UNIT MAINTENANCE & 

SER

VICE GUIDE

INST

ALLER'S 

INSTRUCTION

TROUBLE SHOOTING

P33 OF 44

INSTALLATION AND MAINTENANCE OF ENHANCED FILTER

CONFIRMATION

1) Power Connection

    Check and confirm that the power breaker of proper size is installed and can operates (ON/OFF) normally.

2) Power Voltage

    

onfirm that power voltage is AC 208-230V

±

10%. If power voltage is not falling  in this range, the 

    unit may not operate properly and damage may be caused.

Check and c

FLASHING LED OF INDOOR/OUTDOOR UNIT AND PRIMARY JUDGEMENT

P34 OF 44

Take out the (enhanced) filter before cleaning according to the installation instruction. Pay special attention tthat
silver ion filter can't be cleaned with water, while active carbon, photo catalyst, low temperature conversion (LTC) 
catalyst, formaldehyde eliminator, ca-techin or mite killing filter can (but can't be cleaned with brush or hard/sharp
tools). Dry and reinstall it after cleaning. Make sure to replace securely and properly.

CLEANING AND MAINTENANCE (Regular Filter and/or Other Enhanced Filters)

FILTER LIFETIME

The washable filter will last a long time. But some (enhanced) filters may only have a lifetime of about one year 
under normal conditions. As far as  the silver ion filter, it will become invalid when its surface becomes black (green).

INSTALLATION INSTRUCTIONS

No.

Indoor unit display

Double 8 display

Indicator display (LED 
blinks 0.5s-ON/0.5s-
OFF)

Running 
LED

Cooling 
LED

Heating 
LED

D40 D41 D42 D43

Outdoor unit 
display (LEDs 
have 3 status)

Unit actions

Possible clauses 

(Primary judgement)

High pressure of system, might be:
1) Refrigerant is too much;
2) Poor heating exchanging for units 
    (including heat exchanger is dirty 
    and unit heating radiating ambient 
    is poor);
3) Ambient temp. is too high.

E1

E2

Cooling, dehumidifying, except the 
indoor fan motor is running, others 
will stop running. 

Cooling, dehumidifying: compressor, 
outdoor fan motor will stop running, 
indoor fan motor will keep running.

☆ ☆

■ □

■ □

1) Poor indoor unit air returning;
2) indoor fan motor rotating speed 
    abnormal;
3) Evaporator ailter is dirty.

3s off 
blink 
once

3s off 
blink 
twice

1

2

Pls refer to trouble shooting (air 
exhaust protection, overload)

3

E4

Cooling, dehumidifying: compressor, 
outdoor fan motor will stop running, 
indoor fan motor works. Heating: all 
stop running.

3s off 
blink 
four 
times

■ □

1) Forcibly lift up the panel at a specific angle from the two 
    ends of the front panel following the arrow direction. 
    Then pull the air filter downwards to remove it. (Fig.a)

2) Mount the healthy filter onto the air filter, (Fig.b). If the air 
    filter cannot be installed, please mount the healthy filter 
on the front case. (Fig.c)

3) Mount the air filter properly along the arrow direction in 
    Fig.d, and then close the panel cover.

TROUBLE SHOOTING

4

1) Power supply is not stable, 
    fluctuation is too much;
2) Power supply is too low, 
    overload is too much.

Cooling, dehumidifying: compressor, 
outdoor fan motor will stop, indoor 
fan will work. Heating: all will stop.

Off 3s 
blink 
5 times

E5

5

Please refer to trouble shooting.

Cooling: compressor will stop,
indoor fan motor works. Heating:
all will stop.

E6

Off 3s 
blink 
6 times

□ ☆

6

■ □

Please refer to trouble shooting.

Cooling: compressor will stop,
indoor fan motor works. Heating:
all will stop.

Off 3s 
blink 
8 times

E8

H6

Off 3s 
blink 
11 
times

Whole unit will stop to run.

1) Poor insert for GPF;
2) Indoor control board API 
    malfunction;
3) Indoor motor M1 malfunction.

7

C5

Off 3s 
blink 
15 
times

Whole unit will stop to run.

Indoor control board
APl jump cap poor connected,
please pull and then or replace
the jump cap.

8

1) Room temp. sensor is not 
    connected with the control 
    panel AP1;
2) Room temp. sensor is damaged.

Cooling, dehumidifying: indoor fan 
motor is running, other overloads
will stop. Heating: whole unit will 
stop to run.

Off 3s 
blink 
once

F1

9

Protection 
malfunction 
status

System high 
pressure 
protection

Anti-freezing 
protection

Compressor 
air exhaust 
high temp. 
protection

AC overload
protection

Indoor and 
outdoor units
communication 
malfunction

Anti-high tcmp.
protection

Indoor unit 
motor no 
feedback

Jump wire cap
mal function
protection

Indoor ambient
sensor open
circuit,
short circuit

Indoor 
evaporator
sensor circuit,
open, short 
circuit

F2

Off 3s 
blink 
twice

Cooling, dehumidifying: indoor fan 
motor running, other overload will 
stop. Heating: whole unit will stop.

1) Tube temp. sensor is not 
    connected with the control panel 
    AP1;
2) Tube temp. sensor is damaged.

