9-6
<Toc> <Ind>
<9. Configuration >
IM 34M6H28-01E
1st Edition : Feb.01,1999-00
R:
System reserved
EX:
Message communications
P:
I/O communications: Polling
ST:
I/O communications : Bit strobe
•
The I/O data offset is the relative position from the beginning of every I/O data buffer.
The unit for the I/O data offset/size is bytes.
•
The input data size of a Bit Strobe should be less than or equal to 8 bytes.
•
Set the size/offset to 0 when no I/O communications are being carried out.
•
Registration is not possible during scanning.
2) Read device
Reads device information of a node from the scan list.
• Request
T090104-4.EPS
Data position no.
Content
400
Command = $04
401
Node number
• Response (normal exit)
T090104-5.EPS
Data position no.
Content
400
Command = $04
401
Node number
402
Vendor ID
403
Device type
404
Product code
405-407
Reserved
408
Communications type
409-411
Reserved
412
Size of output data (bytes)
413
Offset of output data (bytes)
414-415
Reserved
416
Size of input data (bytes)
417
Offset of input data (bytes)
418-426
Reserved
• Response (error exit)
T090104-6.EPS
Data position no.
Content
400
$8004
401
Exit code