<Appendix 1. Details on Network Configuration >
Appx.1-5
IM 34M6H28-01E
Appendix 1.3
Terminating Resistor
Installing terminating resistors (121
V
) at both ends of a trunk line reduces reflection and
stabilizes communications.
The terminating resistor should satisfy the following specifications.
•
121
V
•
1% of metallic film resistance
•
1/4 W
Terminating resistors are in-built in this module. When connecting to the terminals of a
trunk line using the daisy chain method, turn on the terminating resistor setting switch and
use the built-in terminating resistors. In situations other than this, make sure that the switch
is off and the terminating resistors are not in use.