Table 11.2
Contents of DEVICE_STATUS_2 (index 1046)
Hexadecimal
Diplay through DD
Description
NAMUR
NE-107 category
0x80000000
LTB in O/S Mode
LCD Transducer Block is in O/S mode
C
0x40000000
LCD Failure
LCD has been failing
F
0x20000000
Amp Temp Out of Range
Amplifier temperature is out specification range
S
0x00008000
MAO1 in O/S Mode
MAO1 Block is in O/S mode
C
0x00004000
MAO1 in Man Mode
MAO1 Block is in Man mode
C
0x00002000
MAO1 Not Scheduled
MAO1 Block is not scheduled
C
0x00000800
MAO2 in O/S Mode
MAO2 Block is in O/S mode
C
0x00000400
MAO2 in Man Mode
MAO2 Block is in Man mode
C
0x00000200
MAO2 Not Scheduled
MAO2 Block is not scheduled
C
0x00000080
IS1 in O/S Mode
IS1 Block is in O/S mode
C
0x00000040
IS1 in Man Mode
IS1 Block is in Man mode
C
0x00000020
IS1 Not Scheduled
IS1 Block is not scheduled
C
0x00000008
IS2 in O/S Mode
IS2 Block is in O/S mode
C
0x00000004
IS2 in Man Mode
IS2 Block is in Man mode
C
0x00000002
IS2 Not Scheduled
IS2 Block is not scheduled
C
Table 11.3
Contents of DEVICE_STATUS_3 (index 1047)
Hexadecimal
Diplay through DD
Description
NAMUR
NE-107 category
0x80000000
PID1 in O/S Mode
PID1 Block is in O/S mode
C
0x40000000
PID1 in Man Mode
PID1 Block is in Man mode
C
0x20000000
PID1 Not Scheduled
PID1 Block is not scheduled
C
0x10000000
PID1 in Bypass Mode
PID1 Block is in Bypass mode
C
0x08000000
PID2 in O/S Mode
PID2 Block is in O/S mode
C
0x04000000
PID2 in Man Mode
PID2 Block is in Man mode
C
0x02000000
PID2 Not Scheduled
PID2 Block is not scheduled
C
0x01000000
PID2 in Bypass Mode
PID2 Block is in Bypass mode
C
0x00080000
SC in O/S Mode
SC Block is in O/S mode
C
0x00040000
SC in Man Mode
SC Block is in Man mode
C
0x00020000
SC Not Scheduled
SC Block is not scheduled
C
0x00008000
IT in O/S Mode
IT Block is in O/S mode
C
0x00004000
IT in Man Mode
IT Block is in Man mode
C
0x00002000
IT Not Scheduled
IT Block is not scheduled
C
0x00001000
IT Total Backup Err
IT Total Backup has failed. Last IT Output.Value(IT.LAST.
VALUE) is not saved
F
0x00000800
IT Conf. Err
IT Clock Period(IT.CLOCK_PER) is smaller than IT
Period of Execution(EXECUTION_PERIOD)
C
0x00000080
AR1 in O/S Mode
AR1 Block is in O/S mode
C
0x00000040
AR1 in Man Mode
AR1 Block is in Man mode
C
0x00000020
AR1 Not Scheduled
AR1 Block is not scheduled
C
0x00000010
AR1 Range Conf. Err
AR1 Range High(AR1.RANGE_HI) is smaller than AR1
Range Lo(AR1.RANGE_LO)
C
0x00000008
AR2 in O/S Mode
AR2 Block is in O/S mode
C
0x00000004
AR2 in Man Mode
AR2 Block is in Man mode
C
0x00000002
AR2 Not Scheduled
AR2 Block is not scheduled
C
0x00000001
AR2 Range Conf. Err
AR2 Range High(AR2.RANGE_HI) is smaller than AR2
Range Lo(AR2.RANGE_LO)
C
Содержание FVX110
Страница 1: ...User s Manual FVX110 Fieldbus Segment Indicator IM 01S01C01 01EN IM 01S01C01 01EN 4th Edition ...
Страница 15: ... 2 Handling Cautions 2 4 IM 01S01C01 01EN ...
Страница 16: ... 2 Handling Cautions 2 5 IM 01S01C01 01EN ...
Страница 17: ... 2 Handling Cautions 2 6 IM 01S01C01 01EN ...
Страница 18: ... 2 Handling Cautions 2 7 IM 01S01C01 01EN ...
Страница 19: ... 2 Handling Cautions 2 8 IM 01S01C01 01EN ...
Страница 20: ... 2 Handling Cautions 2 9 IM 01S01C01 01EN ...