background image

INST

ALLER'S 

INSTRUCTION

INST

ALLER'S 

INSTRUCTION

P31 OF 44

OPERATION FREQUENCY

CONDENSING PRESSURE (MPa (G))

580

4.0

3.5

3.0

2.5

2.0

1.5

0

507

435

362

290

217

0

20

40

60

80

100

120

140

CONDENSING PRESSURE (PSI (G))

SYSTEM INSPECTION AND TRIAL RUNNING

Evacuate the pipes  between indoor and outdoor units, using vacuum pump and manifold/gauge set, to a 
minimum of 500 microns (service valves remain front seated). Hold for 30 minutes to check if the vacuum level is 
maintained. Using dry nitrogen or other leakage detection tool for leak checking. Be certain there is no pressure 
in the system when repairing a leak.

VACUUM REFRIGERANT PIPES

VACUUM AND LEAKAGE CHECK

P32 OF 44

CHECK AFTER INSTALLATION AND TEST OPERATION

1) Before test operation

1) Do not turn on power before installation is finished 
    completely.
2) Electric wires must be connected correctly and 
    securely.
3) Cut-off valves of the connection pipes should be 
    back seated/turned on.
4) All the left over installation material scraps must be 
    cleared away from the unit before initial start up.

2) Test operation method

1) Switch on power, press "ON/OFF" button on the 
    wireless remote control to start the operation.

2) Press MODE button, to select the COOL, HEAT 
    (not available for cooling only unit's ), FAN and so 
    on to check :

* All the functions (to make sure the unit functions 
  correctly and properly).

* Refrigerant (pressures/temperatures at service 
  values/pipes should be good).

* Drainage (condensate/water flow should be 
  dripping out of drainage pipe ONLY).

* Noise (there should be not any abnormal sound).

Has the unit been positioned firmly? 

The unit may drop, shake or emit noise.

Have you done the refrigerant leakage test?

It may cause insufficient cooling(heating), or compressor 
overheating, or other unit malfunctions.

Is heat insulation sufficient?

It may cause unexpected condensate and dripping.

Is drainage pipe tested ?

 It may cause leakage or 

g.

unexpected drippin

Is the voltage in accordance with the rated voltage marked on 
the nameplate?

It may cause unit malfunction or damage to the part/unit.

Is the electrical wires and pipes connection installed correctly 
and securely?

It may cause unit malfunction or damage to the part/unit.

Has the unit been connected to a secure ground connection?

It may cause electric leakage.

Is the power cord specified properly per NEC codes ? 

It may cause wire overheat or even fire.

Is the air inlet and outlet been cleared?

It may cause insufficient cooling/heating capacity, and 
unexpected noise.

CHECK AFTER INSTALLATION

TEST OPERATION

SYSTEM INSPECTION AND TRIAL RUNNING

Vacuum and Check Leakage before Releasing Refrigerant from Outdoor Unit to Indoor Unit

Service valve

Hexagon 
Allen wrench

3-way valve

Blank cap

Refrigerant pipe

Outdoor unit

Cap

Service hose 
with valve core

Compound pressure gauge

Gauge manifold

Pressure gauge

High pressure 
side valve 
(closed)

Service hose

Vacuum pump

Service hose

Low pressure 
side valve

-100 kPa
-76cm.Hg
-1 bar

(For a description of how to use the 
gauge manifold, refer to the gauge 
manifold operation manual.)

Warning: 

R410A refrigerant bears higher pressures than R22. 

Only handled by Licensed HVAC technician.

Outdoor Dry-Bulb (F)

Outdoor Dry-Bulb (C)

Outdoor Wet-Bulb (F)

Outdoor Wet-Bulb (C)

Indoor Dry-Bulb

Indoor Wet-Bulb

Discharge-PSI/F

Suction-PSI/F

15

-9.4

13.6

-10.2

25

-3.9

23.0

-5

35

1.7

30.2

-1.0

50

10.0

42.8

6.0

55

12.8

46.9

8.3

60

15.6

51.1

10.6

67

19.4

59.5

15.3

75

23.9

66.6

19.2

82

27.8

64.9

18.3

90

32.2

71.2

21.8

95

35.0

75.0

23.9

100

37.8

79.0

26.1

105

40.6

82.9

28.3

110

43.3

86.9

30.5

115

46.1

90.7

32.6

74/21.2 

84/27.1  105/35.1  115/38.5  125/42.8  130/45.5  140/48.2  146/51.2  156/54.3  166/57.5  175/61.2  180/62.5  186/63.7  189/64.5  191/64.9

60/46.2 

70/53.5 

85/55.2 

92/55.7 

98/56.1  103/56.7  110/56.9  115/57.1  120/57.5  128/57.8  135/57.9  136/58.6  137/59.1  139/59.3  140/59.5

80F (26.7C)

67F (19.4C)

Suggest to Add on Low Ambient Control, If Still
in Need of AC for Long Time In Cold Weather.
Closely Check/Watch Refrigerant Charge Level.

