<Appendix 1. Details on Network Configuration >
Appx.1-9
IM 34M6H28-01E
• Configuration example 2
Node
0.1A
Node
0.1A
Node
0.1A
100 m thick cable
150 m thick cable
Node
0.05A
Node
0.1A
Network
power supply
Terminating resistor
FAP0110.EPS
Terminating resistor
Figure 1.10
Network Power Supply Configuration (Example 2)
Total length of network on right side = 150 m
Total current consumption on right side = 0.1 A + 0.05 A + 0.1 A = 0.25 A
Maximum current capability of 150 m of a thick cable = 2.01 A
Total length of network on left side = 100 m
Total current consumption on left side = 0.1 A + 0.1 A =0.2 A
Maximum current capability of 100 m of a thick cable = 2.93 A
In both the right and left networks, the total electricity consumption is less than the max.
current capability of cables, so this network configuration is possible.
1st Edition : Feb.01,1999-00