5.6.6.5
Counter output channel
Each counter has an output channel. You pre-define the behavior of the counter output
via the parametrization:
n
no comparison:
–
The output is used as normal output.
–
SFB 47:
The input parameter CTRL_DO is effect less.
The status bits STS_DO and STS_CMP (status comparator in the instance DB)
remain reset.
n
Counter value
³
comparison value respectively counter value
£
comparison value
–
The output remains set as long as the counter value is higher or equal
compar-
ison value
respectively lower or equal
comparison value
.
–
SFB 47:
Control bit CTRL_DO must be set.
The comparison result is shown by the status bit STS_CMP. This status bit may
only be reset if the comparison condition is no longer fulfilled.
n
Pulse at comparison value
–
When the counter reaches the
comparison value
the output is set for the parame-
trized
pulse duration
. When you've set a main counting direction the output is only
set at reaching the
comparison value
from the main counting direction.
If the
pulse duration
= 0, the output is set until the comparison condition is not
longer fulfilled.
–
SFB 47:
Control bit CTRL_DO must be set.
The status of the digital output may be shown by the status bit ST_DO.
The comparison result is shown by the status bit STS_CMP. The bit may only be
reset if the
pulse duration
has expired.
n
Pulse duration
–
The
pulse duration
starts with the setting of the according digital output.
–
The inaccuracy of the
pulse duration
is less than 1ms.
–
There is no past triggering of the
pulse duration
when the
comparison value
has
been left and reached again during pulse output.
–
If the
pulse duration
is changed during operation, it will take effect with the next
pulse.
–
If the
pulse duration
= 0, the output is set until the comparison condition is not
longer fulfilled.
–
Range of values: 0...510ms in steps of 2ms
5.6.6.6
Hysteresis function
n
The
hysteresis
serves the avoidance of many toggle processes of the output and the
interrupt, if the
counter value
is in the range of the
comparison value
.
n
For the
hysteresis
you may set a range of 0 to 255.
n
The settings 0 and 1 deactivate the
hysteresis
.
n
The
hysteresis
influences zero run, comparison, over- and underflow.
n
An activated
hysteresis
remains active after a change. The new
hysteresis
range is
activated with the next
hysteresis
event.
The following pictures illustrate the output behavior for
hysteresis
0 and
hysteresis
3 for
the according conditions:
Characteristics of the
output
Hysteresis
VIPA System MICRO
Deployment I/O periphery
Counting > Counter - Additional functions
HB400 | CPU | M13-CCF0000 | en | 16-47