Reference Temperature-Pressure Table (Split Condensing Unit-R410A AC)
Product Series: YMGI Group-Mini Split    Version: 01/11/2010

Reference Temperature-Pressure Table (Split Condensing Unit, R410A-Heat Pump)
Product Series: YMGI Group-Mini Split System    Version: 01/11/2010

Outdoor Dry-Bulb (F)

Outdoor Dry-Bulb (C)

Outdoor Wet-Bulb (F)

Outdoor Wet-Bulb (C)

Indoor Dry-Bulb

Indoor Wet-Bulb

Discharge-PSI/F

Suction-PSI/F

0

-17.8

-0.8

-18.2

5

-15

4.1

-15.5

10

-12.2

8.8

-12.9

17

-8.3

15

-9.4

25

-3.9

22.8

-5.1

30

-1.1

27.5

-2.5

35

1.7

28.9

-1.7

40

4.4

36.3

2.4

45

7.2

41.0

5

47

8.3

43.0

6.1

55

12.8

50.4

10.2

62

16.7

56.5

13.6

70F (21.1C)

60F (15.6C)

260/84

269/90

284.5/95

290/102

296/111

304/128

304/133

330/138

345/142

354/149

400/149

440/176

246/72

255/78

270/86

278/89

285/92

290/95

310/98

318/100

330/102

340/104

380/107

425/113

PRESSURE CHECKING

      CHECK SYSTEM THOROUGHLY

Check system thoroughly to make sure the unit is ready for trial running: 
check wires and pipes and air intake and discharge and power and 
thermostat and others necessary components. 

ADJUST REFRIGERANT-
GUIDELINE

Right amount of refrigerant is very important. It is one of the 
basics to ensure a safe operation over time.
Normally single zone outdoor unit is pre-charged with 
refrigerant for 25ft inter-connecting copper (liquid) line. 
Multiple zone outdoor unit is pre-charged for various length 
of copper (liquid) lines of allowed quantity of indoor units, 
following specs. or engineering submittal.
For single zone unit or multiple zone multiple compressor unit, 
normally the outdoor unit is pre-charged for 25ft line sets. If 
the copper line is longer or shorter than 25ft, need to add or 
deduct refrigerant, following general rule of thumb for rough 
adjustment: 1/4" liquid line unit: 0.3 Oz/ft; 
3/8" liquid line unit: 0.4 OZ/ft; 1/2" liquid line unit: 1.2 OZ/ft.
For multiple zone one compressor unit, if the copper line is 
longer or shorter than the length at which pre-charged 
refrigerant is good for, as listed in the engineering submittal 
or related labels or tables, need to add or deduct refrigerant, 
following 0.23 OZ/ft rule of thumb for rough adjustment.
In all situations, the minimum  copper line (liquid or gas) 
length for each indoor unit is 15ft.
For a better adjustment, may combine above guideline with
 the indoor or outdoor (ambient) temperature-refrigerant 
pressure chart, or generally 8-12F super-heat method. 

System pressure checking should be a must-do job during trial running of initial installation, and compressor/refrigerant-related trouble-
shooting.  It is a more accurate refrigerant adjusting method than rough refrigerant addition or deduction guideline shown above.
In some cases, if the service valve on unit is 5/16

 and your service valve connection is 1/4

, need to use a 5/16

-1/4

 adaptor so that 

you can connect to your manifold. Need to pay attention to use the right manifold that is rated for the refrigerant in the unit, and pay attention 
to connect to the right hose (blue hose for low pressure, red hose for high pressure, yellow hose for vacuum or charging or deduction). Not 
recommended to put hose onto service valve while compressor is running. Remove hose quickly and carefully to avoid air suck-in, refrigerant 
leakage, or any refrigerant-freezing burn. 
The following curves are only reference for system pressure checking. Actual pressures may vary upon many factors such as inter-connecting 
pipe length, refrigerant charge / leakage level, elevation difference between indoor unit and outdoor unit, tool calibration, reading error, and so 
on. 

Items to be checked 

Has the refrigerant pressure been checked or refrigerant 
been adjusted accordingly?

It may generate unexpected noise, freezing pipe, capacity 
issues, compressor or system damage or even worse.

Has the installing technician filled all the fields in the 
checklist inside the warranty registration card?

If not filed or not filled completely or correctly, your factory 
warranty may not be qualified.

Possible Problems or Consequences

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

Содержание WMMS-09K-V2A(57)2

Страница 1: ...in material and workmanship for normal use and maintenance Installation operation maintenance and service shall follow professional practices for regular cooling and heating equipment NEC State City...

