INSTALLATION-INDOOR UNIT

INSTALLATION-INDOOR UNIT

REFIT DRAIN HOSE FROM THE RIGHT TO THE LEFT SIDE     

If drain hose needs to be refitted from the original 
position (right side) to left side of the indoor unit, 
careful handling is very necessary. 

Refitting method: remove the drain hose from 
original position, without breaking hose. Unplug 
the plug at the left side. Apply water-resistant glue 
to fit the drain hose and the fitting before securing 
it.
Apply water-resistant glue onto the plug and fit it 
back into the condensate connection at right side. 

NOTES: May use some sort of clamp to double secure connections.

Alternative condensate 

connection at left side

Drain hose

HANG INDOOR UNIT 

Run copper set/wire cables/drain hose through the 
wall hole and hang the indoor unit onto the 
mounting plate (place the hook on the mounting 
plate into the hanging rib at rear side of plastic 
casing).

Snap the plastic casing bottom into the mounting 
plate, gently .

To drain the condensate easily, the drain hose should be inclined downward (pitched towards drain direction 
1/4" per foot).
Figures below from the 2nd to 5th show some incorrect 

.

practices

Drain hose may be extended using the hose coming with the installation list.

SHAPE THE DRAIN HOSE

STUFF AND SEAL THE HOLE FOR COPPER LINE SET/WIRE CABLE/DRAIN HOSE 

* Use putty to seal the wall hole.
* Use clamp (pipe fastener) to secure the pipe at specified position.

>

1

8

"

>

1

8

"

Other Brackets

Heavy-Duty PVC Riser

for Ground Mounting

Coated Brackets 
with Accessories       

Bracket Accessories

(Optional) 

Strongly suggest to install the outdoor unit above the ground either on platform or brackets as shown below. 

Heat pump unit must be lift up from ground level, since condensate must be drained out of the drain pan in 
condensing unit; othewise, condensate may ice up causing damage to the condensing unit.

Suggest to use YMGI-provided brackets and condensate drainage fitting accessories.

Indoor unit
front

Bottom

the rib of indoor unit

the mounting plate

Slice the 
insulation 
before 
bending.     

Hold the 90 
degree bend 
root, bend one 
tube one time, 
slowly, no 
quicker than 
10 seconds/
90 degree 
bend.

* If pipes need to come out of the rear side (facing 
  the front of indoor unit) of the indoor unit, no need 
  to snap off anything.

* If pipes need to be rerouted to a different direction 
  from the one preset at factory (towards left side, if 
  facing the front cover of indoor unit), lay down the 
  indoor unit on soft cushion or foam. Don't rub the 
  plastic casing.

* In order to keep from pipe damage, need to bend 
  the copper tubing set gently and slowly (finish 
  bending no less than 10 seconds/90 degree), by 
  holding at the root of the original 90 degree bend 
  nicely and firmly. Don't rub two copper lines during 
  bending. Better to cut off the insulation and bend 
  the two pipes one by one, not two together.

PREPARE INDOOR UNIT- COPPER LINE SET/DRAIN HOSE

INSTALL DRAIN PIPE AT INDOOR

The drain hose must be placed beneath the copper 
pipes and MUST NOT be hunched or bended 
sharply.                                                 

Do not pull the drain hose too hard, otherwise it 
may get broken.

Before passing drain hose through the hold, wrap 
with insulation to keep from possible damage.

The copper pipe and the drain hose must be 
wrapped by piping wrap. 

Insulation pad should be used where the pipe 
contacts the wall.

Drain hose coming with indoor unit

Drain hose extending to drain line

2 in or less
from floor

dip hose in water

water 
leak

standing
water

air

water 
leak

rise up

water 
leak

decline 
downward

Sealed with putty

Secure the piping/
wiring set with clamp

Trim the extra portion

Indoor unit

Screw

Clamp

INSTALLATION-OUTDOOR UNIT

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World !

Содержание WMMS-09K-V2A(57)2

Страница 1: ...in material and workmanship for normal use and maintenance Installation operation maintenance and service shall follow professional practices for regular cooling and heating equipment NEC State City...

Страница 2: ...etails may vary and some may be the key to determine the success and quality of the installation Experience with certain manufacturer may not be applied fully to another manufacturer For example wirin...

Страница 3: ...s and wires are to be installed 11 If all the suggestions have been taken and all the necessary steps are followed CUSTOMER AND TECHNICIAN MUST READ The cost of not having your unit installed properly...

Страница 4: ...rical power V Ph Hz measured at wiring terminal block of Indoor unit outdoor unit 7 Wire gauge length and terminal colors between circuit breaker disconnect switch to outdoor unit 9 The size of HVAC c...

Страница 5: ...rience or professional knowledge to correct the problem RECEIVING AND FREIGHT DAMAGE ATTENTION Freight package unit shall be checked thoroughly for damage at receiving before accepting by signing on t...

Страница 6: ...help you in the following steps in sequence from 1 to 3 CUSTOMER AND TECHNICIAN MUST READ If the damage is minor or partial that you choose to accept you can contact the distributor or YMGI to discus...

Страница 7: ...Customer Request to Ship Products to YMGI Service Center for Inspection and Repair and Authorization to Charge form 2 You will review the form and fill all fields appropriately sign and send back to t...

Страница 8: ...ons of general up flow condensing units are limited such as apartments condos lofts multi families and high rise buildings and others named or unnamed Indoor unit s delivers the thermal and acoustical...

Страница 9: ...6 7 25 3 5 3 6 7 x 30 1 8 18 Cooling Speed SH H M L RPM 1300 1100 900 700 1350 1150 950 750 1400 1150 1000 850 1350 1150 1000 850 19 Heating Speed SH H M L RPM 1300 1140 980 820 1350 1190 1020 850 145...

Страница 10: ...s can be installed on a wall or balcony close to the indoor unit the following are some benefits for contractors and customers Each system is thoroughly tested before leaving the factory Each unit is...

Страница 11: ...27 6 37 9 37 6 Model 09K 12K 18K 24K Unit W 30 30 35 0 35 0 D1 12 6 21 3 11 3 12 6 21 3 11 3 15 6 22 0 22 0 14 3 14 3 15 6 D 10 1 10 1 13 4 13 4 P20 OF 44 USER NOTES AND SERVICE LOG 6 6 12 100 6 20 12...

Страница 12: ...Tape Level Flash Light Screw Driver Phillps and Flat Hammer Knife Scissors Goggled Glass Mask Gloves Ladder 2 Refrigeration Related Work RECOMMENDED TOOLS FOR INSTALLATION 3 Electrical Related Instal...

Страница 13: ...ors are to be used make sure to keep the two holes close to each other at least 2 inches apart Mounting plate should be attached to the structural part of the wall Minimum clearance as shown below is...

Страница 14: ...in condensing unit othewise condensate may ice up causing damage to the condensing unit Suggest to use YMGI provided brackets and condensate drainage fitting accessories Indoor unit front Bottom the r...

Страница 15: ...perpendicular to the pipe surface Don t cut too fast or too hard Turn and tighten the tube cutter slowly Remove residual left and de bur at the cutting edge The cutting edge should be clear and clean...

Страница 16: ...ation securely on the external wall with proper clamps at 6 feet apart Fill the gap between the wall hole and wall sleeve with putty to keep from rain or dust entering inside PIPING GUIDE Set the pack...

Страница 17: ...frigerant Charge Level Reference Temperature Pressure Table Split Condensing Unit R410A AC Product Series YMGI Group Mini Split Version 01 11 2010 Reference Temperature Pressure Table Split Condensing...

Страница 18: ...ng indoor fan motor works Heating all stop running 3s off blink four times 1 Forcibly lift up the panel at a specific angle from the two ends of the front panel following the arrow direction Then pull...

Страница 19: ...e is not staable cooling dehumidifying compressor will stop indoor fan motor works Heating all will stop 1 Check the Input voltage if the Voltage is lower than 150VAC restart the machine when the powe...

Страница 20: ...protection Heating LED Off 3S Blinks 6 times HE Compressor de managet protection rotor locked doesn t rotate Heating LED Off 3S Blinks 14 times L0 Airflow switch error TBD L1 Humidity sensor error TB...

Страница 21: ...uring gas sensor error Running LED Off 3S Blinks 21 times HP Solar AC solar power input voltage is higher than 180V TBD dA AHU or RT discharge air relative humidity sensor error TBD dE AHU or RT fresh...

Страница 22: ...r Cooling LED Off 3S Blinks 7 times FC Slide door error or air louver mechanism error TBD FE Over load sensor error TBD H8 Water level high overflow protection Heating LED Off 3S Blinks 8 times H9 Ele...

Страница 23: ...the unit and or know more details than anybody else They will check the unit and find out the problems with the professional knowledge about HVAC and electric product installation by using special to...

Отзывы: