<6. Configuration>
6-5
IM 01S01C01-01EN
Table 6.4
VCR Static Entry
Sub-
index
Parameter
Description
1
FasArTypeAndRole
Indicates the type and
role of communication
(VCR). The following
4 types are used for
FVX110.
0x32: Server
(Responds to
requests from
host.)
0x44: Source
(Transmits alarm
or trend.)
0x66: Publisher (Sends
AI block output
of field device to
other blocks.)
0x76: Subscriber
(Receives output
of other blocks by
MAO block or PID
block.)
2
FasDllLocalAddr
Sets the local address
to specify VCR in
FVX110. A range of 20
to F7 in hexadecimal.
3
FasDllConfigured
RemoteAddr
Sets the node address
of the called party for
communication and
the address (DLSAP
or DLCEP) used to
specify VCR in that
address. For DLSAP or
DLCEP, a range of 20
to F7 in hexadecimal is
used.
Addresses in Subindex
2 and 3 need to be set
to the same contents of
the VCR as the called
party (local and remote
are reversed).
4
FasDllSDAP
Specifies the quality
of communication.
Usually, one of the
following types is set.
0x2B: Server
0x01: Source (Alert)
0x03: Source (Trend)
0x91: Publisher/
Subscriber
5
FasDllMaxConfirm
DelayOnConnect
To establish connection
for communication, a
maximum wait time
for the called party's
response is set in ms.
Typical value is 60
secounds (60000).
6
FasDllMaxConfirm
DelayOnData
For request of data,
a maximum wait time
for the called party's
response is set in ms.
Typical value is 60
secounds (60000).
Sub-
index
Parameter
Description
7
FasDllMaxDlsduSize
Specifies maximum DL
Service Data unit Size
(DLSDU). Set 256 for
Server and Trend VCR,
and 64 for other VCRs.
8
FasDllResidual
ActivitySupported
Specifies whether
connection is
monitored. Set TRUE
(0xff) for Server.
This parameter is
not used for other
communication.
9
FasDllTimelinessClass Not used for FVX110.
10
FasDllPublisherTime
WindowSize
Not used for FVX110.
11
FasDllPublisher
SynchronizaingDlcep
Not used for FVX110.
12
FasDllSubsriberTime
WindowSize
Not used for FVX110.
13
FasDllSubscriber
SynchronizationDlcep
Not used for FVX110.
14
FmsVfdId
Sets VFD for FVX110
to be used.
0x1: System/network
management VFD
0x1234: Function block
VFD
15
FmsMaxOutstanding
ServiceCalling
Set 0 to Server. It is
not used for other
applications.
16
FmsMaxOutstanding
ServiceCalled
Set 1 to Server. It is
not used for other
applications.
17
FmsFeatures
Supported
Indicates the type
of services in the
application layer.
In the FVX110, it is
automatically set
according to specific
applications.
35 VCRs are factory-set as shown in the Table 6.5.
Содержание FVX110
Страница 1: ...User s Manual FVX110 Fieldbus Segment Indicator IM 01S01C01 01EN IM 01S01C01 01EN 4th Edition ...
Страница 15: ... 2 Handling Cautions 2 4 IM 01S01C01 01EN ...
Страница 16: ... 2 Handling Cautions 2 5 IM 01S01C01 01EN ...
Страница 17: ... 2 Handling Cautions 2 6 IM 01S01C01 01EN ...
Страница 18: ... 2 Handling Cautions 2 7 IM 01S01C01 01EN ...
Страница 19: ... 2 Handling Cautions 2 8 IM 01S01C01 01EN ...
Страница 20: ... 2 Handling Cautions 2 9 IM 01S01C01 01EN ...