Страница 2: ...etails may vary and some may be the key to determine the success and quality of the installation Experience with certain manufacturer may not be applied fully to another manufacturer For example wirin...

Страница 3: ...s and wires are to be installed 11 If all the suggestions have been taken and all the necessary steps are followed CUSTOMER AND TECHNICIAN MUST READ The cost of not having your unit installed properly...

Страница 4: ...rical power V Ph Hz measured at wiring terminal block of Indoor unit outdoor unit 7 Wire gauge length and terminal colors between circuit breaker disconnect switch to outdoor unit 9 The size of HVAC c...

Страница 5: ...rience or professional knowledge to correct the problem RECEIVING AND FREIGHT DAMAGE ATTENTION Freight package unit shall be checked thoroughly for damage at receiving before accepting by signing on t...

Страница 6: ...help you in the following steps in sequence from 1 to 3 CUSTOMER AND TECHNICIAN MUST READ If the damage is minor or partial that you choose to accept you can contact the distributor or YMGI to discus...

Страница 7: ...Customer Request to Ship Products to YMGI Service Center for Inspection and Repair and Authorization to Charge form 2 You will review the form and fill all fields appropriately sign and send back to t...

Страница 8: ...ons of general up flow condensing units are limited such as apartments condos lofts multi families and high rise buildings and others named or unnamed Indoor unit s delivers the thermal and acoustical...

Страница 9: ...6 7 25 3 5 3 6 7 x 30 1 8 18 Cooling Speed SH H M L RPM 1300 1100 900 700 1350 1150 950 750 1400 1150 1000 850 1350 1150 1000 850 19 Heating Speed SH H M L RPM 1300 1140 980 820 1350 1190 1020 850 145...

Страница 10: ...s can be installed on a wall or balcony close to the indoor unit the following are some benefits for contractors and customers Each system is thoroughly tested before leaving the factory Each unit is...

Страница 11: ...27 6 37 9 37 6 Model 09K 12K 18K 24K Unit W 30 30 35 0 35 0 D1 12 6 21 3 11 3 12 6 21 3 11 3 15 6 22 0 22 0 14 3 14 3 15 6 D 10 1 10 1 13 4 13 4 P20 OF 44 USER NOTES AND SERVICE LOG 6 6 12 100 6 20 12...

Страница 12: ...Tape Level Flash Light Screw Driver Phillps and Flat Hammer Knife Scissors Goggled Glass Mask Gloves Ladder 2 Refrigeration Related Work RECOMMENDED TOOLS FOR INSTALLATION 3 Electrical Related Instal...

Страница 13: ...ors are to be used make sure to keep the two holes close to each other at least 2 inches apart Mounting plate should be attached to the structural part of the wall Minimum clearance as shown below is...

Страница 14: ...in condensing unit othewise condensate may ice up causing damage to the condensing unit Suggest to use YMGI provided brackets and condensate drainage fitting accessories Indoor unit front Bottom the r...

Страница 15: ...perpendicular to the pipe surface Don t cut too fast or too hard Turn and tighten the tube cutter slowly Remove residual left and de bur at the cutting edge The cutting edge should be clear and clean...

Страница 16: ...ation securely on the external wall with proper clamps at 6 feet apart Fill the gap between the wall hole and wall sleeve with putty to keep from rain or dust entering inside PIPING GUIDE Set the pack...

Страница 17: ...frigerant Charge Level Reference Temperature Pressure Table Split Condensing Unit R410A AC Product Series YMGI Group Mini Split Version 01 11 2010 Reference Temperature Pressure Table Split Condensing...

Страница 18: ...ng indoor fan motor works Heating all stop running 3s off blink four times 1 Forcibly lift up the panel at a specific angle from the two ends of the front panel following the arrow direction Then pull...

Страница 19: ...e is not staable cooling dehumidifying compressor will stop indoor fan motor works Heating all will stop 1 Check the Input voltage if the Voltage is lower than 150VAC restart the machine when the powe...

Страница 20: ...protection Heating LED Off 3S Blinks 6 times HE Compressor de managet protection rotor locked doesn t rotate Heating LED Off 3S Blinks 14 times L0 Airflow switch error TBD L1 Humidity sensor error TB...

Страница 21: ...uring gas sensor error Running LED Off 3S Blinks 21 times HP Solar AC solar power input voltage is higher than 180V TBD dA AHU or RT discharge air relative humidity sensor error TBD dE AHU or RT fresh...

Страница 22: ...r Cooling LED Off 3S Blinks 7 times FC Slide door error or air louver mechanism error TBD FE Over load sensor error TBD H8 Water level high overflow protection Heating LED Off 3S Blinks 8 times H9 Ele...

Страница 23: ...the unit and or know more details than anybody else They will check the unit and find out the problems with the professional knowledge about HVAC and electric product installation by using special to...

Отзывы: