IM 34M06H28-01E-003
Jun. 2017
1/2
Yokogawa Electric Corporation
Addendum
Manual No
:
IM 34M06H28-01E
Manual Name
:
DeviceNet Scanner Module
Edition :
1st
Edition
Page 4-2, “Table 4.2 General Specifications”
Add the following note, “*2”.
Items Specifications
Transmission
distance*
2
Data rate
Maximum length of trunk line
Length of drop line
Only thick
cables
Only thin cables
Maximum
Cumulative
125 kbps
500 m
100 m
6 m
156 m
250 kbps
250 m
78 m
500 kbps
100 m
39 m
*2: To comply with the standard, the outdoor cable shall be less than 10m, the indoor cable shall be
less than 30m.
Page 5-3
In the text, replace 0.5N.m. with 0.5N-m (4.4 lbf-in).
Page 5-4
In the text, replace 0.3N.m. with 0.3N-m (2.7 lbf-in).
Page 5-4, “Attaching the connector to this module”
Add the following caution text.
■
External Wiring
To ensure compliance to CE Marking for a system incorporating this module, use a
shielded cable for connecting to the module and the outdoor cable shall be less than 10m,
the indoor cable shall be less than 30m.
Or peel off part of the insulation on the both ends of shielded cable to expose the shields,
and apply FG clamps to the shields to secure and ground them.
Peel off insulation and
apply an FG clamp to
the exposed shield.
Shielded cable
Screw the FG clamp
to the metal plate of
the panel enclosure
for grounding.
User’s
Manual
DeviceNet Scanner Module
Содержание FA-M3 Vitesse
Страница 2: ...Blank Page...
Страница 28: ...Blank Page...
Страница 40: ...Blank Page...
Страница 94: ...Blank Page...
Страница 116: ...Blank Page...
Страница 118: ...Blank Page...