OFF
DISABLE_7 = OFF
DISABLE_8 = ON
OP_SELECT = 0
FA0308.ai
Figure A3.8 Example (7)
If the number of valid INs is an odd multiple, the IN with the middle value will be output. In the above example,
the IN_5 input having the middle value is output.