Parameter setting 5-27
IM 12J6B3-E-H
Code
Display
Function
Function detail
X
Y
Z
Default values
User Interface
50
*RET
Auto return
No return to meas. from HOLD
0
1
Return to meas after 10 min
1
51
*MODE
add. to MAINT
Setpoint adj. disabled
0
0.0.0
Setpoint adj. also in MAINT
1
Wash start disabled
0
Wash start in maintenance mode
1
Manual pressure disabled
0
Manual pressure enabled
1
52
*PASS
Password
Direct access to MAINT
0
0.0.0
MAINT protected by password
#
Direct access to COMM
0
COMM protected by password
#
Direct access to SERV
0
SERV protected by password
#
53
*Err.01
Error setting
Response & Time failure
Soft fail
0
Response & Time failure
Hard fail
1
1
Hard
*Err.02
Zero calibration
Soft fail
0
Zero calibration
Hard fail
1
1
Hard
*Err.03
Slope calibration
Soft fail
0
Slope calibration
Hard fail
1
1
Hard
*Err.04
Membrane failure
Soft fail
0
Membrane failure
Hard fail
1
1
Hard
*Err.07
Temperature sensor open
Soft fail
0
Temperature sensor open
Hard fail
1
1
Hard
*Err.08
Temp. sensor shorted
Soft fail
0
Temp. sensor shorted
Hard fail
1
1
Hard
*Err.09
Cell current abnormal
Soft fail
0
Cell current abnormal
Hard fail
1
1
Hard
*Err.12
Abnormal measured value
Soft fail
0
Abnormal measured value
Hard fail
1
1
Hard
*Err.16
Cell for maintenance
Soft fail
0
interval time exceeded
Cell for maintenance
Hard fail
1
1
Hard
interval time exceeded
*Err.22
Control time-out
Soft fail
0
0
Soft
Control time-out
Hard fail
1
*SOFT
LCD Fail Constant
0
0
LCD Fail
LCD only
1
54
*E12
overrange limit
E12 active at 0 - 300 % sat
150%
55
*CALL.M
E16 setting
No call for maintenance
0
0
Call for maint. enabled
1
*CALL .M
E16 message after 1- 250 days
30
56
*UNIT
PV unit
Unit of measurement mg/l
0
0
Unit of measurement ppm
1
Unit of measurement % sat.
2
57-59
Not used
Pass: 111 for #=1,
333 for #=2,
777 for #=3,
888 for #=4,
123 for #=5,
957 for #=6,
331 for #=7,
546 for #=8 and
847 for #=953