10

Air filter 
enhanced

Ion carbon cold 
catalyst

Enhanced

Fig.a

Fig.b

Fig.c

Fig.d

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

Содержание WMMS-09K-V2A(57)2

Страница 1: ...in material and workmanship for normal use and maintenance Installation operation maintenance and service shall follow professional practices for regular cooling and heating equipment NEC State City...

Страница 2: ...etails may vary and some may be the key to determine the success and quality of the installation Experience with certain manufacturer may not be applied fully to another manufacturer For example wirin...

Страница 3: ...s and wires are to be installed 11 If all the suggestions have been taken and all the necessary steps are followed CUSTOMER AND TECHNICIAN MUST READ The cost of not having your unit installed properly...

Страница 4: ...rical power V Ph Hz measured at wiring terminal block of Indoor unit outdoor unit 7 Wire gauge length and terminal colors between circuit breaker disconnect switch to outdoor unit 9 The size of HVAC c...

Страница 5: ...rience or professional knowledge to correct the problem RECEIVING AND FREIGHT DAMAGE ATTENTION Freight package unit shall be checked thoroughly for damage at receiving before accepting by signing on t...

Страница 6: ...help you in the following steps in sequence from 1 to 3 CUSTOMER AND TECHNICIAN MUST READ If the damage is minor or partial that you choose to accept you can contact the distributor or YMGI to discus...

Страница 7: ...Customer Request to Ship Products to YMGI Service Center for Inspection and Repair and Authorization to Charge form 2 You will review the form and fill all fields appropriately sign and send back to t...

Страница 8: ...ons of general up flow condensing units are limited such as apartments condos lofts multi families and high rise buildings and others named or unnamed Indoor unit s delivers the thermal and acoustical...

Страница 9: ...6 7 25 3 5 3 6 7 x 30 1 8 18 Cooling Speed SH H M L RPM 1300 1100 900 700 1350 1150 950 750 1400 1150 1000 850 1350 1150 1000 850 19 Heating Speed SH H M L RPM 1300 1140 980 820 1350 1190 1020 850 145...

Страница 10: ...s can be installed on a wall or balcony close to the indoor unit the following are some benefits for contractors and customers Each system is thoroughly tested before leaving the factory Each unit is...

Страница 11: ...27 6 37 9 37 6 Model 09K 12K 18K 24K Unit W 30 30 35 0 35 0 D1 12 6 21 3 11 3 12 6 21 3 11 3 15 6 22 0 22 0 14 3 14 3 15 6 D 10 1 10 1 13 4 13 4 P20 OF 44 USER NOTES AND SERVICE LOG 6 6 12 100 6 20 12...

Страница 12: ...Tape Level Flash Light Screw Driver Phillps and Flat Hammer Knife Scissors Goggled Glass Mask Gloves Ladder 2 Refrigeration Related Work RECOMMENDED TOOLS FOR INSTALLATION 3 Electrical Related Instal...

Страница 13: ...ors are to be used make sure to keep the two holes close to each other at least 2 inches apart Mounting plate should be attached to the structural part of the wall Minimum clearance as shown below is...

Страница 14: ...in condensing unit othewise condensate may ice up causing damage to the condensing unit Suggest to use YMGI provided brackets and condensate drainage fitting accessories Indoor unit front Bottom the r...

Страница 15: ...perpendicular to the pipe surface Don t cut too fast or too hard Turn and tighten the tube cutter slowly Remove residual left and de bur at the cutting edge The cutting edge should be clear and clean...

Страница 16: ...ation securely on the external wall with proper clamps at 6 feet apart Fill the gap between the wall hole and wall sleeve with putty to keep from rain or dust entering inside PIPING GUIDE Set the pack...

Страница 17: ...frigerant Charge Level Reference Temperature Pressure Table Split Condensing Unit R410A AC Product Series YMGI Group Mini Split Version 01 11 2010 Reference Temperature Pressure Table Split Condensing...

Страница 18: ...ng indoor fan motor works Heating all stop running 3s off blink four times 1 Forcibly lift up the panel at a specific angle from the two ends of the front panel following the arrow direction Then pull...

Страница 19: ...e is not staable cooling dehumidifying compressor will stop indoor fan motor works Heating all will stop 1 Check the Input voltage if the Voltage is lower than 150VAC restart the machine when the powe...

Страница 20: ...protection Heating LED Off 3S Blinks 6 times HE Compressor de managet protection rotor locked doesn t rotate Heating LED Off 3S Blinks 14 times L0 Airflow switch error TBD L1 Humidity sensor error TB...

Страница 21: ...uring gas sensor error Running LED Off 3S Blinks 21 times HP Solar AC solar power input voltage is higher than 180V TBD dA AHU or RT discharge air relative humidity sensor error TBD dE AHU or RT fresh...

Страница 22: ...r Cooling LED Off 3S Blinks 7 times FC Slide door error or air louver mechanism error TBD FE Over load sensor error TBD H8 Water level high overflow protection Heating LED Off 3S Blinks 8 times H9 Ele...

Страница 23: ...the unit and or know more details than anybody else They will check the unit and find out the problems with the professional knowledge about HVAC and electric product installation by using special to...