<10. Errors and Troubleshooting >
10-7
IM 34M6H28-01E
1st Edition : Feb.01,1999-00
10.6 Error Codes
This module conveys error status not only by LED but also by input relay (X
■■■
■■■
01 to 16),
error codes and other node error information.
The error codes within the module information of the input/output data register and the
node error information is of latched type. The latest error information is maintained until a
Request to Clear Error is executed.
The error codes are given in Table 10.1.
Table 10.1 Error Codes
Item
EC1
EC2
Relay
OT
MS-LED
NS-LED
Description
Internal error
$1005
–
1
No
Red On
Off
Internal discrepancy in the basic
program
Memory error
$1203
–
1
No
Red On
Off
RAM error
Flash memory
error 1
$1281
–
1
No
Red On
Off
Error in the part of flash memory
which stores the program
Flash memory
error 2
$1282
–
1
No
Red On
Off
Error in the part of the flash
memory which stores DeviceNet
information
Flash memory
error 3
$1283
–
1
No
Red On
Off
Failure in storing scan list and
transmission time interval in flash
memory
Watchdog timer
error
$1285
–
1
No
Red On
Off
Watchdog timer error
CAN error 1
$1286
–
1
No
Red On
Off
CAN controller error (cannot
cancel reset)
CAN error 2
$1287
–
1
No
Red On
Off
CAN controller error (data bus
error)
CAN error 3
$1288
–
1
No
Red On
Off
CAN controller error (address bus
error)
System failure
$1289
–
8
No
–
–-
System failure occurred
Node Busy
$1305
Node no.
4
Yes
Green On
Red
flashing
Communications not possible
because of communicating with
another master
Switch setting
invalid
$E111
Data
position no.
1
No
Red
flashing
Off
Switch setting error (node
address, data rate, etc)
Network power
error
$E112
–
3
No
Green On
Off
No power to network
Duplicate node
address
$E121
Node no.
2
No
Green On
Red On
The current node has the same
address as another node and as a
result cannot join the network
Bus-off detected
$E122
–
2
No
Green On
Red On
Numerous data errors on the
network
Node absent
$E141
Node no.
4
Yes
Green On
Red
flashing
No response from the registered
node in the scan list
Node information
mismatch
$E142
Node
address
4
Yes
Green On
Red
flashing
The information read from the
scan list and node differs.
Scan list not
registered
$E143
–
7
No
–
–
There are no registered devices in
the scan list. There is nothing
stored in the flash memory.
T1001.EPS
Relay: The input relay no. (** in X
■■■
■■■
**) that is on in the status.
OT: Reflected in the error code storage information of other nodes (input/output data
registers 29 to 32)
Содержание FA-M3 Vitesse
Страница 2: ...Blank Page...
Страница 28: ...Blank Page...
Страница 40: ...Blank Page...
Страница 94: ...Blank Page...
Страница 116: ...Blank Page...
Страница 118: ...Blank Page...