<Appendix 2. Integrator (IT) Block>
A2-9
IM 01S01C01-01EN
4.) Judging OUT_TRIP and OUT_PTRIP (see A2.5)
OUT_TRIP and OUT_PTRIP are judged again on the basis of the cleared integrated values.
There are three options relating to a reset:
i Confirm reset (bit 8 of INTEG_OPTS)
ii Carry (bit 6 of INTEG_OPTS)
iii Generate reset event (bit 9 of INTEG_OPTS)
i Confirm reset (bit 8 of INTEG_OPTS)
If this option is enabled, the next reset is rejected until "1" is set to RESET_CONFIRM.
ii Carry (bit 6 of INTEG_OPTS)
If this option is enabled while INTEG_TYPE is UP_AUTO or DN_AUTO, the value exceeding the threshold
at a reset will be carried into the next integration.
If INTEG_TYPE is any setting other than UP_AUTO or DN_AUTO, this option is irrelevant.
iii Generate reset event (bit 9 of INTEG_OPTS)
If this option is enabled, an alert event is generated if a reset occurs.
A2.7 List of Integrator Block Parameters
Index
Parameter
Name
Initial
Value
Write
Mode
View
Definition
1 2 3 4
0
BLOCK_
HEADER
TAG:“IT”
Block
Tag=O/S
Information relating to this function block, such as block tag, DD revision,
execution time
1
ST_REV
0
---
2 2 2 2 The revision level of the set parameters associated with the Integrator
block
2
TAG_DESC
Null
Stores comments describing tag information.
3
STRATEGY
1
2
The strategy field is used by a high-level system to identify the function
block.
4
ALERT_KEY
1
1 Key information used to identify the location at which an alert occurred
5
MODE_BLK
4
4
Integrator block mode. O/S, MAN, and AUTO are supported.
6
BLOCK_ERR
---
2
2
Indicates the active error conditions associated with the function block in
bit strings.
7
TOTAL_SP
1000000.0
4
4
The setpoint of an integrated value or a start value for counting down
8
OUT
MAN
5
5
The block output
9
OUT_RANGE 1000000.0
11
Set scaling for output display. This does not affect operation of the function
block.
It is used for making memos.
0.0
m3(1034)
0
10
GRANT_DENY
0
2
The parameter for checking if various operations have been executed
11
STATUS_
OPTS
0
O/S
2 Allows you to select a status-related option.
The Integrator block uses "Uncertain if Man mode" only.
12
IN_1
0.0
5
5
Inputs flow (Rate, Accum) signals from the AI block or PID block.
13
IN_2
0.0
5
5
14
OUT_TRIP
0
2
2
An output parameter informing the user that the integrated value has
exceeded the setpoint
15
OUT_PTRIP
0
2
2
An output parameter informing the user that the integrated value is
reaching the setpoint
16
TIME_UNIT1
sec(1)
MAN
1
Set the time unit of the rate (kg/s, lb/min, kg/h ... etc.) of the corresponding
IN.
17
TIME_UNIT2
sec(1)
MAN
1
18
UNIT_CONV
1.0
4 Specify the unit conversion factor for standardizing the unit of IN_2 into
that of IN_1.
19
PULSE_VAL1
1.0
MAN
4 Set the factor for converting the number of pulses for the corresponding
IN into an appropriate engineering unit.
20
PULSE_VAL2
1.0
MAN
4
21
REV_FLOW1
0
2
2
Selector switch used to specify the fluid flow direction (forward/reverse)
with respect to the corresponding IN
22
REV_FLOW2
0
2
2
23
RESET_IN
0
2
2
The parameter that receives a reset request from an external block to
reset the integrated values
24
STOTAL
0.0
4
Indicates the snapshot of OUT just before a reset.
25
RTOTAL
0.0
MAN
4
4
Indicates the integrated value of the absolute values of the increments if
the input status is "Bad."
Содержание FVX110
Страница 1: ...User s Manual FVX110 Fieldbus Segment Indicator IM 01S01C01 01EN IM 01S01C01 01EN 4th Edition ...
Страница 15: ... 2 Handling Cautions 2 4 IM 01S01C01 01EN ...
Страница 16: ... 2 Handling Cautions 2 5 IM 01S01C01 01EN ...
Страница 17: ... 2 Handling Cautions 2 6 IM 01S01C01 01EN ...
Страница 18: ... 2 Handling Cautions 2 7 IM 01S01C01 01EN ...
Страница 19: ... 2 Handling Cautions 2 8 IM 01S01C01 01EN ...
Страница 20: ... 2 Handling Cautions 2 9 IM 01S01C01 01EN ...