<Toc> <Ind>
<4. Module Specifications >
4-5
IM 34M6H28-01E
1st Edition : Feb.01,1999-00
4.6
Setting Switches
An explanation about the switch settings of this module is given in this section.
4.6.1
Node Address Setting Switch
Node addresses can be set using 2 decimal rotary switches which are on the front side of
this module.
Set the switch to a value from 0 to 63, before switching the power supply on. If the switch is
set to 64 or higher, operation will not be normal.
Settings that are mode after switching the power supply on have no effect.
The factory setting is 0.
F0402.EPS
Upper switch: 10-position
Lower switch: 1-position
NODE
ADDRESS
Figure 4.2 Node Address Setting Switch
4.6.2
Operation Mode Setting Switch
Four DIP switches can be seen when the cover on the right side of the module is removed.
The operation mode is set by setting the switches to on or off.
Set the switches before switching the power supply on.
Settings that are made after turning the power supply on have no effect.
The factory setting for all the switches is off.
F0403.EPS
O
F
F
• Data rate
Number
Status of number 1
Status of number 2
Data rate
Functions
Data rate (see the table below.)
System reserved (Make sure it is off)
2
1
3
4
125 kbps
250 kbps
500 kbps
Invalid setting
Off
Off
On
On
Off
On
Off
On
Figure 4.3 Operation Mode Setting Switches