* To be installed at the position where the air 
  delivered from the unit can reach every comer of 
  the room.
* To avoid being affected by the outdoor air.
* To avoid blockage to the air inlet or outlet of the unit.
* To avoid too much oil, smoke or steam.
* To avoid possible generation, inflow, lingering or 
  leakage of flammable gases.
* To avoid high-frequency facilities (such as high 
  frequency arc welders, etc.).
* To avoid the places where acid solutions are 
  frequently used.
* To avoid the places where some special sprayers 
  (sulfides) are frequently used.

* Not to install on top of the musical instruments, TV, 
  computer etc. valuable appliance.
* Not to install a fire alarming device near the air 
  outlet of the unit (during operation, the fire alarm 
  device might be erroneously triggered by the warm 
  air from the unit).

All Units Shall Be Installed by Licensed Contractor or Technician.

Read Manuals before Installation.

Check the unit for damage and missed parts or accessories. If damage is found or parts are found missing, call 
the distributor right away.
Spin fan wheels and blades to check and make sure they can rotate freely. If fan wheel scratches with housing, 
call the distributor right away and do not to proceed with the installation before it is fixed.
Check the unit to make sure no foreign materials have been left in the unit.
Check all the parts and accessories that are needed other than those provided with the unit. 
It is strongly recommended to only use YMGI supplied or recommended parts and accessories.
Be sure a properly sized circuit breaker is for the electric power to the units.
Pre-build the support platform on the ground or bracket for the wall before or during construction and before 
installation. Refer to the table below for footprint dimensions.
Read installation instructions of all units thoroughly.
Ask rep./distributor/us anything you are not sure about.
Get your tools and parts ready for installation.

CAUTION & SUGGESTIONS TO FOLLOW PRIOR TO INSTALLATION

* Either the indoor unit or the outdoor unit can be 
  higher, but the height difference must comply the 
  stated requirements.
* Try to reduce the bending of the piping line as much 
  as possible so as to avoid possible negative impacts 
  upon the performances of the units.
* Make P-trap if elevation drop difference is more 
  than 25", as illustrated below.  

Indoor unit

Outdoor unit

Lift

Indoor unit

Outdoor unit

Drop

Oil-Trap

18 Ft

Locate the central hole at the stud (firn structure)

At least 6"

6" or more 
from sidewall

Respect the slope

Plumb

Mounting Plate

Anchors of self-
tappping screw

6" or 

more from 

sidewall

Install Mounting Plate and Drill Hole for Combination of Copper Line/Wire Cable/Drain Hose

NOTES: 

Anchors must be put into the holes, where the solid 
arrows are pointing, as shown above, to secure the 
mounting plate firmly and to hold the weight of indoor 
unit. If more screws/anchors are to be used, make 
sure to keep the two holes close to each other, at 
least 2 inches apart.

Mounting plate should be attached to the structural 
part of the wall. Minimum clearance, as shown below, 
is required in order to ensure proper airflow and 
enough service room.

      INSTALL WALL MOUNT PLATE

* Check unit to make sure the unit is in good shape and ready to install.

* Check unit to make sure the installation location is firm enough to hold the weight of the whole unit and is 
  convenient to install, maintain, and service.

* Install Indoor unit. Enough anchor bolts/nuts shall be used to secure mounting plates for indoor units. 
  Brackets should be at level position.

Mark drill positions. At least 4 anchor holes, one at each perimeter corner of the plate are needed to secure the 
plate, where the bold arrows are pointing, as shown in the picture above. Refer to the specification sheet for 
unit weight so that enough anchors are installed at proper positions.

Pre-drill guiding holes where are marked for anchors or screws on the wall

Confirm the position of the holes and finish drill to the depth needed for anchors (NOT for screws)

Align mounting plate holes with those holes drilled on the wall and put anchors or screws into the holes to 
secure mounting plate.

STEPS TO MOUNT PLATE:

a

b

c

Drill mounting holes 
to make sure at least 
either one of three 
dimensions a, b and 
c is 16" center to 
center.

INSTALLATION-INDOOR UNIT

INSTALLATION POSITIONS FOR OUTDOOR UNIT

INSTALLATION LOCATIONS & CAUTIONS

If pipes need to come out of the right side (facing 
the front of indoor unit) of the indoor unit, snap off 
portion

1

on plastic casing.

If pipes need to come out of the bottom side 
(facing the front of indoor unit) of the indoor unit, 
snap off portion

2

on plastic casing.

If pipes need to come out of the left side (facing 
the front of indoor unit) of the indoor unit, snap off 
portion

3

on plastic casing.

DRILL 3IN HOLE FOR PIPING/WIRING/DRAIN

Locate the center where the hole will need to 
drilled.

Drill the holes of 2.5-3Inch diameter. A down pitch 
about 1/4" per foot, as illustrated below, is needed 
for the hole, in order to drain the condensate 
properly.

PREPARE INDOOR UNIT- COPPER LINE SET/DRAIN HOSE

1

《 》

2

《 》

3

INST

ALLER'S 

INSTRUCTION

INST

ALLER'S 

INSTRUCTION

P23 OF 44

P24 OF 44

* The location and structure shall also be convenient for both installation and service.
* The location shall NOT be where discharge air and noise could bother your neighbor.

* The location shall NOT be somewhere drain may cause any damage to property or bother the neighbor.

* The location shall NOT be somewhere soldering or torching work may cause fire or smoke to the materials around.

* The location shall NOT be somewhere near flammable gases.

* The location shall NOT be in or close to corrosive gases.

* The location shall NOT be somewhere children can access.

Hole Diameter: 2.5~3 In

Align ruler 
with straight 
line

Hanger certer

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

Содержание WMMS-09K-V2A(57)2

Страница 1: ...in material and workmanship for normal use and maintenance Installation operation maintenance and service shall follow professional practices for regular cooling and heating equipment NEC State City...

Страница 2: ...etails may vary and some may be the key to determine the success and quality of the installation Experience with certain manufacturer may not be applied fully to another manufacturer For example wirin...

Страница 3: ...s and wires are to be installed 11 If all the suggestions have been taken and all the necessary steps are followed CUSTOMER AND TECHNICIAN MUST READ The cost of not having your unit installed properly...

Страница 4: ...rical power V Ph Hz measured at wiring terminal block of Indoor unit outdoor unit 7 Wire gauge length and terminal colors between circuit breaker disconnect switch to outdoor unit 9 The size of HVAC c...

Страница 5: ...rience or professional knowledge to correct the problem RECEIVING AND FREIGHT DAMAGE ATTENTION Freight package unit shall be checked thoroughly for damage at receiving before accepting by signing on t...

Страница 6: ...help you in the following steps in sequence from 1 to 3 CUSTOMER AND TECHNICIAN MUST READ If the damage is minor or partial that you choose to accept you can contact the distributor or YMGI to discus...

Страница 7: ...Customer Request to Ship Products to YMGI Service Center for Inspection and Repair and Authorization to Charge form 2 You will review the form and fill all fields appropriately sign and send back to t...

Страница 8: ...ons of general up flow condensing units are limited such as apartments condos lofts multi families and high rise buildings and others named or unnamed Indoor unit s delivers the thermal and acoustical...

Страница 9: ...6 7 25 3 5 3 6 7 x 30 1 8 18 Cooling Speed SH H M L RPM 1300 1100 900 700 1350 1150 950 750 1400 1150 1000 850 1350 1150 1000 850 19 Heating Speed SH H M L RPM 1300 1140 980 820 1350 1190 1020 850 145...

Страница 10: ...s can be installed on a wall or balcony close to the indoor unit the following are some benefits for contractors and customers Each system is thoroughly tested before leaving the factory Each unit is...

Страница 11: ...27 6 37 9 37 6 Model 09K 12K 18K 24K Unit W 30 30 35 0 35 0 D1 12 6 21 3 11 3 12 6 21 3 11 3 15 6 22 0 22 0 14 3 14 3 15 6 D 10 1 10 1 13 4 13 4 P20 OF 44 USER NOTES AND SERVICE LOG 6 6 12 100 6 20 12...

Страница 12: ...Tape Level Flash Light Screw Driver Phillps and Flat Hammer Knife Scissors Goggled Glass Mask Gloves Ladder 2 Refrigeration Related Work RECOMMENDED TOOLS FOR INSTALLATION 3 Electrical Related Instal...

Страница 13: ...ors are to be used make sure to keep the two holes close to each other at least 2 inches apart Mounting plate should be attached to the structural part of the wall Minimum clearance as shown below is...

Страница 14: ...in condensing unit othewise condensate may ice up causing damage to the condensing unit Suggest to use YMGI provided brackets and condensate drainage fitting accessories Indoor unit front Bottom the r...

Страница 15: ...perpendicular to the pipe surface Don t cut too fast or too hard Turn and tighten the tube cutter slowly Remove residual left and de bur at the cutting edge The cutting edge should be clear and clean...

Страница 16: ...ation securely on the external wall with proper clamps at 6 feet apart Fill the gap between the wall hole and wall sleeve with putty to keep from rain or dust entering inside PIPING GUIDE Set the pack...

Страница 17: ...frigerant Charge Level Reference Temperature Pressure Table Split Condensing Unit R410A AC Product Series YMGI Group Mini Split Version 01 11 2010 Reference Temperature Pressure Table Split Condensing...

Страница 18: ...ng indoor fan motor works Heating all stop running 3s off blink four times 1 Forcibly lift up the panel at a specific angle from the two ends of the front panel following the arrow direction Then pull...

Страница 19: ...e is not staable cooling dehumidifying compressor will stop indoor fan motor works Heating all will stop 1 Check the Input voltage if the Voltage is lower than 150VAC restart the machine when the powe...

Страница 20: ...protection Heating LED Off 3S Blinks 6 times HE Compressor de managet protection rotor locked doesn t rotate Heating LED Off 3S Blinks 14 times L0 Airflow switch error TBD L1 Humidity sensor error TB...

Страница 21: ...uring gas sensor error Running LED Off 3S Blinks 21 times HP Solar AC solar power input voltage is higher than 180V TBD dA AHU or RT discharge air relative humidity sensor error TBD dE AHU or RT fresh...

Страница 22: ...r Cooling LED Off 3S Blinks 7 times FC Slide door error or air louver mechanism error TBD FE Over load sensor error TBD H8 Water level high overflow protection Heating LED Off 3S Blinks 8 times H9 Ele...

Страница 23: ...the unit and or know more details than anybody else They will check the unit and find out the problems with the professional knowledge about HVAC and electric product installation by using special to...

Отзывы: